• Title/Summary/Keyword: pole-transformer

Search Result 108, Processing Time 0.03 seconds

A study for the overload and fault protective device of pole transformers (주상변압기 과부하 및 고장보호장치 개발에 관한연구)

  • Choi, Bong-Il;Lim, Chang-Ho;Kim, Chang-Kyung;Kim, Young-Rae;Song, Il-Keun
    • Proceedings of the KIEE Conference
    • /
    • 1992.07a
    • /
    • pp.67-69
    • /
    • 1992
  • This paper presents the new protective device which is developed specifically for use in oil filled distribution transformers. This device is mounted Inside of the transformer and connected between the secondary winding and the secondary bushings. It provides both fault and overload protection to the transformer, and visual warning of the existence of uneconomical loading conditions. It Is available in thermal/magnetic operating device depending upon fault duty required.

  • PDF

Short-Term Load Forecasting of Transformer Using Artificial Neural Networks (신경회로망을 이용한 변압기의 단기부하예측)

  • Kim, Byoung-Su;Song, Kyung-Bin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.7
    • /
    • pp.20-25
    • /
    • 2005
  • In this paper, the short-term load forecasting of transformers is performed by artificial neural networks. Input parameters of the proposed algorithm are peak loads of pole-transformer of previous days and their maximum and minimum temperatures. The proposed algorithm is tested for one of transformers in Seoul, Korea. Test results show that the proposed algorithm improves the accuracy of the load forecasting of transformer compared with the conventional algorithm. The reposed algorithm can help to prevent some damages by over-loads of transformers.

Optimized Synthetic Making Test Facilities for Estimating the Making Performance of Circuit Breaker (차단기의 투입성능 평가를 위한 최적 합성투입시험설비)

  • Suh Yoon-Taek;Kim Maeng-Hvun;Song Won-Pyo;Koh Hee-Seog;Park Seung-Jae
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.54 no.6
    • /
    • pp.284-292
    • /
    • 2005
  • Because all of the short-circuit testing laboratories have the limitation of test facilities, the synthetic making test methods have been used to estimate the short-circuit making performance of the ultra high-voltage circuit breaker as the alternative to direct test methods. So, KERI(Korea Eelctrotechnology Research institute) has completed the construction of the synthetic making test facilities using the low capacity step-up transformer method which fulfill the requirements specified in newly revised IEC 62271-100 Edition 1.1(2003) and have the testing capability up to 550kV, 63kA full-pole circuit breaker. The test facilities using the low capacity step-up transformer method presented in this paper are made up of the unit equipments such as HCS(High-speed Closing Switch), ITMC(Initial Transient Making Current) circuit and UP TR(low capacity step-up transformer) and have the operating range of 17.6$^{\circ}$ $\~$ 145.1$^{\circ}$ for testing the circuit breaker rated on up to 50kA and 43.1$^{\circ}$ $\~$ 119.6$^{\circ}$ for more than 50kA.

Practical Design Methodology of Dual Active Bridge Converter as Isolated Bi-directional DC-DC Converter for Solid State Transformer (Solid State Transformer를 위한 양방향 Dual Active Bridge DC-DC 컨버터의 설계 기법)

  • Choi, Hyun-Jun;Lee, Won-Bin;Jung, Jee-Hoon
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.22 no.2
    • /
    • pp.102-108
    • /
    • 2017
  • Proper design guides are proposed for a practical dual-active bridge (DAB) converter based on the mathematical model on the steady state. The DAB converter is popular in bidirectional application due to its zero-voltage capability and easy bidirectional operation for seamless control, high efficiency, and performance. Some design considerations are taken to overcome the limitation of the DAB converter. The practical design methodology of power stage is discussed to minimize the conduction and switching losses of the DAB converter. Small-signal model and frequency response are derived and analyzed based on the generalized average method, which considers equivalent series resistance, to improve the dynamics, stability, and reliability with voltage regulation of the practical DAB converter. The design of closed-loop control is discussed by the derived small-signal model to obtain the pertinent gain and phase margin in steady-state operation. Experimental results of a 3.3 kW prototype of DAB converter demonstrate the validity and effectiveness of the proposed methods.

A Study on Preventive Diagnosis of the Pole Transformer by Gas Analysis -Measurement of Aging of Insulating Oil by UV-Visible Spectrophotometric Method- (개스분석에 의한 주상변압기의 예방진단에 관한 연구 -자외-가시선 흡수분광광도법에 의한 절연유의 열화도 측정-)

  • 곽희로;남영우;윤영자;남궁미옥;이동준
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.10 no.5
    • /
    • pp.94-100
    • /
    • 1996
  • Criteria for insulating oil condition of pole transformer were suggested by applying the UV-Visible spectrophotometric method. Aging of insulating oil caused the change in absorbances of oil as well as the deterioration of electrical properties of oil. By comparing the electrical properties such as tan$\delta$ and dielectric breakdown voltage with the UV-Visible absorbances of oil, following criteria for absorbance values determining oil condition were established, fair condition is below 0.580, need attention is 0.580-0.900 and poor condition is above 0.900. This W-Visible spectrophotometric method may be applied in aging analysis of oil and expected to replace the current visual method. It is necessary to develop cheap, light and portable UV-Visible spectrophotometer in near future for field application.

