• 제목/요약/키워드: Stator Winding Insulation

검색결과 130건 처리시간 0.034초

고압 유도전동기 고정자 권선의 절연 신뢰성 평가에 관한 연구 (A Study on Evaluation of Insulation Reliability for High-Voltage Motor Stator Windings)

  • 황돈하;심우용;강동식;강도현;김용주
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1909-1912
    • /
    • 2002
  • Recently, domestic electrical parts and materials without safety and reliability are avoided by consumers and introducing the product liability (PL) law. Therefore, the dependance on import product of electrical machines will be increased in the future. In this paper, high-voltage induction motor ensures reliance that can maintain the performance of machines for a long time. Furthermore, the test of reliability evaluation that predicts a remaining life and breakdown test of the stator winding are performed. Also, this paper introduces various reliability assessment tests for getting reliability of the stator winding insulation in high-voltage motor.

  • PDF

4.16kV 및 6.6kV 전동기 고정자 권선의 절연열화 판정기준 (Judgement Criterion of Insulation Deterioration in 4.16kV and 6.6kV Motor Stator Windings)

  • 김희동
    • 전기학회논문지
    • /
    • 제58권4호
    • /
    • pp.788-794
    • /
    • 2009
  • To assess the condition of stator insulation, nondestructive tests were performed on twenty five coil groups and twenty six motors. The stator windings has nominal ratings of 6.6kV and are classified into five coil groups ;one group with healthy insulation and four groups with four different types of artificial defects. After completing nondestructive tests, the AC voltage applied to the stator windings was gradually increasing until insulation failure in order to obtain the breakdown voltage. No.1, No.2 and No.6 of 6.6kV motors failed near rated voltage of 14kV, 8.7kV and 14kV, respectively. The breakdown voltage of three motors was lower that expected for good quality coils(14.2kV) in 6.6kV motors. No.3 and No.6 of 4.16kV motors failed near rated voltage of 5.6kV and 4.2kV, respectively. Almost all of failures were located in a line-end coil at the exit from the core slot. The breakdown voltages and the types of defects showed strong relation to the stator insulation tests such as in the case of AC current, dissipation factor(tan${\delta}$) and partial discharge magnitude.

고압전동기 고정자 권선의 절연열화 분석 (Analysis of Insulation Aging in High Voltage Motor Stator Windings)

  • 김희동;공태식;이영준
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2006년도 하계학술대회 논문집 Vol.7
    • /
    • pp.200-203
    • /
    • 2006
  • Prior to destructive testing, diagnostic tests were performed in eight high voltage motors. Diagnostic tests included polarization index, ac current, dissipation factor($tan{\delta}$) and partial discharge magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 motor failed near rated voltage of 12.96 kV. The breakdown voltage of No. 4 motor was 6.99 kV which is lower that expected for good quality coils in 6.6 kV class motors. The failure was located in a line-end coil at the exit from the core slot. These two motors began operation in 1994. While testing No. 7 motor, flashover occurred between the stator winding and the stator frame at 15 kV. The relationship between the diagnostic test and the drop in insulation breakdown voltage was analyzed.

  • PDF

철도차량용 견인전동기의 형권 고정자 코일에 대한 절연열화 특성 연구 (A Study on the Insulation Degradation Properties for Stator Form-wound Winding of Traction Motors in Urban Transit E.M.U)

  • 김기준;채승훈;왕종배;박현준;이인우;허익구;하현성
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 A
    • /
    • pp.452-454
    • /
    • 1999
  • In this paper, sample coils for stator form-wound winding of traction motor were made for the accelerative thermal degradation composed of heat, vibration, moisture and overvoltage. In progress of test periods, diagnosis tests such as insulation resistance, dielectric loss and partial discharge were investigated. Reliability and expected life were evaluated on the insulation system for 200 class traction motor considering various environmental stress.

  • PDF

고압 전동기 고정자 권선의 활선 부분방전 모니터링 기술개발 (Development of On-Line Partial Discharge Monitoring Techniques for Stator Winding of High-Voltage Motors)

  • 황돈하;이주훈;강동식;김용주;이재영;신병철
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 춘계학술대회 논문집 방전 플라즈마 유기절연재료 초전도 자성체연구회
    • /
    • pp.43-46
    • /
    • 2004
  • Recently many research activities on the diagnosis of stator winding insulation of high-voltage motors have been reported. Most of them utilize a trend analysis of partial discharges. In this paper, a novel on-line monitoring system for an insulation diagnosis is proposed. This system displays magnitude and phase angle distribution of partial discharge. The partial discharge activities can be interpreted more precisely by these techniques.

