A Three-Phase Four-Wire DSTATCOM for Power Quality Improvement

  • Singh, Bhim (Dept. of Electrical Engineering, Indian Institute of Technology) ;
  • Jayaprakash, P. (Dept. of Electrical Engineering, Indian Institute of Technology) ;
  • Kothari, D.P. (Vellore Institute of Technology)
  • Published : 2008.07.20

Abstract

Power quality improvement in a three-phase four-wire system is achieved using a new topology of DSTATCOM (distribution static compensator) consisting of a star/delta transformer with a tertiary winding and a three-leg VSC (voltage source converter). This new topology of DSTATCOM is proposed for power factor correction or voltage regulation along with harmonic elimination, load balancing and neutral current compensation. A tertiary winding is introduced in each phase for a delta connected secondary in addition to the star-star windings and this delta connected winding is responsible for neutral current compensation. The dynamic performance of the proposed DSTATCOM system is demonstrated using MATLAB with its Simulink and Power System Blockset (PSB) toolboxes under varying loads. The capacitor supported DC bus of the DSTATCOM is regulated to the reference voltage under varying loads.

Keywords

References

  1. E.Acha, V.G. Agelids, O. Anaya-Lara, T.J.E. Miller, Power Electronic Control in Electric Systems, Newness Power engineering series, 1st Edition, Oxford, 2002
  2. A.Ghosh and G. Ledwich, Power Quality Enhancement using Custom Power devices, Kluwer Academic Publishers, London, 2002
  3. R. C. Dugan, M. F. McGranaghan and H. W. Beaty, Electric Power Systems Quality. 2ed Edition, McGraw Hill, New York, 2006
  4. H. Akagi, E. H. Watanabe and M. Aredes, Instantaneous power theory and applications to power conditioning, John Wiley & Sons, New Jersey, USA, 2007
  5. Antonio Moreno-Munoz, Power Quality: Mitigation Technologies in a Distributed Environment, Springer-Verlag London limited, London, 2007
  6. IEEE Recommended Practices and Requirements for Harmonics Control in Electric Power Systems, IEEE Std. 519, 1992
  7. Electromagnetic Compatibility (EMC) - Part 3: Limits- Section 2: Limits for harmonic current emissions (equipment input current <16 A per phase), IEC1000-3-2 Document, First Edition, 1995
  8. M.C. Benhabib and S. Saadate, "New control approach for four-wire active power filter based on the use of synchronous reference frame", Electric Power Systems Research, Vol. 73, No. 3, pp. 353-362, Mar. 2005 https://doi.org/10.1016/j.epsr.2004.08.012
  9. Maria Isabel Milanes, Enrique Romero Cadaval and Fermin Barrero Gonzalez, "Comparison of Control Strategies for Shunt Active Power Filters in Three-Phase Four-Wire Systems", IEEE Transactions on Power Electronics, Vol. 22, No. 1, pp.229-236, Jan. 2007 https://doi.org/10.1109/TPEL.2006.886616
  10. Hurng-Liahng, Kuen- Der Wu, Jinn- Chang Wu and Wen- Jung Chiang, "A three-phase four- wire power filter comprising a three-phase three-wire active filter and a zig-zag transformer", IEEE Trans. of Power Electronics., Vol. 23, No. 1, pp. 252-259, Jan. 2008
  11. Sikyung Kim, Prasad N. Enjeti and Ira J. Pitel, "A New approach to improve power factor and reduce harmonics in a three-phase diode rectifier type utility interface", IEEE Trans. Ind. Applicat., Vol. 30, No. 6, pp. 1557-1564, Nov./ Dec. 1994 https://doi.org/10.1109/TIA.1994.350310
  12. P. Enjeti, W. Shireen, P. Packebush and I. Pitel, "Analysis and Design of a New Active Power Filter to Cancel Neutral Current Harmonics in Three-phase Four-Wire Electric Distribution Systems", IEEE Trans. Ind. Applicat., Vol. 30, No. 6, pp. 1565-1572, Nov./ Dec. 1994 https://doi.org/10.1109/TIA.1994.350311
  13. Steffan Hansen, Peter Nielsen and Frede Blaabjerg, "Harmonic Cancellation by mixing Non-linear single-phase and three-phase loads", IEEE Trans. Ind. Applicat., Vol.36, No.1, pp.152-159, Jan./Feb. 2000 https://doi.org/10.1109/28.821810
  14. P. Vedelho and G. D. Marques, "A neutral current electronic compensator", Proc. of IEEE Proceedings in Industrial Electronics, Vol.2, pp. 831-836, Aug/Sept 1998
  15. M.G.Molina and P.E.Mercado, "Control Design and Simulation of DSTATCOM with Energy Storage for Power Quality Improvements", in Proc. of TDC 06, pp. 1-7, Aug. 2006
  16. H. Fugita and H. Akagi, "Voltage-regulation performance of a shunt active filter intended for installation on a power distribution system", IEEE Trans. on Power Electron., Vol. 22, No.1, pp. 1046-1053, May 2007 https://doi.org/10.1109/TPEL.2007.897115