Abstract
In 22.9kV underground distribution system, power cables are provided with multiple-point ground in which each neutral line of the distribution cable(A, B, C phases) and three-wire common grounded at every connecting section. But in such grounding methods, circulating current flows between the neutral wire and grounding wire. And power loss due to circulating current also occurs in all conductors. Therefore it is getting necessary reducing circulating current in underground distribution system. This paper presents improved grounding method to overcome such problems. The proposed grounding method eliminates circulating current in the neutral line effectively and is verified that there is no electrical problem or any ineffectiveness of operating protection systems. These analyses are carried out by EMTP/ATPDraw to compare each grounding methods in steady and transient state. This grounding method suggested in this paper can be applied on real distribution system after field tests considering elimination of circulating current was implemented.
Keywords
Circulating current; Underground cable; Neutral wire; Combined distribution system; Grounding method; EMTP;
Citations & Related Records

Times Cited By SCOPUS : 0
연도 인용수 순위
  • Reference
1 한국전력공사, "배전지중설계기준 5900 부록", 2003
2 한국전력공사, "22,9kV 동심중성선 전력케이블', 2001
3 대한전기협회 배전규정전문위원회, "배전규정", 1997
4 한국전력공사, "설계기준 - 3500(접지공사)", 1999
5 한국전력공사, "설계기준 - 5001(총칙)", 1998
6 전명수, 송중호, "22.9kV 지중배전계통케이블의 동심중성선에 흐르는 순환저류 제거방안 및 효과
7 IEEE Std 1299/C62.22.1-1996 "IEEE Guide for the Connection of Surge Arresters to Protect Insulated, Shielded Electric Power Cable Systems", 1996
8 IEEE Std. C62.22-1997 "IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating Current Systems", 1997
9 한국전력공사, "배전계통 절연협조 기준정립에 관한 연구", 2003
10 EEUG, "ATPDraw version 5.6 Rule Book", 2010
11 Lszl Prikler, "ATPDraw version 5.6 user manual", Preliminary Release No. 1.0, 2009
12 임광식, 이종범, "지중송배전계통에서 과도상태시 공동 접지의 영향 분석", 2007
13 정채균, 이종범, "퍼지추론시스템 기반 지중송전계통 보호용 거리계전 알고리즘 개발", 2007
14 한국전력공사, "지중편설계기준 1650", 2004