• Title/Summary/Keyword: FRP insulator

Search Result 39, Processing Time 0.029 seconds

The study on DC FRP support insulator wind tunnel test (직류용 FRP 지지애자 시작품 풍압시험에 대한 고찰)

  • Sim, Jae-Suk;Kin, Yoon-Sik;Jung, Ho-Sung;Cho, Ho-Ryung;Lee, Sang-Sik;Lee, Gi-Seung
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.46-49
    • /
    • 2010
  • Fiber Reinforced Plastic (FRP) insulator has a higher performance than porcelain. It is only used in domestic AC 25 kV electric railway system. Seoul Metro has developed DC 1500 V FRP insulator since 2008. FRP support insulator of flexible property is affected by the wind in tunnel. A wind tunnel test was carried out to measure influence on the insulator housing when the train passed by. The test results showed that the wind which is resulted from the passing train had a little impact on the FRP insulator shed movements.

  • PDF

Analysis of Breaking Accident of FRP Insulator Rod installed in Dead Section (절연구간 조가선 FRP 절연봉의 절단사고 원인분석)

  • Jang, Don-Guk;Lee, Ki-Won;Kim, Ju-Rak;Park, Hyun-June
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.502-505
    • /
    • 2003
  • The accidnet of breaking insulator rod leads to inturruption of moving the subway. We investigate the analysis of analysis of breaking accident of FRP insulator rod installed in dead section for catenary feeding system. To analysis of accident reason, SEM is used to analysis microscopic struture on surface of cross section of broken FRP insulator rod. At the same time, we examine the chage of atomic amount on solace of accident insulator through EDX analysis. Also, the test for tensional breaking load is condoled to check the mechanical strength.

  • PDF

The Performance Test and Mechanical Strength Analysis for 154kV Hollow Composite Insulator (154kV급 Hollow Composite Insulator의 기계적 강도해석 및 특성시험)

  • Park, Ki-Ho;Cho, Han-Gu;Han, Dong-Hee
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.495-498
    • /
    • 2002
  • This paper describes the results the problem of stress calculation and optimization into a FRP(Fiber-glass Reinforced Plastic) tube crimped into a metal end-fitting. This type of assembly is used mainly is used mainly for suspension and line post insulators. Fitting strength of FRP and flange of this study is required greatly from composite insulator to important special quality. Therefore, wish to seek analysis and mechanical strength performance that follow to FRP tube and flange of top and bottom mechanical fitting.

  • PDF

Study on Optimum Design for constitution part of Composite Insulator (Composite Insulator 구성 부품에 대한 최적 설계 연구)

  • Chung, Young-Soo;Choi, Sung-Man;Jang, Yoon-Ki;Lee, Dong-Woen;Kim, Jeong-Bae
    • Proceedings of the KSME Conference
    • /
    • 2008.11a
    • /
    • pp.1181-1186
    • /
    • 2008
  • Insulators which are used in the domestic electrical industries are mostly depended on importation from some advance countries. Even though insulators which are made of ceramic material have been mostly used domestically, the ratio of usage on composite insulators is recently being increased because of difficulties in manufacturing and high cost regarding ceramic stuffs. In this research, we are trying to develop the composite insulators which are very efficient in insulation regardless of the matter of weight. Even though the technique of manufacturing composite insulator are quite generalized worldwide at the moment, one of the most important issue is to keep security on the know-how that an ingredient of insulated material named 'SF6 gas' is included. Therefore, The aim of this paper is to improve the bonding force and air tight property between two components of composite insulator, Flange and FRP Tube.

  • PDF

Simulation and Evaluation of Bending Strength of FRP for Insulator According to Winding Angle (와인딩 각도에 따른 절연용 FRP의 굽힘강도 시뮬레이션 및 평가)

  • Park, Hoy-Yul;Kang, Dong-Pil;Ahn, Myeong-Sang;Myung, In-Hae
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.436-439
    • /
    • 2003
  • FRP has been used widely for insulator. FRP consists of fiber and resin. The fiber contributes the high strength and modulus to the composite. The fiber orientation in FRP has a great effect on the strength of FRP because the strength of FRP mainly depends on the strength of fiber. In this study, FRP was made unidirectionally by pultrusion method. Outer part of the FRP was made by filament winding method to give fiber orientation to the FRP. And outer part of FRP was also made by wrapping method. The bending strength and bending stresses of FRP rods were simulated according to the winding orientation of glass fiber. The bending strength of FRP was also evaluated. The results of simulation and evaluation were compared each other to investigate main stresses which affect the fracture of FRP. The main stresses which had a great effect on the strength of FRP were shear stresses. Bending strength of the FRP was different with the winding angle. The bending strength of $15^{\circ}$ winded FRP was the highest.

