This is a study on the insulation methods of home appliances and wiring devices proper to the new electric distribution system, primary side is 22.9/13.2KV, 3 phase 4 wire multigrounding system and secondary side is 380/220V, 3 phase 4 wire common neutral system. 1800V is determined as the electrical insulation voltage of the functional insulation because the abnormal voltage rise of the neutral line is 1300V. In the case of the functional insulation faults, the following safety methods will be suggested to protect the accidental faults: (a) class I appliance (accessible metal part is earthed), (b) class II appliance (doublly insulated), (c) class III appliance (operates at low voltage source). The mechanisms of the wiring devices are not improved to guarantee for the harmful electric shock but also the electrical insulation voltage is rised to 2000V.