Abstract
To assess the condition of stator insulation, nondestructive tests were performed on twenty five coil groups and twenty six motors. The stator windings has nominal ratings of 6.6kV and are classified into five coil groups ;one group with healthy insulation and four groups with four different types of artificial defects. After completing nondestructive tests, the AC voltage applied to the stator windings was gradually increasing until insulation failure in order to obtain the breakdown voltage. No.1, No.2 and No.6 of 6.6kV motors failed near rated voltage of 14kV, 8.7kV and 14kV, respectively. The breakdown voltage of three motors was lower that expected for good quality coils(14.2kV) in 6.6kV motors. No.3 and No.6 of 4.16kV motors failed near rated voltage of 5.6kV and 4.2kV, respectively. Almost all of failures were located in a line-end coil at the exit from the core slot. The breakdown voltages and the types of defects showed strong relation to the stator insulation tests such as in the case of AC current, dissipation factor(tan${\delta}$) and partial discharge magnitude.
Keywords
Motor; Nondestructive test; Stator winding; Breakdown voltage; Artificial defect; Dissipation factor;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
Times Cited By SCOPUS : 0
연도 인용수 순위
1 J. H. Dymond, N. Stranges, K. Younsi and J. E. Hayward, 'Stator Winding Failures : Contamination, Surface Discharge, Tracking', IEEE Trans. on Industry Applications, pp. 577-583, 2002   DOI   ScienceOn
2 김희동외 6명, '고압전동기 정지중 절연열화 판정기준 및 진단기법 연구 (최종보고서)' 산업자원부(R-2004-0-160-01), 2007
3 H. Zhu, C. Morton and S. Cherukupalli, 'Quality Evaluation of Stator Coils and Bars under Thennal Cycling Stress', Conference Record of the 2006 IEEE International Symposium on Electrical Insulation, pp. 384-387, 2006
4 김희동, '발전기 고정자 권선의 절연열화 메카니즘 분석', 전기전자재료학회 논문지, Vol.15, No.2, pp. 119-126, 2002   과학기술학회마을   DOI
5 H. G. Sedding, R. Schwabe, D. Levin, J Stein and B. K. Gupta, 'The Role AC & DC Hipot Testing m Stator Winding Ageing', IEEE Electrical Insulation and Electrical Manufacturing & Coil Winding Conference, pp. 455-457, 2003
6 G. Stone and J Kapler, 'Stator Winding Monitoring', IEEE Industry Applications Magazine, pp. 15-20, 1998   DOI   ScienceOn
7 H. Yoshida and K. Umemoto, 'Insulation Diagnosis for Rotating Machine Insulation', IEEE Trans. on Electrical Insulation, Vol. EI-21, No.6, pp. 1021-1025, 1986   DOI   ScienceOn
8 I. M Culbert, H. Dhirani, and G. C. Stone, 'Handbook to Assess the Insulation Condition of Large Rotating Machines', EPRI, EL-5036, Vol. 16, pp. 3-25-3-28, 5-13-5-14, 1989
9 Claude Hudon and Mario Belec, 'Partial Discharge Signal Interpretation for Generator Diagnostics', IEEE Trans. on Dielectrics and Electrical Insulation, Vol. 12, No.2, pp. 297-319, 2005   DOI   ScienceOn
10 김희동, 주영호, '고압전동기 고정자 권선 절연재료의 미세구조 특성', 한국전기전자 재료학회 춘계학술대회 논문집, pp. 513-517, 1999   과학기술학회마을