• Title/Summary/Keyword: Smoke Spread

Search Result 124, Processing Time 0.02 seconds

Study of the Characteristics of Smoke Spread by an Installing Smoke Barrier in Medium Length Road Tunnel (중규모 도로터널의 제연경계벽 설치에 따른 연기확산특성)

  • Baek, Doo-San;Lee, Seung-Chul
    • Fire Science and Engineering
    • /
    • v.30 no.5
    • /
    • pp.9-17
    • /
    • 2016
  • In the case of a medium length road tunnel, the installation of a smoke control facility is not mandatory so users can suffer considerable injuries if a fire breaks out. Therefore, this study analyzed the high-temperature air and toxic gas generated by fire proliferating with time when a smoke barrier is not installed and when the installation interval is 100, 150, 200, and 250 m through 3-dimensional numerical analysis, evacuation simulation, and Quantitative Risk Assessment Methodology targeting the medium length road tunnel. As a result, the diffusion of the high-temperature air and toxic gas occurring from the a fire was delayed when the smoke barrier was installed in a medium length road tunnel compared to that when it was not installed. In addition, when the installation interval of a smoke barrier was 100m and the numerical analysis target was 100m, the diffusion of high-temperature air and toxic gas generated by the fire was delayed more than in the other cases, which was most suitable for tunnel users to evacuate.

A Study for Pressure Difference and Critical Velocity by Pressurization of Elevator Shaft at High Rise Apartment (고층 공동주택의 승강로가압을 이용한 차압 및 방연풍속에 관한 연구)

  • Park, Kyung-Hwan;Yoon, Myong-O
    • Fire Science and Engineering
    • /
    • v.25 no.4
    • /
    • pp.89-93
    • /
    • 2011
  • It is not recommended that elevator use for egress at (super) high rise buildings because elevator shaft main roles to spread of fire smoke. But in North America used to protect this area by elevator shaft pressurization. These tests are performed at high rise apartment to verify that elevator shaft pressurization can protect to spread of fire smoke or not. and verify to used for egress at fire. Pressurization at elevator shaft make pressure difference of 50 Pa all floor at 150 CMM because this method have low friction loss from air flow. Also when dwelling door and elevator door are opened that critical velocity is performed to protect of back-layering from fire room for escape routs by 180 CMM. Therefore through out these pressurization tests by elevator shaft are estimated to have less overpressure because supply air difference are low between to satisfy critical velocity at one door opened and maintain to pressure difference all doors closed. Finally we verified that disable or residual people can use elevator for egress at fire by elevator shaft pressurization.

A Study on the Fire Reconstruction of Exterior on High-rise Building (Focus on Fire Case Including the Woosin Golden Suite in Haeundae) (고층 건축물 외장재의 화재 재현에 관한 연구 (해운대 우신골든스위트의 화재사례를 중심으로))

  • Min, Se-Hong;Lee, Jae-Moon
    • Fire Science and Engineering
    • /
    • v.27 no.2
    • /
    • pp.25-30
    • /
    • 2013
  • 'Heaundae Woosin Building' fire was the case that a fire breaking out on the $4^{th}$ floor spread out the $38^{th}$ floor which is a top story and the penthouse was destroyed by fire. After this fire, the fire safety for high rise buildings has been on the rise and several new laws and regulations related in the buildings were created. The study is to analyze Heaundae officetel building case using FDS which is one of the CFD programs for fire. The methodology of this study is to analyze the case comparing with fire spread and route from a virtual fire simulation and related articles and a video clip of actual scene fire. This study shows that a fire spreading on top of levels spent approximately 30 minutes and, which is similar to the actual fire case. Also the pattern of spread has similarity with the case. However, even if the actual fire case shows the fire pattern was "V shape", the smoke-view presents the fire dose not spread horizontally as much as the real fire case. The result shows uncertainty of the modeling based on many grids and a limitation of putting interior finish input sources and the direction of the wind might cause the difference. Also, to analyze factors influencing on a vertical fire, another fire modeling is performed by in condition of modeling environment considering concrete interior finish between buildings and no wind. The result presents the fire spread in smoke-view does not spread vertically as much as the actual case.

