• 제목/요약/키워드: Three-phase four wire system

검색결과 71건 처리시간 0.023초

Series Active Power Filters to Compensate Harmonics and Reactive Power with the Direct Compensating Voltage Extraction Method in Three-Phase Four-Wire Systems

  • Kim, Jin-Sun;Kim, Young-Seok
    • Journal of Power Electronics
    • /
    • 제9권5호
    • /
    • pp.691-699
    • /
    • 2009
  • This paper presents the analysis of series active power filter for reactive power compensation, load balancing, harmonic elimination, and neutral current eradication in three-phase four-wire power systems. Generally, the three-phase four-wire system is widely employed in distributing electric energy to several office building and manufacturing plants. In such systems, the third harmonic and its 3rd harmonics are termed as triple and zero sequence components that do not cancel each other in the system neutral. Consequently, the triple harmonics add together creating a primary source of excessive neutral current. Regarding this concern, this paper presents a new control algorithm for a series hybrid active system, whereas the control approach it adopts directly influence its compensation characteristics. Hence, the advantage of this control algorithm is the direct extraction of compensation voltage reference without phase transformations and multiplying harmonic current value by gain and the required rating of the series active filter is much smaller than that of a conventional shunt active power filter. In order to show the effectiveness of the proposed control algorithm, experiments have been carried out.

A Simplified Control Algorithm for Three-Phase, Four-Wire Unified Power Quality Conditioner

  • Singh, Bhim;Venkateswarlu, P.
    • Journal of Power Electronics
    • /
    • 제10권1호
    • /
    • pp.91-96
    • /
    • 2010
  • In this paper, a simplified control algorithm for a three-phase, four-wire unified power quality conditioner (UPQC) is presented to compensate for supply voltage distortions/unbalance, supply current harmonics, the supply neutral current, the reactive power and the load unbalance as well as to maintain zero voltage regulation (ZVR) at the point of common coupling (PCC). The UPQC is realized by the integration of series and shunt active filters (AFs) sharing a common dc bus capacitor. The shunt AF is realized using a three-phase, four leg voltage source inverter (VSI) and the series AF is realized using a three-phase, three leg VSI. A dynamic model of the UPQC is developed in the MATLAB/SIMULINK environment and the simulation results demonstrating the power quality improvement in the system are presented for different supply and load conditions.

A Novel Three-Phase Four-Wire Grid-Connected Synchronverter that Mimics Synchronous Generators

  • Tan, Qian;Lv, Zhipeng;Xu, Bei;Jiang, Wenqian;Ai, Xin;Zhong, Qingchang
    • Journal of Power Electronics
    • /
    • 제16권6호
    • /
    • pp.2221-2230
    • /
    • 2016
  • Voltage and frequency stability issues occur in existing centralized power system due to the high penetration of renewable energy sources, which decrease grid absorptive capacity of them. The grid-connected inverter that mimics synchronous generator characteristics with inertia characteristic is beneficial to electric power system stability. This paper proposed a novel three-phase four-wire grid-connected inverter with an independent neutral line module that mimics synchronous generators. A mathematical model of the synchronous generator and operation principles of the synchronverter are introduced. The main circuit and control parameters design procedures are also provided in detail. A 10 kW prototype is built and tested for further verification. The primary frequency modulation and primary voltage regulation characteristics of the synchronous generator are emulated and automatically adjusted by the proposed circuit, which helps to supports the grid.

IGBT PWM Rectifier의 각상 개별제어 알고리즘에 관한 연구 (A Study on the Algorithm for Single Phase Control of IGBT PWM Rectifier)

  • 김승호;박재범;태동현;김승종;송중호;노대석
    • 한국산학기술학회논문지
    • /
    • 제17권4호
    • /
    • pp.26-33
    • /
    • 2016
  • 최근 UPS의 효율을 높이기 위하여 무변압기형 UPS의 사용이 증가되고 있다. 하지만 무변압기형 UPS는 입 출력 구조상 문제로 인해 3상4선식의 IGBT PWM 정류기가 필요하며 이는 기존의 3상3선식 PWM 정류기의 PFC 제어기법으로는 중성선 전류 문제로 동작이 되지 않으므로 3상4선식 PWM 정류기의 특성에 맞는 적절한 PWM 제어기법이 요구되고 있다. 3상4선식 IGBT PWM 정류기의 제어를 위한 제어기법으로는 각상 개별제어 기법과 3D SVM 기법이 있지만 두 방식 모두 장단점이 존재한다. 각상 개별제어 기법은 제어가 불안정하고 3D SVM 기법은 입력 측 인덕터의 L값이 상당히 커져야하는 문제점을 가지고 있다. 따라서 본 논문에서는 기존의 각상 개별제어 방식과 d-q 제어 알고리즘을 접목시켜 동기좌표계상에서 직류로 제어하는 3상4선식 IGBT PWM 정류기 제어기법을 제안하였다. 또한 본 논문에서 제안한 3상4선식 IGBT의 PWM 정류기 제어 알고리즘을 바탕으로 시뮬레이션과 실험을 수행 하였다. 시뮬레이션을 수행한 결과, 3상4선식 IGBT PWM 정류기를 안정적으로 제어하고 중성선 전류를 줄일 수 있어, 본 논문에서 제안한 방식의 유효성을 확인하였다.

