Browse > Article

A study on the Improvement of Ventilation Performance in Apartment House According to the Location of Exterior Air-Vents  

Park, Jin-Chul (School of Architecture, Chung-Ang University)
Yu, Hyung-Kyu (Dept. of Architecture, graduate School, Chung-Ang University)
Cha, Jin-Young (Centre for Sustainable Architecture and Building Research, Chung-Ang University)
Publication Information
Journal of the Korean Solar Energy Society / v.25, no.2, 2005 , pp. 71-79 More about this Journal
Abstract
In this study, the ventilation performance of mechanical ventilation system in apartment House was analyzed through model test according to characteristics of air-vent. Then adequate interval of air-vent was suggested using computer simulation which will create comfort environment through improvement of ventilation performance in apartment house. The result of experiment with separation plate to prevent mixture of contaminated exhaust air with fresh supply air, the ventilation efficiency improved about 10%. The result of simulation with horizontal location of exterior air-vent, contaminated exhaust air is mixed regardless of interval variation. Consequently, mixture of the exhaust air can be prevented through locating the supply air vent on the top side and exhaust air vent on the lower side.
Keywords
Ventilation Performance; Exterior Air-Vents; CFD(Computational Fluid Dynamic);
Citations & Related Records
연도 인용수 순위
  • Reference
1 공동주택단지내 풍력발전 시스템의 적용방안에 관한 연구 /
[ 강소연 ] /
2 한국기후표 제I권 /
[ 기상청 ] /
3 공동주택 환기시스템의 환기효율에 관한 실험적 연구 /
[ 김기혁 ] /
4 공동주택의 환기효율 향상을 위한 환기계획에 관한 연구 /
[ 김기훈 ] /
5 인구주택총조사보고서 /
[ 통계청 ] /
6 Wind and Solar Power System /
[ Patel, Mukun R. ] /