Optimized Synthetic Making Test Facilities for Estimating the Making Performance of Circuit Breaker

차단기의 투입성능 평가를 위한 최적 합성투입시험설비

  • Published : 2005.06.01

Abstract

Because all of the short-circuit testing laboratories have the limitation of test facilities, the synthetic making test methods have been used to estimate the short-circuit making performance of the ultra high-voltage circuit breaker as the alternative to direct test methods. So, KERI(Korea Eelctrotechnology Research institute) has completed the construction of the synthetic making test facilities using the low capacity step-up transformer method which fulfill the requirements specified in newly revised IEC 62271-100 Edition 1.1(2003) and have the testing capability up to 550kV, 63kA full-pole circuit breaker. The test facilities using the low capacity step-up transformer method presented in this paper are made up of the unit equipments such as HCS(High-speed Closing Switch), ITMC(Initial Transient Making Current) circuit and UP TR(low capacity step-up transformer) and have the operating range of 17.6$^{\circ}$ $\~$ 145.1$^{\circ}$ for testing the circuit breaker rated on up to 50kA and 43.1$^{\circ}$ $\~$ 119.6$^{\circ}$ for more than 50kA.

Keywords

References

  1. A. Balossi, M. Malaguti, and P. Ostano, 'Laboratory full-scale tests for the determination of the secondary arc extinction time in high speed reclosing,' IEEE Conference Summer Power Meeting, New Orleans, No. CP-66-382, 1996
  2. A.D. Strokes and S. Rovelli, 'Balanced synthetic circuit: new circuit for high-power testing with low frequency transient recovery voltage,' IEEE Proceedings. No.3, pp. 184-190, 1975
  3. R. Ballada, 'A new fast and high current making switch for synthetic testing,' AIta Frequenza, No.2, pp. 107-111, February 1975
  4. R. Ballada, 'A fast high current making-switch for synthetic testing of circuit breakers,' Reprinted from Energy Storage, Compression and Switching, 1976
  5. S. Managanaro, and H. H. Schramm, 'Application of synthetic auto-reclosing circuit for testing high-voltage circuit-breakers,' IEEE Transactions, Vol. PAS-99, No.6, pp. 2223-2231, 1980 https://doi.org/10.1109/TPAS.1980.319852
  6. S. Manganaro, 'New developments in synthetic testing technique,' International Workshop on HV-Switchgear, Bangalore, India, pp. 18-19, 1985
  7. G. AIdrovandi, I. Bonfanti, G. Kuhnhardt, and H. PIiet, 'Development and application of new synthetic circuits in CESI and IPH,' CIGRE Report 13-201, 1992
  8. L. Vander Sluis, G.C. Damster, H.W. Kempen, and W.A. Vander Linden, 'Synthetic test methods : Experience and future developments,' CIGRE Report 30, 1992
  9. S. Managanaro, G. Mazza, and S. Rovelli, 'Some problems encountered in the evaluation of the stresses on high voltage circuit breakers during making operations on a short circuit,' CIGRE Report SC No. 13, 1977
  10. IEC60056/FDIS, 2001 : IEC-High voltage alternating current circuit breaker
  11. IEC 60427, 2000 : IEC-Synthetic testing high voltage alternating current circuit breaker
  12. lEC 62271-100 Edition 1.1, 2003 : lEC-High voltage alternating current circuit breaker