Browse > Article
http://dx.doi.org/10.5370/KIEEP.2014.63.2.095

Development of Uninterruptible Power Supply with Voltage Sag Restorer Function  

Park, Jong-Chan (오산대학교 전기시스템제어과)
Shon, Jin-Geun (가천대학교, 전기공학과)
Publication Information
The Transactions of the Korean Institute of Electrical Engineers P / v.63, no.2, 2014 , pp. 95-101 More about this Journal
Abstract
In this paper, UPS, with a built-in instantaneous sag drop compensation features, was developed to improve performance. The improved UPS, using instantaneous moving average method, compensates by quickly measuring the voltage and series inverter of half-bridge type, using line-interactive method that links with the voltage of the battery and power source, was developed. In addition, by developing a parallel inverter that uses a high-efficiency PWM switching method, overall UPS system was enhanced. To verify the performance of the proposed algorithm, single-phase 5[kVA] UPS systems were designed and the experimental system was constructed. The low-cost type of Cortex-M3 module CPU STM32F103R8T6 (32[bit]) is attached and the switching time of mode transfer was set within 4 [ms]. THD of the linear load operates in less than 3[%], and the stability of the output voltage operates in approximately ${\pm}2[%]$ range. The superior performance of the operations was confirmed with the system set as above.
Keywords
Half-bridge inverter; High-efficiency PWM(pulse width modulation); Line-interactive Method; UPS (uninterruptible power supply); Voltage sag compensation;
Citations & Related Records
Times Cited By KSCI : 3  (Citation Analysis)
연도 인용수 순위
1 Dong-Jun Kim , Jin-Geun Shon, Hee-Jong Jeon, "A development of Diagnosis Monitoring System for UPS DC Link Capacitors using Zigbee Wireless Communication", Trans. KIEE. Vol. 61P, No. 1, pp.41-46, Mar. 2012.   과학기술학회마을   DOI   ScienceOn
2 Jin-Geun Shon, Hee-Jong Jeon, "Series Voltage Compensation Systems for Voltage Sag by Using an Environmentally Friendly Ultra-capacitor", Trans. KIEE. Vol. 58, No. 4, pp.763-769, APR. 2009.   과학기술학회마을
3 D. Mahinda Vilathgamuwa et al, "Voltage Sag Compensation With Energy Optimized Dynamic Voltage Restorer", IEEE Trans., POWER DELIVERY, Vol.18, NO.3, pp.928-936, July 2003.   DOI   ScienceOn
4 F. Botteron, H. Pinheiro "A Three-Phase UPS That Complies With the Standard IEC 62040-3", IEEE Trans. Ind. Electron., vol. 54, no. 4, pp.2120 - 2136, Aug. 2007.   DOI   ScienceOn
5 R. Martinez and P. N. Enjeti, "A high-performance single-phase rectifier with input power factor correction", IEEE Trans. on PE, vol. II, no. 2, pp. 311-317, 1996,
6 Jong-Chan Park, Jin-Geun Shon, "Power Factor Correction of Single-phase Boost Converter for Low-cost Type UPS Configuration", Trans. KIEE. Vol. 62P, No. 3, pp. 145-150, SEP, 2013.   과학기술학회마을   DOI   ScienceOn
7 R.M. Santos Filho, P.F. Seixas, P.C. Cortizo, LAB. Torres, and A. F.Souza, "Comparison of Three Single-Phase PLL Algorithms for UPS Applications," IEEE Trans. on Industrial Electronics, vol. 55, no. 8, pp.2923-2932, 2008.   DOI   ScienceOn
8 Math H. J. Pollen, Understanding Power Quality Problems, IEEE Press, 1999.