An Experimental Study on the Formation of Smoke Layer of Compartment Fire

건물화재시 연기층의 형성에 관한 실험적연구

  • 허만성 (중경공업전문대학 소방안전관리과)
  • Published : 1997.03.01

Abstract

The objective of this research is to study the formations of smoke layer in case of several furniture fires such as trashcan, carpet, mattress and wardrobe as a fire starter in a residential room by performing the experimental studies. The uniformly distributed fire in case of carpet showed that the ignition and the initial growth period were relatively short while the fully developed period was considerably long. The concentrated fires such as the trashcan, mattress and wardrobe showed that the ignitions and the initial growth periods were relatively long. The descending speed of the interface height was proportioned to the inflammability of the furniture and the spread of the fire. The time required to come down around 1m was within 1-3 minutes. The Interface heights for the furniture fires were around 1m as the steady state. However, at the time of the maximum temperature, the interface height was lowered to 0.25m-0.75m from the floor. The carbon dioxide concentration reached the highest while the oxygen concentration was minimum.

Keywords