• Title/Summary/Keyword: Suspension insulator

Search Result 83, Processing Time 0.035 seconds

Insulating Characteristics of the Distribution Facilities due to Grade of Salt Contamination (오손등급에 따른 배전기자재의 절연특성 연구)

  • Kwon, Tae-Ho;Kim, Dong-Myung;Kim, Ju-Young
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1490-1491
    • /
    • 2007
  • The salt contamination on the distribution facilities, such as suspension insulator, line post insulator, lightning arrester, COS, is one of the major coastal areas because more than 90% of salt contaminated failure occurs in distribution facilities. Did to stain distribution facilities artificially according to Equivalent Salt Deposit Density(ESDD) grade. The electrical test were performed on the non-polluted and polluted facilities(ESDD B, C, D grade).

  • PDF

Reliability Evaluation Criteria and Multi-Stress Aging Test for Polymer Insulator (폴리머 현수애자의 신뢰성 평가 및 복합가속열화 방법)

  • Park, Hoy-Yul;Kang, Dong-Pil;Ahn, Myeong-Sang
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07a
    • /
    • pp.469-472
    • /
    • 2004
  • There have been numerous accelerated aging laboratory tests for evaluating suitability of polymeric materials and devices. Aging test for materials and its full scale device has been conducted, but poor correlation of aging test such as service experience were observed. Service experience plays a key role in the utility section of composite insulators. A meaningful and reliable accelerated aging test is needed for evaluating composite insulator. During the service these insulators are subjected to aging stress such as humidity, pollution, and electrical field, and erosion and tracking of the weathershed occurs. This paper presents the criteria of reliability evaluation and evaluation facilities for 22.9 kV suspension composite insulator. We adopt the criteria of reliability evaluation consist of two test methods. One is CEA tracking wheel test for examining the tracking and erosion performance of composite insulator. The other is multi-stress aging test for examining effects of environmental factors such as UV, temperature, humidity, etc on composite insulator.

  • PDF

Various Factors Influencing the Lifetime of Suspension-Type Porcelain Insulators for 154 kV Power Transmission Lines

  • Choi, In Hyuk;Park, Joon Young;Kim, Tae Gyun;Yoon, Yong Beum;Yi, Junsin
    • Transactions on Electrical and Electronic Materials
    • /
    • v.18 no.3
    • /
    • pp.151-154
    • /
    • 2017
  • In this article, we investigated the various influencing factors that degraded the lifetime of suspension insulators in 154 kV transmission lines, and showed the possible solutions to avoid such breakdowns. With respect to achieve safety, reliability and aesthetical considerations, the characteristics of transmission and distribution network power cables should be improved. Suspension insulators are particularly important to study, as they have developed to be the main component of transmission lines due to their ability to withstand the electrical conductivity of high-voltage power transmission. Suspension insulators are mostly made from glass, rubber and ceramic material due to their high resistivity. In Korea, porcelain suspension insulators are typically used in the transmission line system, as they are cheaper and more flexible compared to other types of insulators. This is effective from preventing very high and steep lightening impulse voltages from causing the breakdown of suspension insulators used in power lines. Other influential factors affect the lifetime of suspension insulators that we studied include temperature, water moisture, contamination, mechanical vibration and electrical stress.

Stress Response of Cement Interface on Manufacturing Process of a Suspension Insulator (송전선용 현수애자 양생공정에서 발생하는 접착부의 응력변화)

  • Woo, Byung-Chul;Han, See-Won;Cho, Han-Goo
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1448-1450
    • /
    • 2003
  • The suspension insulators are subjected to harsh environment in service for a long time. Long term reliability of the insulators is required for both mechanical and electrical performances. We studied an analysing method to find out a deformation of brittle porcelain with a thermal expansion of simulation analysis and experimental results show that cement volume growths affect severely to be mechanical failure ageing.

  • PDF

Failure Analysis of Porcelain Suspension Insulators for Distribution Line (배전용 자기제 현수애자의 고장 분석)

  • 김찬영;김추용;송일근;이병성;한용희
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.05a
    • /
    • pp.157-160
    • /
    • 1999
  • The paper provides the results of failure analysis for the porcelain suspension insulators. The comparisons of characteristics were made as a function of failed and unfailed isulators which had been used in real distribution line. This paper also described the failure modes which could be occurred in the fields. The cracks inside cap were detected though measuring the resistance or the leakage current. The ratio of open porosity was calculated from the Archimedes Method. The failure analyses of porcelain suspension insulators were conducted from the various analysis method.

  • PDF

Characteristic Analysis of Suspension Insulators for Distribution Line (배전용 현수애자의 특성분석)

  • 김찬영;김주용;송일근;이병성
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.13 no.3
    • /
    • pp.259-264
    • /
    • 2000
  • The paper provides the characteristic analyses of porcelain suspension insulators. The comparisons of characteristics were made as a function of failed and unfailed insulators which had ben used in the fields. This paper also describes the failure modes occurred in the fields. The aging of cement corrosion of metal breaking of shed puncture in the head and separation of glaze are different failure modes for porcelain suspension insulators. Among these failure modes the puncture breaking and glaze problems were major concerns in this research. The cracks porosities of porcelain and micro-crystals on the graze were the causes of these failures. These results were confirmed by conducting various failure analyses.

