• Title/Summary/Keyword: Single phase UPS

Search Result 67, Processing Time 0.026 seconds

Output Filter and Controller designs for UPS Inverter with Single-Phase (단상 UPS 인버터의 출력필터와 제어기 설계)

  • Kim, Jae-Sig;Choi, Chang-Ho;Choi, Jae-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2001.07b
    • /
    • pp.1064-1066
    • /
    • 2001
  • In this paper, the harmonic components generated by those two sources are analyzed separately based on the transfer function and shown as the closed form considering the switching frequency, speed of the control processor, gain of the controller, and the inductor and capacitor value of L-C filter. A design procedure is described with one flow chart and explained step by step.

  • PDF

Static Switch Control of UPS with Active Filter Function (능동 필터 기능을 갖는 무정전전원장치의 정적 스위치 제어)

  • Hong, Hyun-Mun;Jeon, B.S.;Kim, J.G.;Lee, S.H.;Kim, J.S.;Min, Y.G.
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.406-408
    • /
    • 2005
  • In this literature, when the utility line is normal, the Off-Line UPS operates as an active power filter to compensate the reactive power from a load, and when the utility line is in outage, the On-Line UPS opuates as in single phase inverter to supply an active and reactive power to the load. An additional static switch in UPS was used to decrease an transient state during these mode changes. And the result shows that the transient state disappeared.

  • PDF

A Study on a Single-Phase Module UPS using a Three-Arm Converter/Inverter

  • Koo, Tae-Geun;Byun, Young-Bok;Joe, Ki-Yeon;Kim, Dong-Hee;Kim, Chul-U
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.3B no.1
    • /
    • pp.44-51
    • /
    • 2003
  • The module UPS can flexibly implement expansion of power system capacities. Further-more, it can be used to build up the parallel redundant system to improve the reliability of power system operation. To realize the module UPS, load sharing without interconnection among parallel connecting modules as well as a small scale and lightweight topology is necessary. In this paper, the three-arm converter/inverter is compared with the general full-bridge and half-bridge topology from a practical point of view and chosen as the module UPS topology. The switching control approaches based on a pulse width modulation of the converter and inverter of the system are presented independently. The frequency and voltage droop method is applied to parallel operation control to achieve load sharing. Two prototype 3㎸A modules are designed and implemented to confirm the effectiveness of the pro-posed approaches. Experimental results show that the three-arm UPS system has a high power factor, a low distortion of output voltage and input current, and good load sharing characteristics.

Robust Double Deadbeat Control of Single-Phase UPS Inverter (단상 UPS 인버터의 강인한 2중 데드비트제어)

  • 박지호;허태원;안인모;이현우;정재륜;우정인
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.15 no.6
    • /
    • pp.65-72
    • /
    • 2001
  • This paper deals with a novel full digital control of the single-phase PWM(Pulse Width Modulation) inviter for UPS(Uninterruptible Power Supp1y). The voltage and current of output filter capacitor as a state variable are the feedback control input. In the proposed scheme a double deadbeat control consisting of minor current control loop and major voltage control loop have been developed In addition, a second order deadbeat currents control which should be exactly equal to its reference in two sampling time without error and overshoot is proposed to remove the influence of the calculation time delay. The load current prediction is achieved to compensate the load disturbance. The simulation and experimental result shows that the proposed system offers an output voltage with THD(Total Harmonic Distortion) less than 5% at a full nonlinear load.

  • PDF

Development of Uninterruptible Power Supply with Voltage Sag Restorer Function (순시전압강하 보상 기능을 가지는 무정전전원공급장치의 개발)

  • Park, Jong-Chan;Shon, Jin-Geun
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.63 no.2
    • /
    • pp.95-101
    • /
    • 2014
  • In this paper, UPS, with a built-in instantaneous sag drop compensation features, was developed to improve performance. The improved UPS, using instantaneous moving average method, compensates by quickly measuring the voltage and series inverter of half-bridge type, using line-interactive method that links with the voltage of the battery and power source, was developed. In addition, by developing a parallel inverter that uses a high-efficiency PWM switching method, overall UPS system was enhanced. To verify the performance of the proposed algorithm, single-phase 5[kVA] UPS systems were designed and the experimental system was constructed. The low-cost type of Cortex-M3 module CPU STM32F103R8T6 (32[bit]) is attached and the switching time of mode transfer was set within 4 [ms]. THD of the linear load operates in less than 3[%], and the stability of the output voltage operates in approximately ${\pm}2[%]$ range. The superior performance of the operations was confirmed with the system set as above.