  • PDF

Breakdown and Surface Flashover Characteristics of FRP in $LN_2$ (액체질소 중 FRP의 절연파괴 및 연면방전 특성 연구)

  • 정종만;백승명;김상현
    • Progress in Superconductivity and Cryogenics
    • /
    • v.4 no.1
    • /
    • pp.119-123
    • /
    • 2002
  • In this study, we discussed the characteristics of breakdown and surface flashover of FRP in L$N_2$ for applying it to spacer of a superconducting power equipment. Fiberglass reinforced plastic(FRP) has high breakdown puncture strength and has high mechanical strength. So the research of its dielectric properties have been conducted in liquid nitrogen($LN_2$). We measured breakdown voltage of FRP and distinguished four types of surface flashover along solid insulator with arrangement of electrodes and measured the surface flashover voltages of each types of electrode arrangement. The type of a electrode set at the back of the insulator showed the worst dielectric property. The property of surface flashover depending on pressure was tested.

Study on a design and characteristics tests of polymeric insulators for subway (지하철 고분자 지지애자의 설계 및 특성 평가)

  • Han, Se-Won;Cho, Han-Goo;Song, Hong-Jun
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.514-517
    • /
    • 2003
  • Polymeric suspended insulators for subway and electrical track line had been designed and manufactured. The main elements to design polymeric insulators were the insulation ability and the optimal structure. To get the insulation ability, electrical and mechanical tests according to standards had done on housing rubbers and FRP cores and selected the sample with best properties as a insulator. The insulator shape and fitting parts with minimum electrical stress was simulated by FEM electrical field analysis program. The manufactured insulator set had been tested and estimated the electrical and mechanical according to ES and KS, and showed good characteristics in these tests.

  • PDF

Compressive Strength of FRP in Variation with Fiber Orientation (섬유의 배향에 따른 FRP의 압축강도)

  • Park, Hoy-Yul;Ahn, Myeong-Sang;Na, Moon-Kyong
    • Proceedings of the KIEE Conference
    • /
    • 2006.07c
    • /
    • pp.1349-1350
    • /
    • 2006
  • FRP has been used much for core materials of insulator. FRP consists of fiber and plastics(resin and binder). The fiber contributes strength to FRP. The fiber orientation in FRP has a great effect on the strength of FRP because the strength of FRP mainly depends on the strength of fiber. The direction of applied stress of FRP is different from the kinds of insulators. In this study, inner part of FRP rod was made unidirectionally by pultrusion method and outer part of FRP rod was made by filament winding method. Compressive strength and stress of FRP rods were simulated according to the winding orientation of glass fiber. Simulated value and real evaluated compressive strength were compared each other.

  • PDF

도시철도 직류용 FRP 지지애자 및 장간애자 특성 분석

  • Gang, Hyeon-Il;Lee, Gi-Seung;Kim, Yun-Sik;Sim, Jae-Seok
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.152-152
    • /
    • 2009
  • Direct Current Fiber Reinforced Plastic (DC FRP) insulators were developed and their mechanical and electrical characteristics were investigated. Electrical tests were carried out to measure withstanding and flashover voltages under common use frequency condition. Tensile and bending tests were performed for the mechanical characteristics. The test results showed that DC FRP insulators had superior voltage resistances and strengths to porcelain insulators.

  • PDF

Electric properties of FRP polymer stem insulator for DC power (직류용 FRP 폴리머 장간애자의 전기적 특성에 관한 연구)

  • Kang, Hyun-Il;Kim, Youn-Sik;Sim, Jae-Suk;Lee, Gi-Seung
    • Proceedings of the KSR Conference
    • /
    • 2010.06a
    • /
    • pp.1912-1917
    • /
    • 2010
  • Fiber Reinforced Plastic (FRP) insulators for direct current (DC) were developed and their electrical characteristics were investigated. Electrical tests were carried out to measure withstanding and flashover voltages under common use frequency condition. Tensile and bending tests were performed for the mechanical characteristics. The test results showed that DC FRP insulators had superior voltage resistances and strengths to porcelain insulators.

  • PDF