  • PDF

Performance of Polymer Suspension Insulator with Shed Profile (갓 형상에 따른 폴리머 현수애자의 열화특성)

  • Cho, H.G.;Lee, U.Y.;Kang, S.H.;Lim, K.J.;Yeo, H.G.;Ji, W.Y.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.539-542
    • /
    • 2003
  • Recently, the polymer insulators which are being used for high voltage applications have some advantages such as light weight, small size, vandalism resistance, hydrophobicity and easy making process. During outdoor service of polymer insulators, the surface of the insulating material is frequently subjected to moisture and contamination which lead to the well known phenomenon of dry band arcing. Their tracking resistance, erosion resistance, end sealing and shed design are very important because dry band arcing causes degradation of polymer surface. The shape design of porcelain insulator is formalized but design standard for polymer insulator is no standardized up to now, much research is necessary in real condition. In this paper, the aging property of polymer insulator with shed shape(regular, alternative type) is analyzed through numerical analysis, CEA(canadian electricity association) tracking wheel test and IEC 61109 Annex C.

  • PDF

Insulation coordination of 765 KV double circuit transmission line (765 KV 2 회선(回線) 송전선(送電線) 절연협조(絶緣協助))

  • Kim, Jeong-Boo;Min, Suk-Won;Lee, Dong-Il
    • Proceedings of the KIEE Conference
    • /
    • 1988.07a
    • /
    • pp.774-777
    • /
    • 1988
  • This paper covers the insulation coordination of 765 KV transmission line in Korea Electric Power Corporation. The design for the lightning, switching surge, and contamination was conducted to increase the reliability of 765 KV line. The authors have used the result of a limited Westinghouse ANACOM swiching surge study of the Korea Electric Corporation's 765 KV Expansion plan. The study investigated the switching surge overvoltage distribution and maximum switching overvoltage when relosing 765 KV lines. They used the technical data of the suspension insulator for the contamination design, which was available from a foreign insulator manufacture. From this paper, the authors find out that the contamination design dominates to determine the number of insulator and the SOV design dominates the air clearance in the tower. Afterwards the authors will confirm this design by Demonstration Test with Korea Electro-technology Research Institute.

  • PDF

Monitoring Technique and Device of Surface Contamination for Line-Post Insulator (지지애자의 표면오염 모니터링 기술 및 장치)

  • Kil, Gyung-Suk;Park, Dae-Won;Jung, Kwang-Seok;Kim, Sun-Jae;Seo, Dong-Hoan
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.5
    • /
    • pp.413-417
    • /
    • 2010
  • Line to ground faults by deterioration of insulators has frequently occurred in power system, and the main cause is surface contamination of the insulators. The contamination of insulator is analyzed by monitoring the surface leakage current flowing them. The suspension insulator is monitored by installation of a zero-phase current sensor(ZCT), but the line-post insulator is impossible to apply the same method because of its large diameter structure. This paper proposed a detection method of surface leakage current for a line-post insulator, and it can easily be applied to new and/or built insulators. The leakage current is indirectly calculated from the potential difference between the metal electrode attached on the surface of insulator and the ground connector. To evaluate the performance of the proposed method, the leakage current is compared as a function of contamination condition controlled by the density of NaCl solution. The leakage current is proportioned to the density of NaCl solution, and the voltage detected by the electrode showed the same trend. From the experimental results, we designed and fabricated a monitoring device which is composed of a detection electrode, signal converter, microprocessor, and ZigBee, and its measurement range is $10{\mu}A{\sim}5mA$.

Development of Working Platform for the Polymer Insulator String (송전선로 폴리머애자 공사용 장비 개발)

  • Min, Byeong-Wook;Wi, Shwa-Bok;Bang, Hang-Kwon;Choi, Han-Yeol;Baek, Soo-Gon;Park, Jae-Ung
    • Proceedings of the KIEE Conference
    • /
    • 2006.07a
    • /
    • pp.438-439
    • /
    • 2006
  • Porcelain insulators have generally been used in Korea to insulate a transmission line from the tower, and a highly polymerized compound polymer insulator which has superior stain proof characteristics, has also been used widely. Currently, a worker rides on the suspension insulator string for installation on towers and conductors but in case of polymer insulators, this will pollute and scratch the housing result in durability reduction by deterioration and corona. This study developed a high strength aluminum compound metal lauder designed to work on polymer insulators without riding, and a clamp type connecting device and safety gear for easy installation on the tower and conductor. These polymer insulator work device can be used for 154kV and 345kV polymer insulators through a strength and load test to secure safety. This paper presents field usage.

  • PDF