Active Power Filter Type Single Phase Uninterruptible Power Supply(UPS) System (단상 전력용 능동필터형 무정전 전원장치)

  • Kim, Je-Hong;Son, Jae-Hyun
    • Journal of the Korean Institute of Telematics and Electronics T
    • /
    • v.36T no.4
    • /
    • pp.53-59
    • /
    • 1999
  • In this paper, a bi-directional UPS with the performance of active power filter has been proposed. The operation of the proposed system can be divided into two modes, such as the active power filter mode and the battery back-up power mode. To improve the transient response for the effective compensation of harmonics and reactive power in active power filter mode, a novel closed-loop control strategy is used to calculate the reference current instantaneously. Finally, the performance of proposed UPS is verified by the simulation and experimental results.

  • PDF

Digital Control Strategy for Single-phase Voltage-Doubler Boost Rectifiers

  • Cho, Young-Hoon;Mok, Hyung-Soo;Ji, Jun-Keun;Lai, Jih-Sheng
    • Journal of Power Electronics
    • /
    • v.12 no.4
    • /
    • pp.623-631
    • /
    • 2012
  • In this paper, a digital controller design procedure is presented for single-phase voltage-doubler boost rectifiers (VDBR). The model derivation of the single-phase VDBR is performed in the s-domain. After that the simplified equivalent z-domain models are derived. These z-domain models are utilized to design the input current and the output dc-link voltage controllers. For the controller design in the z-domain, the traditional K-factor method is modified by considering the nature of the digital controller. The frequency pre-warping and anti-windup techniques are adapted for the controller design. By using the proposed method, the phase margin and the control bandwidth are accurately achieved as required by controller designers in a practical frequency range. The proposed method is applied to a 2.5 kVA single-phase VDBR for Uninterruptible Power Supply (UPS) applications. From the simulation and the experimental results, the effectiveness of the proposed design method has been verified.

A Disturbance Observer-Based Load Current Estimation Method for Ups Inverter Applications (인버터응용을 위한 외란관측기에 의한 부하전류추정 방법)

  • Jang, Jae-Young;Lee, Kyo-Beum;Song, Joong-Ho;Choy, Ick;Yoo, Ji-Yoon;Choi, Ju-Yeop
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.51 no.3
    • /
    • pp.116-124
    • /
    • 2002
  • Design and analysis of disturbance observer-based deadbeat control fur single-phase inverter applications are comprehensively presented in this paper. Load current can be estimated by disturbance observer, which is basically structured with the first order equation in this case and is regarded as a relatively simple method in comparison with conventional full-order Luenberger observer. Also, an inherent one-step delay problem appeared in the deadbeat control method is overcome by a simple prediction technique proposed. Output voltage dip is reduced by the feedforward control with the change rate of the estimated load current involved in the deadbeat current control loop. The proposed algorithms are verified by the respective simulation and experiment results.

Implementation of BOOST Converter with Power Factor Correction(PFC) using a Single-phase On-line UPS (단상 On-line UPS를 이용하여 역율을 개선하는 BOOST 컨버터의 구현)

  • Han, Wan-Ok;Kim, Tae-Woong
    • Journal of the Korean Institute of Telematics and Electronics T
    • /
    • v.36T no.4
    • /
    • pp.47-52
    • /
    • 1999
  • This paper proposed simplified method to complicated Power Stage with a new On-line UPS scheme by replacing essential battery-voltage booster with a dual-functional PFC. Direct Load Voltage (${V_o}$) can not be applied to high voltage switching converter due to ripple from traditional Power Factor Correction (PFC) but Boost Function of On-line UPS is united so that the cost of system design and development is inexpensive. Through varification of experimental result, proposed UPS scheme shows its performance, low cost and high power density.

  • PDF

Single-phase Uninterruptible Power Supply employing Superconducting Magnet Energy Storage Unit

  • Kang, Feel-Soon
    • Journal of information and communication convergence engineering
    • /
    • v.5 no.4
    • /
    • pp.362-368
    • /
    • 2007
  • A single-phase uninterruptible power supply system equipped with a superconducting magnet energy storage unit is proposed to achieve a simple circuit configuration and higher system reliability. It reduces a number of switching devices by applying a common-arm scheme. Removing some switches or substituting passive elements for active switches can increase the sophistication and reduces degree of freedom in control strategy. However, high-performance DSP controller can execute the complicated control task with no additional cost. Operational principles to normal, stored-energy, and bypass mode are discussed in detail. The validity of the proposed system is verified by experimental results.