• Title/Summary/Keyword: Common grounding

Search Result 64, Processing Time 0.03 seconds

Assessment of Electrical Safety for Grounding System by Investigation on the Spot (현장조사에 의한 접지시스템의 전기안전성 평가)

  • Gil, Hyoung-Jun;Kim, Dong-Woo;Kim, Dong-Ook;Lee, Ki-Yeon;Kim, Hyang-Kon
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.361-364
    • /
    • 2008
  • This paper deals with assessment of electrical safety for grounding system of buildings by investigation on the spot at construction site. The investigation was carried out for grounding method, grounding type, shape of grounding electrode, grounding for lightning protection system, continuity of steelwork in reinforced concrete structure and so on. The investigation on the spot was performed by researcher, engineer with over fifteen years of industry experience all over the country. As a result of investigation on the spot to 13 buildings, common grounding method was dominant. A new grounding system based on international standards includes unity grounding system, structure grounding utilizing steel reinforced concrete, equipotential bonding. use of surge protective device.

  • PDF

Investigation on the Spot for Grounding Systems in Buildings

  • Gil, Hyoung-Jun;Kim, Dong-Woo;Kim, Dong-Ook;Kim, Hyang-Kon
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.3
    • /
    • pp.39-45
    • /
    • 2010
  • This paper deals with investigation on the spot for grounding systems of buildings based on international standards at construction sites. The investigation was carried out for grounding method, grounding type, shape of grounding electrode, grounding for a lightning protection system, continuity of steelwork in reinforced concrete structures, etc. The investigation on the spot was performed by a researcher and engineer with over fifteen years of industry experience all over the country. As a result of the investigation on the spot in 13 buildings, common grounding and structure grounding methods were dominant. The safety improvement methods include installation of equipotential bonding conductors for the connection to the main earthing terminal, equipotential bonding conductors for supplementary bonding, use of Surge Protective Devices (SPD), and safe connections between earthing conductors and the rebar.

The Plural Subject Account of Group Beliefs Using Grounding Concept

  • Koo, Ja-Rok
    • Journal of the Korea Society of Computer and Information
    • /
    • v.20 no.11
    • /
    • pp.17-23
    • /
    • 2015
  • In this paper, we propose a plural subject account of group beliefs using grounding concept, which bridges the gap between the two main approaches of ACLs, the mentalistic accounts and the social commitment accounts. The key idea of this Gilbert's plural subject account of group beliefs is to extend the grounding logic into the common ground framework for the semantics of ACLs which is fully verifiable, fully formalized and easily applicable. Thus, we formalize the proper group belief concept using common ground framework and we define the semantics of the primitive speech acts of FIPA-ACL such as inform, request and confirm as case studies. Also, we illustrate our framework on an e-commerce agent purchase negotiation and compare this proposed framework with two traditional semantics for ACLs.

A Study on How to Lower the Grounding Impedance by Needles-typed Grounding Rods (접지침봉에 의한 접지임피던스를 낮추는 방안 연구)

  • Park, Sung-Yeol
    • Journal of the Society of Disaster Information
    • /
    • v.18 no.1
    • /
    • pp.19-28
    • /
    • 2022
  • Purpose: One of the methods for preventing disasters such as fire, explosion, and electric shock caused by electricity is to perform grounding. In case of the grounding current includes a frequency component having a high, it is preferable to measure grounding impedance rather than grounding resistance. This study proposes countermeasures to reduce grounding impedance to suppress an ground potential rise due to a grounding current having a frequency component of several kHz or more. Method: General grounding rods and needles-typed grounding rods were buried in the ground, and grounding resistance and grounding impedance were measured, respectively. The characteristics of grounding impedance according to frequency were identified. Result: There was little difference in the measurement results of the grounding resistance between general grounding rods and needles-typed grounding rods. In a frequency range lower than 62.5kHz, there was little difference in the measurement results of the grounding resistance between general grounding rods and needles-typed grounding rods. In a frequency range higher than 62.5kHz, the grounding impedance of needles-typed grounding rods was reduced by about 15% than the grounding impedance of general grounding rods. Conclusion: In the commercial frequency domain, it is effective to connect several grounding rods (common grounding) to lower the grounding resistance value. In the frequency domain of several kHz or more, it is expected that needles-typed grounding rods can effectively reduce the ground potential rise due to the grounding current.

A Study on Improving of Grounding Systems for Railway Signalling Equipment (철도신호설비의 접지시스템 개선에 관한 연구)

  • Park, Ki-Bum;Lee, Tae-Hoon;Ryu, Young-Tae;Jeon, Yong-Joo
    • Proceedings of the KSR Conference
    • /
    • 2008.06a
    • /
    • pp.588-595
    • /
    • 2008
  • Recently, it is caused by environment change that is increased the number of lightning occurrence and the strength of lightning current is coming to be strong little by little. The performance of grounding system depends on how to construct. Specially the common grounding systems which uses the buried earth cable must be constructed by very well qualities because it is difficult to measure earth resistance and to manage the buried earth cable. Common grounding systems and independence grounding systems could be composed different. Against railway signalling equipment which like this is used from the environment lower part which is various it presents a standard grounding systems, and very it is hard job. We will present improvement through this paper that review grounding systems configuration condition of railway signalling equipment.

