An Experimental Study on the Damage of the Data Process Equipment When $CO_2$ is Discharged

$CO_2$ 소화설비 방사시 정보저장장치의 저온손상에 관한 연구

  • Published : 1999.09.01

Abstract

$CO_2$ extinguishing system is the most $\phi$pular among the gas extinguishing system. $CO_2$ is usually stored with liquified state. But, it gasifies at the tip of nozzle when $CO_2$ was released through the pipe and head. A ro$\alpha$n temperature is very low when $CO_2$ was released. So electrical instrument, magnetic storage equipment and memory semiconductor are electrically or physically injured by cooling effect in a few minutes. So, we intend to find out temperature profile and electrical damage in compartment area, and supply basic d data for research and making standards and code through the full scale experiment. As result of experiment on the damage due to cooling effect from $CO_2$ extinguishing system, i instantaneous discharging temperature. was $-82.5^{\circ}C$ in average. An average temp. in the compartment after discharging $CO_2$ was $-40^{\circ}C$.

이산화탄소 소화설비는 가스계 소화설비 중 비용의 저렴함과 작동후의 청결함, 그리고 절연성등의 특성으로 인하여 통신기기설, 전산실, 전기실 등에 많이 사용되고 있다. 이산화탄소는 저장시 액체이다가 방출과 동시에 가스상태로 기화하는데 이때 온도가 급격히 내려간다. 이러한 냉각효과에 의하여 반도체장비나 정보저장장치에 손상을 줄 수 있다. 본 연구는 이산화탄소 방사시 구획내부의 온도분포와 손상정도를 규명하여 차후 연구의 기초자료를 제공하고 $CO_2$소화설비 설계나 관련규정의 정비에 도움이 되고자 시행했다. $CO_2$ 소화설비 방사 시 노즐부분의 순간방출온도는 $-82.53^{\circ}C$까지 내려갔다. 소화약제가 모두 방사되는 1분경의 실내평균온도는 $-40^{\circ}C$이며 이는 충분히 정보저장 장치류에 피해를 입힐 수 있는 온도이다. 플로피 디스켓을 설치하고 실험한 결과 70%의 고장율을 보였다. 컴퓨터를 넣고 실제 화재를 일으켜 실험한 결과, 특별한 고장이 없었으나, 작동으로 인한 내부의 열과의 온도차이에 의하여 수증기가 응결되고 녹아 흐르는 현상을 보여 Water Damage의 발생가능성을 발견할 수 있었다. 또한 저온지속시간(-5$^{\circ}C$기준)이 각 시나리오에서 평균 5분이상 나타났으며, 만약 실내의 단열과 밀폐조건이 더욱 좋은 경우라면 더 장시간 지속될 수 있다.