• Title/Summary/Keyword: supply ventilation air

Search Result 181, Processing Time 0.022 seconds

A Study on Ventilation Effectiveness in the Non-isothermal Supply using Mixing and Displacement Ventilation Systems (비등온 급기조건에서 환기방식에 따른 환기효율 특성에 관한 연구)

  • 이재근;강태욱;윤석구;구재현;한정균;조민철
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.13 no.8
    • /
    • pp.739-745
    • /
    • 2001
  • The objective of this research is to analyze the ventilation effectiveness in the non-isothermal air supply using mixing and displacement ventilation systems for indoor air quality control and management. In this study, a ventilation effectiveness is evaluated in a simplified model chamber using a tracer gas technique of $CO^2$ gas injected into a supply duct as a function of ventilation rates, supply/extract sites and cooling/heating air supply. The ventilation effectiveness decreased with increasing ventilation rate on the cooling and heating conditions. And the ventilation effectiveness of case 3 (down supply and upper extract) was better thant that of case 1(upper supply and upper extract) and case 2(upper supply and down extract) with the cooling supply conditions. but for the heating supply air conditions, the ventilation effectiveness of case 2 was better than that of case 3 and case 1.

  • PDF

A Study on the Reaching Time of Setting Temperature with Ventilation Air (급기환기량에 따른 공조기의 설정온도 도달특성 분석 연구)

  • Kang Tae-Wook
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.30 no.1
    • /
    • pp.50-57
    • /
    • 2006
  • This study describes to analyze the cooling load characteristics for a room air conditioner as a function of supply ventilation air when an air conditioner is running An experimental apparatus consists of a test room, a room air conditioner, a humidifier, an electrical heater a supply fan and a controller The reaching time to the inside setting temperature of the room air conditioner with is evaluated theoretically and experimentally in a conditioned space cooling loads such as supply ventilation air, lighting, occupancy and infiltration. In the conditions of cooling loads for the supply ventilation air of 9.5 L/s(0.98 ACH). lights. one Person, and infiltration, the reaching time to the inside setting temperature ($27\;^{\circ}C$ dry-bulb) increases up to $35\%$ more than for no supply ventilation air condition. Theoretical modelling of the reaching time shows good agreement with experimental results.

A Study on the Ventilation Effect by Establishment Location of Supply Opening and Exhaust Fan of Bathroom in Apartment House (공동주택 화장실의 급기구 및 배기팬 설치 위치에 따른 환기효과에 관한 연구)

  • 함진식
    • Proceeding of Spring/Autumn Annual Conference of KHA
    • /
    • 2002.11a
    • /
    • pp.321-326
    • /
    • 2002
  • To design mechanical ventilation for bathroom of apartment houses where air supply and exhaust are taken Into consideration, mock-ups of ventilation systems, widely used in bathroom of apartment houses with an area of 100$m^2$, were made and installed in a laboratory, These ventilation mock-ups were available for control of air supply and exhaust, and the size of supply openings were 40cm$\times$1cm, 40cm$\times$3cm, 40cm$\times$5cm. They were installed at five positions, spaced 40cm at a height of 25cm from the floor. and the position of exhaust fans were four corners and center Exhaust fan established each one on corner of the ceiling and one in center. As result that measure ventilation effect by each condition, size of hole that supply air is big, and ventilation effect took effect to be good establishment location is low, Also, distance of exhaust fan is far with hole that supply air, ventilation effect took effect by superior thing.

  • PDF

A Study on the Mechanical Ventilation System of Bathroom in Apartment House (공동주택 화장실의 기계 환기시스템에 관한 연구)

  • 함진식
    • Journal of the Korean housing association
    • /
    • v.12 no.3
    • /
    • pp.141-148
    • /
    • 2001
  • To design mechanical ventilation for bathroom of apartment houses where air supply and exhaust are taken into consideration, mock-ups of ventilation systems, widely used in bathroom of apartment houses with an area of 100$\textrm{m}^2$, were made and installed in a laboratory. These ventilation mock-ups were available for control of air supply and exhaust, and the sizes of supply openings were 40cm${\times}$1cm, 40cm${\times}$3cm, and 40cm${\times}$5cm. They were installed at five positions, spaced 45cm at a height of 5cm from the floor. The exhaust fan was designed for its operating voltage to be set to five steps(100V, 130V, 150V, 180V and 220V) in order to control its air flow rates. When the size and position of each supply opening were changed with the wind velocity of the exhaust fan set to the step 5, the ventilation rates were measured and analyzed by the concentration decay method of tracer gas method, in order to present an efficient mechanical ventilation system. The results of the study revealed that the ventilations rates would increase in the presence of supply openings, compared to the absence of supply openings, and that the larger the size of the supply opening, the more the ventilation rates. Therefore, it was found necessary to take air supply into consideration.

  • PDF

An Experimental Study on the Ventilation performance in a Test Chamber and Office Room (모형실과 실공간에서의 환기성능에 관한 실험적 연구)

  • Yoon, Suk-Goo;Ku, Jae-Hyun;Yun, Ok-Chun;Han, Jung-Gun;Lee, Jae-Keum;Cho, Min-Chul;Kang, Tae-Wook;Lee, Kam-Gyu
    • Proceedings of the KSME Conference
    • /
    • 2000.11b
    • /
    • pp.520-525
    • /
    • 2000
  • This research is to analyze the ventilation performance of mechanical ventilation systems for indoor air quality control and management. A ventilation performance with supply sites is evaluated in a test model chamber and office room. A $CO_2$ gas as a tracer gas is used to measure the ventilation performance. The ventilation performance is found to increase with increased the ventilation rate. The ventilation performance is analysed with 55% at the supply air of 570 lpm and with 20% at the supply air of 100 lpm in a test chamber. The ventilation performance is better than 15% comparing with natural decay at the supply of 570 lpm in office room.