  • PDF

백화현상이 나타난 고압전동기 고정자권선의 절연특성 연구 (A Study on Insulation Property of White Powder Found on High Voltage Motor Stator Winding)

  • 공태식;김희동;이상길;김경열;주영호
    • 전기학회논문지
    • /
    • 제60권8호
    • /
    • pp.1627-1631
    • /
    • 2011
  • During a routine inspection of a large pump motor at power plant, white powder was found on the surface of the stator end windings. Visual inspection and high voltage insulation diagnosis was performed to determine whether this motor is available. The purpose of this paper is to understand the insulation properties of white powder found on high voltage stator and to know prevention of insulation weakness.

고압 회전기 On-line 부분방전 측정용 Ceramic Coupler 특성 (Characteristics of Ceramic Coupler for On-line Partial Discharge Measurement in High Voltage Rotating Machines)

  • 강동식;윤대희;김용주;이홍식;윤영호;박정후
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제51권5호
    • /
    • pp.204-212
    • /
    • 2002
  • In order to improve the reliability of high voltage rotating machines, it is necessary to understand the breakdown mechanism of stator windings. Especially partial discharge(PD) inception and growth are important in stator winding insulation. Recently, many research on the diagnosis of stator winding insulation for large rotating machines have been developed since the 1970s. Capacitive couplers have been the most widely used sensor for on-line partial discharge detection in rotating machines. This paper deals with the electrical on-line monitor characteristics of ceramic coupler(CC) which has been developed to continuously measure the PD activity in operating high voltage motor stator windings on site. We investigated the electrical characteristics(PD quantity, breakdown voltage and frequency response) to develop CC. This paper presents frequency characteristics and laboratory test result to compare conventional 80([F] epoxy-mica coupler(EMC) and 105[pF] CC for PD measurement with 6.6㎸ model stator windings.

6.6 kV급 고압전동기 고정자 권선의 절연열화 평가 (Assessment of Insulation Aging in 6.6 kV Class High Voltage Motor Stator Windings)

  • 김희동;김병한
    • 한국전기전자재료학회논문지
    • /
    • 제19권11호
    • /
    • pp.1067-1071
    • /
    • 2006
  • Prior to destructive testing, diagnostic tests were performed in ten high voltage motors. Diagnostic tests included polarization infer, ac current, dissipation factor$(tan{\delta})$ and partial discharge magnitude. The rewind of motet slater insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 8 motor failed near rated voltage of 19.0 kV. The breakdown voltage of No. 4 motet was 7.0 kV which is lower that expected for good quality coils in 6.6 kV class motors. The failure was located in a line-end coil at the exit from the core slot. These two motors began operation in 1994. While testing No. 7 motor, flashover occurred between the stator winding and the stator frame at 15 kV. The relationship between the diagnostic test and the drop in insulation breakdown voltage was analyzed.

발전기 운전중 종합 진단시스템 개발 (Development of On line Diagnosis System for Generator)

  • 이영준;공태식;김희동;주영호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 B
    • /
    • pp.975-977
    • /
    • 2005
  • The generator on-line diagnosis system has been developed. This system monitor the insulation condition of stator winding by on-line measurements of partial discharge and the shorted-turn condition of rotor winding by on-line measurements of slot leakage flux. Sensor, such as SSC(Stator Slot Coupler) and flux probe are used for generator on-line diagnosis.

  • PDF

고압전동기 고정자 권선의 절연파괴 특성 (Characteristics of Insulation Failure in High Voltage Motor Stator Windings)

  • 김희동;김경열;박덕현
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2010년도 하계학술대회 논문집
    • /
    • pp.124-124
    • /
    • 2010
  • Diagnostic tests were performed on six high voltage motors. These tests included ac current, dissipation factor(tan6) and partial discharge(PD) magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 and No.2 motors(4.16 kV) failed near rated voltage of 12.3 kV and 14.2 kV, respectively. The breakdown voltage of No.3 and No.4 motors(6.6 kV) was 17.6 kV and 17.8 kV, respectively. These motors are higher that expected for good quality coils in 6.6 kV class motors.

  • PDF