• Title/Summary/Keyword: Full Scale Fire Experiment

Search Result 20, Processing Time 0.024 seconds

Numerical Study on the Validity of Scaling Law for Compartment Fires (구획 화재의 상사 법칙 유효성에 관한 수치해석 연구)

  • Ko, Gwon-Hyun
    • Fire Science and Engineering
    • /
    • v.28 no.4
    • /
    • pp.29-34
    • /
    • 2014
  • In this study, to assess the validity of scaling law which was based on the ventilation factor and utilized in fields of compartment fires, numerical simulations were conducted on full- and 2/5 reduced-scale compartment fires using FDS and simulation results were compared with the previously published experimental data. The numerical modeling used in this study was verified by comparing the predicted temperature at several points of the upper layer with the experiment data. Temperature and concentration distribution inside of compartments and velocity profile at door of compartment are analyzed to assess the validity of scaling law. Comparison between the predicted results on the full- and reduced-scale compartments shows good agreements on the inner compartment flow patterns, outflowing flame patterns from the compartments, and vertical temperature distributions.

Analysis of a Fire in an Apartment Building Using a Zone Model (ZONE MODEL을 이용한 아파트에서의 화재 해석)

  • 박진국;김충익;유홍선;윤명오
    • Fire Science and Engineering
    • /
    • v.11 no.2
    • /
    • pp.25-33
    • /
    • 1997
  • Fire hazards in an apartment building that represents the average households in Korean were investigated by conducting a full-scale experiment. This experiment attempts to analyze fire hazards using materials, and furnishings common to Korean housing stock. Experimental results are compared to the predictions of the C-FAST and smoke transport computer model. Comparisons between experimental data and C-FAST data are performed only to a living-room fire. Flashover occurred at approximately 380 seconds in a fire experinent, and at approximately 420 seconds in Zone-Model. Based on all of data between experimental data between experimental data and Zone-Model data, it is concluded that the safe egress time is at least 250 seconds.

  • PDF

A Study of Smoke Spread and Flow in a Long Corridor (복도에서의 연기 확산 및 유동에 관한 연구)

  • 김충익;유홍선;김명배;한용식;김진곤;윤명오;김상욱
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 1998.11a
    • /
    • pp.29-39
    • /
    • 1998
  • 복도는 사무실용 건물, 호텔 등 공중이용 건물에서 중요한 피난경로의 일부이다. 화재로 복도에 연기가 확산되면 그 온도, 연층의 높이, 유해물질의 농도 등에 따라 피난에 심각한 장애를 가져올 수 있다. 본 연구는 이러한 복도에서의 연기의 확산 및 유동에 관하여 연구하기 위하여 길이 40m의 복도에서 pool fire로부터의 연기 유동에 관한 실제크기의 실험과 수치해석을 수행하였다. 화재실과 그에 접해있는 긴 복도가 있는 실험장치에 직경 15, 20, 30cm의 가솔린 pool을 화재실 중앙에서 점화 시켰다. 연기의 온도 및 이동을 측정하기 위해 전장 중앙선을 따라 열전대를 설치하였고 연층의 두께를 측정하기 위하여 수직방향으로 세곳에 열전대가 부착된 수직봉을 설치하였다. 아르곤 레이저 sheet 과 비디오 카메라를 이용해 연기의 유동을 가시화 하였다.

  • PDF

The Study on Compartment Fire Experiment According to Fire Load (화재하중에 따른 구획화재 실험 연구)