  • PDF

Proposition of Improved Neutral Grounding Method and Analytical Evaluation on Practicality in Underground Distribution System (지중배전시스템의 개선된 중성점 접지방식 제안과 실효성에 대한 해석적 평가)

  • Jeong, Seok-San;Lee, Jong-Beom;Jang, Seong-Whan;Kim, Yong-Kap;Kwon, Shin-Nam
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.60 no.3
    • /
    • pp.479-485
    • /
    • 2011
  • In 22.9kV underground distribution system, power cables are provided with multiple-point ground in which each neutral line of the distribution cable(A, B, C phases) and three-wire common grounded at every connecting section. But in such grounding methods, circulating current flows between the neutral wire and grounding wire. And power loss due to circulating current also occurs in all conductors. Therefore it is getting necessary reducing circulating current in underground distribution system. This paper presents improved grounding method to overcome such problems. The proposed grounding method eliminates circulating current in the neutral line effectively and is verified that there is no electrical problem or any ineffectiveness of operating protection systems. These analyses are carried out by EMTP/ATPDraw to compare each grounding methods in steady and transient state. This grounding method suggested in this paper can be applied on real distribution system after field tests considering elimination of circulating current was implemented.

A Protection Technique Against the Damages Caused by Lightning Surges on Information and Communication Facilities

  • Lee, Bok-Hee;Kang, Sung-Man;Ahn, Chang-Hwan
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.3C no.4
    • /
    • pp.117-122
    • /
    • 2003
  • The AC power lines and signal lines of info-communication networks are routed on overhead poles and are highly exposed to lightning strikes. Due to the potential difference between grounding points of AC power lines and signal lines, the electronic equipments connected to the signal lines can easily be damaged by lightning surges. In this work, in order to develop reliable methods of protecting information and communication facilities from lightning surges, the reliability and performance of SPDs (surge protective devices) were experimentally investigated in an actual-sized test circuit. The behaviors of SPDs against lightning surges from AC power lines and signal lines and the coordinated effects of SPD installation methods were evaluated. As a consequence, it was confirmed that the bypass arrester methods and common grounding system are both highly effective.

Applicability of Messenger Wire for Purpose of Lightning Protection

  • Seo, Hun Chul;Han, Joon;Choi, Sun Kyu;Lee, Byung Sung;Rhee, Sang Bong;Kim, Chul Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • v.11 no.1
    • /
    • pp.167-174
    • /
    • 2016
  • The Korean distribution line currently consists of overhead ground wires (OHGW), overhead distribution lines, neutral wires (NW), and messenger wires (MW). The MW is installed under the NW. The lightning protection system in Korea is focused on OHGW and lightning arrester and the MW are not considered. Therefore, this paper proposes the applicability of MW for purpose of lightning protection. For this, we analyzed the effects of lightning overvoltage according to the existence of OHGW and MW and the grounding conditions of the MW in the Korean distribution system. The grounding conditions of the MW that we took into consideration were the common or separate grounding of the MW and NW. The analysis based on the equivalent circuit of the distribution pole at each condition was performed. The distribution lines and lightning were modeled using the Electromagnetic Transients Program (EMTP). For each of the installation conditions of the OHGW and MW, the various lightning conditions were simulated and analyzed for both direct and indirect lightning. The simulation results showed that, if the OHGW was not installed in the Korean distribution system, the lightning overvoltage could be reduced by the common grounding of the MW and NW.

A Study on a grounding system of electric railway (전기철도 접지시스템에 대한 연구)

  • Lee, Ho-Jong;Shin, Myoung-Ho
    • Proceedings of the KSR Conference
    • /
    • 2007.11a
    • /
    • pp.1482-1504
    • /
    • 2007
  • An electrical railway system uses high voltage system for train traction and low voltage system for train control. Railway systems are broadly distributed across mountains, sea sides and cities. Electrical accidents provoke the death and injury of a human being and the damage of the equipment by the overcurrent due to the catenary dropping and by the overvoltage due to lightning. Grounding systems are adopted for the protections of the system from the overcurrent and the overvoltage. Isolation grounding for each system can be easily installed. However, the closed circuits between grounding systems can be occurred. The currents flow through the closed circuits cause the abnormal operation of the system. To overcome the problem of the isolation grounding, the equipotential bonding is usually adopted. The equipotential bonding should have very small grounding resistance. In this paper, we showed the transition from the isolation grounding system to the common grounding system and presented the comparison and the analysis of two grounding systems by simulation. In addition, we proposed the direction for a new grounding system of electric railway.

  • PDF

Measurement method of ground impedance for the grounding grid (접지그리드의 접지임피던스 측정 기법)

  • Lee, Bok-Hee;Choi, Jong-Hyuk;Choi, Young-Chul;Yoo, Jae-Duk;Beak, Young-Hwan;Kim, Dong-Seong;Shin, Hee-Kyung;Yoo, Yang-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1487_1488
    • /
    • 2009
  • In these days, the common grounding systems are adapted in most large structures. In order to evaluate the performance of grounding system, it is needed to measure ground impedance. Measuring methods of ground impedance for a large scale grounding systems have not been yet presented in detail. In this paper, we analyze earth mutual resistance and mutual coupling of $15{\times}15m$ grounding grid in different arrangements of auxiliary electrode. As a results, the auxiliary electrodes are installed where the error rate due to earth mutual resistance is less than 5%. Also, the potential lead is installed at obtuse angle from the current lead and the overlapped length between potential lead and grounding grid are minimized.

  • PDF