Calculation of Fire-resisting Time and Extraction of Simple Transplants in the Event of a Building Fire (건축물 화재시 필요내화 시간 산정 및 간이식 도출)

  • Kim, Yun-Seong;Han, Ji-Woo;kim, Hye-Won;Jin, Seung-Hyeon;Lee, Byeong-Heun;Kwon, Yeong-Jin
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2020.11a
    • /
    • pp.59-60
    • /
    • 2020
  • Large fires continue to spread throughout the building, including the fire in Uijeongbu in 2015, the fire in Jecheon in 2017, and the fire in Miryang in 2018. According to the above fire case investigation, major problems were the fire resistance performance of compartment members such as fire doors, the fire spread due to damage to exterior wall openings, and smoke spread through vertical openings. However, in South Korea, only specification design is implemented for buildings that are not subject to performance design. In addition, the analysis of the fire resistance performance standards of building members in the specification design showed that fire doors were not specified in detail for 60 minutes of insulation performance and 60 minutes of fire resistance performance of E/V doors, limiting the prevention of fire spread. Therefore, the purpose of this research is to prepare measures to prevent the spread of fire by presenting simple transplants for calculating the required fire time according to the architectural design conditions for the performance design of the components of the fire room according to the purpose of use of the front of the building.

  • PDF

Analyses of Scenarios Based on a Leakage of Highly Compressed Air and Fire Anticipated in CAES (Compressed Air Energy Storage) Facility (압축공기에너지저장 시설에서 발생 가능한 압축공기 유출 및 화재 시나리오 분석)

  • Yoon, Yong-Kyun;Ju, Eun-Hye
    • Tunnel and Underground Space
    • /
    • v.25 no.6
    • /
    • pp.568-576
    • /
    • 2015
  • In this study, scenarios based on the leakage of highly compressed air and fire occurrence turned out to be high risks in an operation stage of CAES facility were constructed and estimated. By combining Bernoulli equation with momentum equation, an expression to calculate an impact force of a jet flow of compressed air was derived. An impact force was found to be proportional to the square of diameter of fracture and the pressure of compressed air. Four types of fire scenarios were composed to evaluate an effects that seasonal change and location of fire source have on the spread behavior of smoke. Smoke from the fire ignited in the vicinity of CAES opening descended more quickly below the limit line of breathing than one from the fire occurred 10 m away from CAES opening, which is expected to occur due to a propagation of wave front of smoke. It was shown that a rate of smoke spread of the winter fire is faster than one of the summer fire and smoke from the winter fire spreads farther than one of the summer fire, which are dependent on the direction of air flow into access opening. Evacuation simulation indicated that the required safe evacuation time(RSET) of the summer and winter fires are 262, 670 s each.

Fire at an Indoor Shooting Range in Busan I. Fire Reconstruction (부산 실내사격장 화재 I. 화재재현)

  • Park, Woe-Chul
    • Fire Science and Engineering
    • /
    • v.24 no.2
    • /
    • pp.114-119
    • /
    • 2010
  • The fire at a Busan indoor shooting range on November 14, 2009 was reconstructed by using a computational fluid dynamics model for fire simulations, in order to investigate the cause of the heavy death toll in a short period of time. Spread of the flame and smoke, and temperature distribution obtained by fire simulation were compared with the results of fire investigation based on the CCTV recordings. The flame and smoke flew out violently through the door into the cafeteria from the shooting range, and the cafeteria was filled with smoke just within 3 seconds followed by the onset of fire. This is consistent with the CCTV recordings. It was confirmed, as a result, that people in the cafeteria did not have enough evacuation time. The computed temperature at the door knob reached about $1400^{\circ}C$, near its melting point.