3상 4레그 전압형 인버터를 위한 3차원 공간벡터변조 기법 (3-Dimensional SVM Technique for the Three-Phase Four-Leg Voltage Source Inverter System)

  • 도안반투안;최우진
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2013년도 추계학술대회 논문집
    • /
    • pp.111-112
    • /
    • 2013
  • The three-phase four-leg voltage source inverter (VSI) topology can be an interesting option for the three phase-four wire system. With an additional leg, this topology can handle the neutral current, hence the DC link capacitance can be reduced significantly. In this paper the three dimensional space vector modulation (3D SVM) in ${\alpha}{\beta}{\gamma}$ coordinates for the three-phase four-leg VSI is presented. By using the 3D SVM method, the DC link voltage can be reduced by 16% compared with the split DC link capacitor topology and the output distortion can also be reduced under the unbalanced load condition.

  • PDF

A Three-Phase Four-Wire DSTATCOM for Power Quality Improvement

  • Singh, Bhim;Jayaprakash, P.;Kothari, D.P.
    • Journal of Power Electronics
    • /
    • 제8권3호
    • /
    • pp.259-267
    • /
    • 2008
  • Power quality improvement in a three-phase four-wire system is achieved using a new topology of DSTATCOM (distribution static compensator) consisting of a star/delta transformer with a tertiary winding and a three-leg VSC (voltage source converter). This new topology of DSTATCOM is proposed for power factor correction or voltage regulation along with harmonic elimination, load balancing and neutral current compensation. A tertiary winding is introduced in each phase for a delta connected secondary in addition to the star-star windings and this delta connected winding is responsible for neutral current compensation. The dynamic performance of the proposed DSTATCOM system is demonstrated using MATLAB with its Simulink and Power System Blockset (PSB) toolboxes under varying loads. The capacitor supported DC bus of the DSTATCOM is regulated to the reference voltage under varying loads.

Performance Improvement of an Active Neutral Harmonic Suppressor System Under Unbalanced Load Conditions

  • Choi, Se-Wan;Jang, Min-Soo
    • Journal of Power Electronics
    • /
    • 제3권3호
    • /
    • pp.151-158
    • /
    • 2003
  • Three-phase four-wire electrical distribution systems are widely employed in manufacturing plants, commercial and residential buildings Due to the nonlinear loads connected to the distribution system, the neutral conductor carries excessive harmonic currents even under balanced loading since the triplen harmonics in phase currents do not cancel each other This may result in wiring failure of the neutral conductor and overloading of the distribution transformer In response to these concerns, a cost-effective neutral current harmonic suppressor system has been proposed. This paper proposes an improved control method for the harmonic suppressor system under unbalanced load conditions The proposed control method compensates for only the harmonic components in the neutral conductor, and the zero-sequence fundamental component due to unbalanced loading is prevented from flowing through the harmonic suppressor system This remedies overloading and power loss of the system The experimental results on a prototype validate the proposed control approach.

Switching Functions Model of a Three-phase Voltage Source Converter (VSC)

  • Fazeli, Seyed Mahdi;Ping, Hew Wooi;Abd Rahim, Nasrudin Bin;Ooi, Boon Teck
    • Journal of Power Electronics
    • /
    • 제17권2호
    • /
    • pp.422-431
    • /
    • 2017
  • The equivalent circuit of a three-leg, four-wire voltage source converter (VSC) is derived using switching functions. Simulations and experiments are conducted (i) to investigate the effects of the zero sequence on VSCs when a three-phase imbalance exists and (ii) to use the consistency of simulations and laboratory experiments to validate the equivalent circuit. The impact of a three-phase imbalance on the VSC has yet to be fully investigated because of the lack of an equivalent circuit to show rigorously how the zero sequence currents flow through the VSC.

3상 4선식 부하설비의 전압 불평형율 측정 및 분석 (The measurement & Analysis of Voltage Unbalance Factor at Three Phase Four Wire Load System)

  • 김종겸;박영진;이동주;이화수;이은웅
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 춘계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.15-17
    • /
    • 2004
  • Most of LV customer has been composed the 3-phase four wire system distribution system which is supplying simultaneously at the 1-phase & 3-phase load. In this system, the composition of the power apparatus system is simple rather than conventional separation mode of the 1-phase & 3-phase, But due to uneven load unbalance or unclean power quality, various kinds such as derating or power losses become an issue. In this paper, we measured and analyzed voltage and current waveform in the field, compared with internationally allowable voltage unbalance limits.

  • PDF

3상 4선식 저압 수용가의 전압 불평형율 측정분석 (The measurement & Analysis of Voltage Unbalance Factor at LV Customer of Three-Phase Four-Wire System)

  • 김종겸;박영진;이은웅
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.43-47
    • /
    • 2004
  • Most of LV customer has been composed the 3-phase four wire system distribution system which is supplying simultaneously at the 1-phase & 3-phase load. In this system, the composition of the power apparatus system is simple rather than conventional separation mode of the 1-phase & 3-phase, But due to uneven load unbalance or unclean power quality, various kinds such as do-rating or power losses become an issue. In this paper, we measured and analyzed voltage and current waveform in the field, compared with internationally allowable voltage unbalance limits.

  • PDF