  • PDF

Adjustment of load correlation coefficient for advanced load management (부하관리 개선을 위한 부하 상관계수 산정에 관한 연구)

  • Park, Chang-Ho;Cho, Seong-Soo;Kim, Gi-Hyun;Im, Jin-Soon;Kim, Du-Bong;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 1999.07c
    • /
    • pp.1267-1269
    • /
    • 1999
  • This paper studies on arrangement of load correlation coefficient for advanced load management. To accurate load correlation coefficient, we used two real factors, electrical energy(kWh) and peak load current of pole transformers, acquired by measuring instrument. Out of several correlation equations, we find that the quadratic equation is the most accurate to express peak load current and working electrical energy. If the data is located in the outside of ${\pm}3{\sigma}$ it is discarded. For load management, we rearranged load correlation coefficient considering +2${\sigma}$ at load correlation equation. Comparing conventional load correlation coefficient with rearranged one, we can get the result of error reduced and it is adjacent to the actual data. It will be used peak load forecasting from working electrical energy and we are able to prevent from the damaging of pole transformer due to overload.

  • PDF

Improvement Method of SVR Control in Power Distribution System Interconnected Distributed Generator (분산전원이 연계된 배전계통에 있어서 선로전압조정장치(SVR)의 전압제어 개선방안)

  • Lee, Hyun-Ok;Huh, Jae-Sun;Kim, Byung-Ki;Rho, Dae-Seok;Kim, Jae-Chul
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.2
    • /
    • pp.224-229
    • /
    • 2014
  • This paper presents the novel voltage control method in power distribution system with distributed generators. The voltage in distribution systems is regulated by Under Load Tap Changer(ULTC) of substation and pole transformer of primary feeders. Recently, Step Voltage Regulator(SVR) is getting located at distribution feeders to regulate effectively voltage of primary feeders. But the effectiveness of SVR decreases due to independent operation between SVR and ULTC, and also the existing Line Drop Compensator(LDC) method considering the distributed generators may be not able to regulate the proper voltage in a permissible range. Thus, this paper presents a optimal voltage control algorithm of SVR by using the secondary voltage data of main transformer in substation.

The Temperature Distribution Analysis and Temperature Rise Test of Pole Mold Transformer (초고압 현수애자의 Pin 형상에 따른 응력해석)

  • Cho, Han-Goo;Park, Ki-Hoo;Han, Se-Won;Yun, Mun-Su
    • Proceedings of the KIEE Conference
    • /
    • 2001.11a
    • /
    • pp.155-157
    • /
    • 2001
  • Various types suspension insulators made of toughness glass or porcelain are used in the power transmission. And, Insulators are continually subject to mechanical and electrical stresses which depend on the characteristics of the line. The main factor that influence the increase in reliability of insulators. In operation is the capacity of the design to withstand the certain load over a long time, the mechanical strength of the insulators. This paper describes the results of a study on the stress analysis of suspension insulator based on the finite element analysis using NASTRAN. And, the mechanical strength was evaluated through such as kinds of pin type.

  • PDF

Prediction of Characteristics Life of the Rubber Gasket (가스켓용 고무소재의 특성수명 예측)

  • Park, Joon-Hyung;Lee, Se-Hee;Jang, Hyun-Duck;Kim, Gwang-Sub;Yang, Jeong-Sam
    • Journal of Applied Reliability
    • /
    • v.10 no.4
    • /
    • pp.213-235
    • /
    • 2010
  • In this paper, we carried out an accelerated degradation test that is commonly used to predict characteristics life of rubber gaskets for a pole transformer. The potential failure mode applied for the test is rubber elongation and the corresponding failure mechanism is heat. From the result, we found that Weibull distribution is the fatigue life distribution in NBR and H-NBR. After estimating characteristics life in commonly used temperature, the average life span of $B_{50}$ in NBR is 7.7 years under $50^{\circ}C$ and the life span in H-NBR is 28 years.

Life Loss of Pole Mounted Transformers by Thermal Aging (열 열화에 의한 주상변압기의 수명 손실)

  • Joung, Jong-Man;Lee, Byeong-Seong;Song, Il-Kewon
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.209-213
    • /
    • 2005
  • To enhance the reliability of distribution transformers in service and to reduce the cost of maintaining and replaceing these, the condition and life of those insulating system should be evaluated accurately and the time to replace should be determined economically. Since the transformer failures related to insulation failure indicates that the primary cause is normally mechanical failure of integrity due to loss of mechanical strength as a result of degradation, the tensile strength characteristics of paper during ageing under accelerated conditions in insulating oil and research trends for assessing the life of insulating paper were investigated.

  • PDF