  • Kweon, Oh-Sang;Kim, Heung-Youl
    • Fire Science and Engineering
    • /
    • v.31 no.6
    • /
    • pp.16-22
    • /
    • 2017
  • In Korea, performance-based fire safety designs are being discussed to deal with the various risks of fire in complex and diverse types of structure. However, performance-based fire safety designs are not actively employed because it is difficult to estimate the fire characteristics related to the various factors in buildings. In this study, real scale fire tests were conducted based on fire severity levels and fire loads provided in He New Zealand Building Code, in order to use the results as guidelines and fundamental data for performance-based designs. In the real scale fire tests conducted in a 10MW full-scale calorimeter, wood cribs were placed in a $2.4(L){\times}3.6(W){\times}2.4(H)m$ mock-up of a compartment which had one $0.8(L){\times}2.0(H)$ opening for different fire loads and heating was continued until all of the wood cribs were burned down. The heat release rate started to increase rapidly 90 seconds after the wood cribs caught fire. In the test with a fire load level 1, the maximum heat release rate of 4743.4 kW was reached at 244 second. In the test with fire load level 2, a maximum heat release rate of 5050.9 kW was reached at 497 second. In the test with fire load level 3, a maximum heat release rate of 4446.9 kW was reached at 677 second.

Fire resistance of high strength concrete filled steel tubular columns under combined temperature and loading

  • Tang, Chao-Wei
    • Steel and Composite Structures
    • /
    • v.27 no.2
    • /
    • pp.243-253
    • /
    • 2018
  • In recent years, concrete-filled box or tubular columns have been commonly used in high-rise buildings. However, a number of fire test results show that there are significant differences between high strength concrete (HSC) and normal strength concrete (NSC) after being subjected to high temperatures. Therefore, this paper presents an investigation on the fire resistance of HSC filled steel tubular columns (CFTCs) under combined temperature and loading. Two groups of full-size specimens were fabricated to consider the effect of type of concrete infilling (plain and reinforced) and the load level on the fire resistance of CFTCs. Prior to fire test, a constant compressive load (i.e., load level for fire design) was applied to the column specimens. Thermal load was then applied on the column specimens in form of ISO 834 standard fire curve in a large-scale laboratory furnace until the set experiment termination condition was reached. The results demonstrate that the higher the axial load level, the worse the fire resistance. Moreover, in the bar-reinforced concrete-filled steel tubular columns, the presence of rebars not only decreased the spread of cracks and the sudden loss of strength, but also contributed to the load-carrying capacity of the concrete core.

The Study on the Fire Monitoring Dystem for Full-scale Surveillance and Video Tracking (전방위 감시와 영상추적이 가능한 화재감시시스템에 관한 연구)

  • Baek, Dong-hyun
    • Fire Science and Engineering
    • /
    • v.32 no.6
    • /
    • pp.40-45
    • /
    • 2018
  • The omnidirectional surveillance camera uses the object detection algorithm to level the object by unit so that broadband surveillance can be performed using a fisheye lens and then, it was a field experiment with a system composed of an omnidirectional surveillance camera and a tracking (PTZ) camera. The omnidirectional surveillance camera accurately detects the moving object, displays the squarely, and tracks it in close cooperation with the tracking camera. In the field test of flame detection and temperature of the sensing camera, when the flame is detected during the auto scan, the detection camera stops and the temperature is displayed by moving the corresponding spot part to the central part of the screen. It is also possible to measure the distance of the flame from the distance of 1.5 km, which exceeds the standard of calorific value of 1 km 2,340 kcal. In the performance test of detecting the flame along the distance, it is possible to be 1.5 km in width exceeding $56cm{\times}90cm$ at a distance of 1km, and so it is also adaptable to forest fire. The system is expected to be very useful for safety such as prevention of intrinsic or surrounding fire and intrusion monitoring if it is installed in a petroleum gas storage facility or a storing place for oil in the future.

The Real Scale Fire Tests for Vertical Fire Spread Study of External Finishing Material (외벽 마감재료의 수직화재 확산 연구를 위한 실물화재 실험)

  • Kweon, Oh-Sang;Yoo, Yong-Ho;Kim, Heung-Youl;Kim, Jung-Hyun;Min, Se-Hong
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.85-91
    • /
    • 2012
  • To reduce human life and property damage at the fire in a building, it is most critical to control flame spread in the early stage. Fire spread prevention measure generally includes fire resistance performance securing of structure member in the arson zone and use limitation based on combustion performance of finishing material. The latter is most fundamental fire safety design to determine flame spread, but domestic combustion test determines combustion performance by specimen sized fire test method. Thus, there are many restrictions in the determination of combustion performance by composite material such as sandwich panel. Especially, outer finishing material uses a variety of composite material such as dry bit, aluminum composite panel, and metal panel compared to inner finishing material. Therefore, this study would determine vertical fire spread features by a full scaled fire experiment through the test method of ISO 13785-2, an international test standard.

