Browse > Article
http://dx.doi.org/10.5207/JIEIE.2010.24.3.039

Investigation on the Spot for Grounding Systems in Buildings  

Gil, Hyoung-Jun (Electrical safety Research Institute, Senior researcher)
Kim, Dong-Woo (KESCO)
Kim, Dong-Ook (KESCO)
Kim, Hyang-Kon (KESCO)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.24, no.3, 2010 , pp. 39-45 More about this Journal
Abstract
This paper deals with investigation on the spot for grounding systems of buildings based on international standards at construction sites. The investigation was carried out for grounding method, grounding type, shape of grounding electrode, grounding for a lightning protection system, continuity of steelwork in reinforced concrete structures, etc. The investigation on the spot was performed by a researcher and engineer with over fifteen years of industry experience all over the country. As a result of the investigation on the spot in 13 buildings, common grounding and structure grounding methods were dominant. The safety improvement methods include installation of equipotential bonding conductors for the connection to the main earthing terminal, equipotential bonding conductors for supplementary bonding, use of Surge Protective Devices (SPD), and safe connections between earthing conductors and the rebar.
Keywords
Investigation; Grounding System; International Standards; Continuity;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Hyoung-Jun Gil, Chung-Seog Choi, Hyang-Kon Kim, Bok-Hee Le, “Characteristics of Potential Gradient for the type of Structure Grounding Electrode”, The Korean Institute of Electrical Engineers, Vol.54C, No.8, pp.371-377, 2005.   과학기술학회마을
2 Chung-Seog Choi, Hyang-Kon Kim, Hyoung-Jun Gil, Woon-Ki Han, Ki-Yeon Lee, “The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode Using Reduced Scale Model”, IEEJ Trans. PE, Vol. 125, No. 12, pp.1170-1176, 2005.   DOI
3 Ronald P. O’Riley, “Electrical Grounding”, Delmar Thomson Learning, pp.40-60, 2002.
4 Korean Standards Association, “KS C IEC 60364-4-41”, 2005.
5 Korean Standards Association, “KS C IEC 60364-5-53”, 2005.
6 Korean Standards Association, “KS C IEC 62305-3”, 2007.
7 Ki-Hong Lee et al, “Deveiopment of the Earth Termination SystemModel based on IEC Standard in Apartments”, Land & Housing Institute, pp.51-77, 2005.
8 Hyoung-Jun Gil, Chung-Seog Choi, Bok-Hee Lee, “Research on Comparison of Individual and Connecting Grounding Electrode for Potential Rise Distribution”, The Korean Institute of Illuminating and Electrical Installation Engineers, Vol.22, No.2, pp.57-62, 2008.   과학기술학회마을   DOI
9 Bok-Hee Lee, “Protection of Information and Communication Facilities against Lightning”, Inha University Publishing Department, pp.197-221, 2004.
10 Bok-Hee Lee et al, “Development of Guidelines for Human Body Safety and Protection Measures of TN-C-S System”, Korea Electric Association, pp.8-45, 2006.