  • PDF

A Study on Characteristic Analysis for Indoor Ventilation Performance of Mechanical Ventilation System (기계 환기시스템의 실내 환기성능 특성 해석에 관한 연구)

  • Ku, Jae-Hyun
    • Journal of the Korean Institute of Gas
    • /
    • v.16 no.2
    • /
    • pp.31-37
    • /
    • 2012
  • This paper describes to analyze the ventilation performance of a room air conditioner for indoor comfort control. An experimental apparatus consists of a test room, the room air conditioner, a tracer gas measurement system, a supply fan and a controller. Ventilation performance as a function of human occupancy is evaluated with supply ventilation air using a tracer gas technique of CO2 gas in the test room. The ventilation performance is evaluated in a step-down method based on ASTM Standard E741-83 and is found to increase with increasing supply ventilation rate. The CO2 gas concentration is decayed rapidly without human occupancy. The ventilation performance without human occupancy increases up to 55% and the ventilation performance with one person increases up to 25% at the supply air of 570 lpm comparing with a natural reduction after one hour. A modeling for ventilation performance of a room air conditioner in a test room is presented using experimental datum.

Numerical simulation of turbulent air-flow in a closed engine room with heat source in a ship (열원이 있는 밀폐된 선박 기관실에서의 난류기류에 관한 수치적 연구)

  • 박찬수
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.22 no.1
    • /
    • pp.100-107
    • /
    • 1998
  • Ventilation of the marine engine room is very important for the health of the workers as well as the nomal operation of machines. To find proper ventilation conditions of this engine room, numerical simulation with standard k-.epsilon. model was carried out. In the present study, the marine engine room is considered as a closed space with a heat source and forced ventilation ducts. The injection angle of air supply is found to be important. Injection with downword angle depresses recirculation flow, causing a strong steam in the wider space of the room. Ventilation and removal of the released heat are promoted with this pattern. There is a possibility of local extreme heating at the upper surface of engine when supply and exhaust ports of air are in bilateral symmetry. The effect of the increase of exhaust port area on ventilation decreases as the number of supply port increases.

  • PDF

A study on the Improvement of Ventilation Performance in Apartment House According to the Location of Exterior Air-Vents (공동주택에서의 실외 급.배기구 위치에 따른 환기효율 향상 연구)

  • Park, Jin-Chul;Yu, Hyung-Kyu;Cha, Jin-Young
    • Journal of the Korean Solar Energy Society
    • /
    • v.25 no.2
    • /
    • pp.71-79
    • /
    • 2005
  • In this study, the ventilation performance of mechanical ventilation system in apartment House was analyzed through model test according to characteristics of air-vent. Then adequate interval of air-vent was suggested using computer simulation which will create comfort environment through improvement of ventilation performance in apartment house. The result of experiment with separation plate to prevent mixture of contaminated exhaust air with fresh supply air, the ventilation efficiency improved about 10%. The result of simulation with horizontal location of exterior air-vent, contaminated exhaust air is mixed regardless of interval variation. Consequently, mixture of the exhaust air can be prevented through locating the supply air vent on the top side and exhaust air vent on the lower side.

A Study on the Ventilation Effect by Various Location of Air Intake and Exhaust Fan of Bathroom in Apartment Housing (공동주택 화장실의 급기구 및 배기팬 설치위치에 따른 환기효과에 관한 연구)

  • Ham Jin Sik;Lee Kwang Myung
    • Journal of the Korean housing association
    • /
    • v.15 no.5
    • /
    • pp.77-84
    • /
    • 2004
  • The mock-ups of ventilation system, which has been widely adopted for the bathroom with the area of 100 $m^2$ apartment housing, were established and tested to design mechanical ventilation for apartment housing bathroom where air supply exhaust are relatively important. These ventilation mock-ups were capable of controlling intake and exhaust, which has the size of supply openings as 40cm${\times}$1cm, 40cm${\times}$3cm, 40cm${\times}$5cm. They were established at five locations, spaced 40cm from each other at a height of 25cm from the floor. The exhaust fans were located at four corners and center of the ceiling. The results this ventilation effect measurement by different condition are showing that when the size of air supply is bigger and the location is lower, the effect of ventilation was relatively higher. In addition, as the distance between exhaust fan and air supply was farther, the ventilation effect were getting highly efficient.

Performance Evaluation of Multidrop Chamber Ventilation System in Apartment (공동주택 적용을 위한 다분기챔버 환기 시스템의 성능평가에 관한 연구)

  • Kim, Sung Soo;Sohn, Jang yeul
    • KIEAE Journal
    • /
    • v.9 no.4
    • /
    • pp.17-22
    • /
    • 2009
  • It is common to design the duct branches where to supply the required air flow for individual room in residential apartment house. However it is difficult to adjust the air volume adequately in small air duct branches in residential ventilation system. The purpose of this study is to figure out the performance of Multidrop chamber coupling system for the residential ventilation system. The experiments were designed to simulate apartment of $84m^2$ and established multidrop chamber duct and general duct on the ceiling of the apartment. Distribution performance of air supply rate were evaluated in this experiments. As a result, distribution performance of air supply rate in the general duct is different from designed air supply rate by about 35% ~ 50% and about 10% in the multidrop chamber system. In additional the sound insulation performance of the multidrop chamber system decreased about 20% compared with general duct system. Therefore, the multidrop chamber system is considered to satisfy proper air supply rate of each room and to improve the sound insulation performance in apartment Houses.