Implementation of YOLOv5-based Forest Fire Smoke Monitoring Model with Increased Recognition of Unstructured Objects by Increasing Self-learning data

  • Gun-wo, Do;Minyoung, Kim;Si-woong, Jang
    • International Journal of Advanced Culture Technology
    • /
    • v.10 no.4
    • /
    • pp.536-546
    • /
    • 2022
  • A society will lose a lot of something in this field when the forest fire broke out. If a forest fire can be detected in advance, damage caused by the spread of forest fires can be prevented early. So, we studied how to detect forest fires using CCTV currently installed. In this paper, we present a deep learning-based model through efficient image data construction for monitoring forest fire smoke, which is unstructured data, based on the deep learning model YOLOv5. Through this study, we conducted a study to accurately detect forest fire smoke, one of the amorphous objects of various forms, in YOLOv5. In this paper, we introduce a method of self-learning by producing insufficient data on its own to increase accuracy for unstructured object recognition. The method presented in this paper constructs a dataset with a fixed labelling position for images containing objects that can be extracted from the original image, through the original image and a model that learned from it. In addition, by training the deep learning model, the performance(mAP) was improved, and the errors occurred by detecting objects other than the learning object were reduced, compared to the model in which only the original image was learned.

Evacuation Safety Evaluation for Apartment Complexes and Officetel under Floors (공동주택 및 오피스텔 지하층에 대한 피난 안전성 평가)

  • Hyeon-gwon Kang;Yong-Han Jeon
    • Journal of the Korea Safety Management & Science
    • /
    • v.25 no.4
    • /
    • pp.67-72
    • /
    • 2023
  • Human and material damage can be reduced if the risk is evaluated by engineering analysis of fire combustion products, smoke concentration, and smoke movement speed in the event of a fire in apartment houses and officetels. In this study, a lot of research on related safety evaluation in the basement needs to be studied and reflected in design, so experimental research was conducted to analyze the flow of smoke through computer simulation and provide analysis data through evacuation safety evaluation. First of all, the five-story underground parking lot subject to simulation has a large floor area, which is advantageous for improving evacuation safety performance, but it uses temperature detectors to increase detection time and fire spread speed. Second, it was analyzed that the evacuation time at all evacuation ports did not exceed the evacuation time, and as the time from the start of evacuation to the evacuation time was 216.9% compared to the travel time, it was evaluated that the safety performance of the evacuation was secured. Third, the above simulation results are a comprehensive safety evaluation based on the non-operation of fire extinguishing facilities in the fire room to increase safety, which means that smoother evacuation safety performance can be secured by linking fire extinguishing facilities.

A Study on escape using elevators in fire emergency (화재 시 승강기를 이용한 피난에 관한 연구)

  • Chung, Eui-Soo
    • Proceedings of the Safety Management and Science Conference
    • /
    • 2007.11a
    • /
    • pp.55-68
    • /
    • 2007
  • Because of not accepted on escape using elevators in fire emergency has some background. In the background elevator hoistway has turn into smoke spread route in fire. The escape that used an elevator was not able to make ends meet; of the big confusion is expected that cannot control the escape adequately, and do that elevator facilities breakdown possibility by the fire water, the escaper shut in car. Therefore ban on elevator service in fire time as a general rule. Recently, a few company promote super high-rise architecture in the country, a fire disaster prevention and human life safety measures preparation for PBD(A Performance Based Fire Protection Design) are studied concretely. And there is the escape example in fire time that used an elevator in the foreign country. You must promote it so that the escape measures that used enclosed stairway and an elevator in charge of a function of the mutual supplement. The result of this research can be used for establishing the standard and regulation for using elevators in fire emergency.

  • PDF

An Experimental Study on the Formation of Smoke Layer of Compartment Fire (건물화재시 연기층의 형성에 관한 실험적연구)

  • 허만성
    • Journal of the Korean Society of Safety
    • /
    • v.12 no.1
    • /
    • pp.94-100
    • /
    • 1997
  • The objective of this research is to study the formations of smoke layer in case of several furniture fires such as trashcan, carpet, mattress and wardrobe as a fire starter in a residential room by performing the experimental studies. The uniformly distributed fire in case of carpet showed that the ignition and the initial growth period were relatively short while the fully developed period was considerably long. The concentrated fires such as the trashcan, mattress and wardrobe showed that the ignitions and the initial growth periods were relatively long. The descending speed of the interface height was proportioned to the inflammability of the furniture and the spread of the fire. The time required to come down around 1m was within 1-3 minutes. The Interface heights for the furniture fires were around 1m as the steady state. However, at the time of the maximum temperature, the interface height was lowered to 0.25m-0.75m from the floor. The carbon dioxide concentration reached the highest while the oxygen concentration was minimum.

  • PDF