A Study on the Toxic Gases Emission by Full-scale Experiment of Residential Buildings (주택화재재연실험을 통한 유해성 가스의 배출에 관한 연구)

  • Lee, Hae-Pyeong;Park, Young-Ju;Hwang, Me-Jung;Kim, Min-Jung;Kim, Hyo-Beom
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2012.04a
    • /
    • pp.349-352
    • /
    • 2012
  • 본 연구에서는 주택화재가 발생할 경우, 건축용 외장재로부터 발생하는 유해성 가스를 분석하고자 주택화재재연실험을 수행하였다. 실험 방법으로는 스티로폼, 우레탄폼, 글라스울 소재의 샌드위치 패널을 대상으로 KS F 2271 규격을 이용한 실험용 생쥐의 생체반응을 실험하였으며, NES 713을 이용한 독성가스에 대한 분석을 실시하였다. 샌드위치패널에서 발생하는 대표적인 유해성 가스는 시안화수소와 일산화탄소이며, 그 중에서 가장 유독한 것은 시안화수소로서 2차 세계대전 당시 유대인 학살에 사용된 독가스인데 시안화수소를 사람이 흡인한 경우 750ppm 이상이면 즉사하며, 375ppm 이상이면 30분 내에 사망하는 것으로 알려져 있다.

  • PDF

A Study of a Heat Flux Mapping Procedure to Overcome the Limitation of Heat Flux Gauges in Fire Tests (화재실험시 열유속 센서 사용의 단점을 보완한 Heat Flux Mapping Procedure에 관한 연구)

  • Choi, Keum-Ran
    • Journal of the Korean Society of Safety
    • /
    • v.20 no.4 s.72
    • /
    • pp.171-179
    • /
    • 2005
  • It is essential to understand the role of wall lining materials when they are exposed to a fire from an ignition source. Full-scale test methods permit an assessment of the performance of a wall lining material. Fire growth models have been developed due to the costly expense associated with full-scale testing. The models require heat flux maps from the ignition burner flame as input data. Work to date was impeded by a lack of detailed spatial characterization of the heat flux maps due to the use of limited instrumentation. To increase the power of fire modeling, accurate and detailed heat flux maps from the ignition burner are essential. High level spatial resolution for surface temperature can be provided from an infrared camera. The objective of this study was to develop a heat flux mapping procedure for a room test burner flame to a wall configuration with surface temperature information taken from an infrared camera. A prototype experiment was performed using the ISO 9705 test burner to demonstrate the developed heat flux mapping procedure. The results of the experiment allow the heat flux and spatial resolutions of the method to be determined and compared to the methods currently available.

An Experimental Study on the Damage of the Data Process Equipment When $CO_2$ is Discharged ($CO_2$ 소화설비 방사시 정보저장장치의 저온손상에 관한 연구)

  • 이수경;김종훈;김영진;최종운
    • Fire Science and Engineering
    • /
    • v.13 no.3
    • /
    • pp.19-26
    • /
    • 1999
  • $CO_2$ extinguishing system is the most $\phi$pular among the gas extinguishing system. $CO_2$ is usually stored with liquified state. But, it gasifies at the tip of nozzle when $CO_2$ was released through the pipe and head. A ro$\alpha$n temperature is very low when $CO_2$ was released. So electrical instrument, magnetic storage equipment and memory semiconductor are electrically or physically injured by cooling effect in a few minutes. So, we intend to find out temperature profile and electrical damage in compartment area, and supply basic d data for research and making standards and code through the full scale experiment. As result of experiment on the damage due to cooling effect from $CO_2$ extinguishing system, i instantaneous discharging temperature. was $-82.5^{\circ}C$ in average. An average temp. in the compartment after discharging $CO_2$ was $-40^{\circ}C$.

  • PDF