• Title/Summary/Keyword: insulation deterioration

Search Result 170, Processing Time 0.024 seconds

A Study on the Physical Characteristics of the Low-voltage Circuit Breaker Based on the Accelerated Degradation Test (가속 열화 시험에 따른 저압용 차단기의 물리적 특성에 관한 연구)

  • Sin dong, Kang;Jae-Ho, Kim
    • Journal of the Korean Society of Safety
    • /
    • v.37 no.6
    • /
    • pp.1-8
    • /
    • 2022
  • This study analyzed the characteristics of insulation resistance and operating time based on an accelerated degradation test of a low-voltage circuit breaker. The experimental sample used a molded case circuit breaker (MCCB) and an earth leakage circuit breaker (ELCB). After measuring the insulation resistance of the circuit breakers, the leakage current was affected by an external rather than an internal structure. Furthermore, the insulation resistance of the circuit breakers with accelerated degradation was measured using a Megger insulation tester. In the accelerated degradation test, aging times of five, ten, 15, and 20 years were applied according to a temperature derived using the Arrhenius equation. Circuit breakers with an equivalent life of ten, 15, and 20 years had increased insulation resistance compared to those with less degradation time. In particular, the circuit breaker with an equivalent life of ten years had the highest insulation resistance. Component analysis of the circuit breaker manufactured through an accelerated degradation test confirmed that the timing of the increase in insulation resistance and the time of additive loss were the same. Finally, after analyzing the operating time of the circuit breakers with degradation, it was confirmed that the MCCB did not change, but the ELCB breaker failed.

Development of Equipment Measuring Insulation Resistance of High-Power Cables in Operation at Power Station (발전소에서 운전 중인 고전력 케이블의 절연저항의 변화를 감시하는 장치의 개발)

  • Um, Kee-Hong;Kim, Bo-Kyeong
    • The Journal of the Institute of Internet, Broadcasting and Communication
    • /
    • v.16 no.4
    • /
    • pp.159-164
    • /
    • 2016
  • In or to generate high electric power in increasing demand, power station should operate facilities to meet requirement. The scale of electric power equipment is increasing in both size and complexity. With unexpected accidents at power facilities or power stations happening, substantial socioeconomic losses in an industrial society is caused. A major cause of unexpected accidents is deterioration of dielectrics, isolating two conductors electrically. In order to detect the deterioration processes of power cables, the operation status of power cables should be monitored on a regular basis. We have invented and installed equipment at Korea Western Power Co., Ltd., located in Taean, in order to predict and prevent the deterioration status of dielectrics destruction of power cables. The main line in Y-connection to the secondary coils of transformer delivers electric power to the external devices. The equipment we developed is the one measuring insulation resistance of cables operation in on/off status with respect to the main line. We present the equipment in terms of operation and configuration of hardware side.

Investigation on DC Breakdown Strength Characteristics of Power Cable Insulation (전력 케이블 절연재에 대한 DC절연파괴강도특성 고찰)

  • Lee, Han-Joo;Jung, Eui-Hwan;Joe, Sung-Hoon;Yoon, Jae-Hoon;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2010.06a
    • /
    • pp.86-86
    • /
    • 2010
  • Recently, CV, CNCV, CNCV-W cable are used to transmit and distribute electric power. And a lot of researchers put more effort to realize high performance. The dielectric breakdown strength characteristic is a standard to design insulators. Examination of that is a main factor to determine long term insulation performance, which is used to diagnose Insulation deterioration. In this paper, we prepared XLPE, XLPE/nano-filler, LDPE/nano-filler for comparing each of the dielectric breakdown strength characteristics.

  • PDF

A Study on the New Criteria for Assessing the Insulation Deterioration of Generator Stator Winding (발전기 고정자 권선의 새로운 절연열화 판정기준 설정에 관한 연구)

  • Hwang, D.H.;Kim, Y.J.;Kim, J.B.;Jeon, J.W.;Kim, H.G.;Park, J.J.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1692-1695
    • /
    • 1997
  • This paper describes the relationship between the various non-destructive parameters and the breakdown voltage for the 17 kV, 300 MVA and the 22 kV, 500 MVA generators stator bars with polyester and epoxy/mica insulation respectively. Also, this study reports the results of an investigation into the factors which can assess the insulation condition of generator stator winding. Furthermore, a new parameter, Partial Discharge Index(PDI), is introduced as the valuable parameter for the assessment of insulation condition. The ratio between partial discharge increment and the stepwise voltage increment from the Discharge Inception Voltage (DIV) at the characteristic or resonant frequency band shows the close relationship between the breakdown voltage and PDI.

  • PDF

Analysis of PD Patterns Depending on Defect Types in Insulation System (절연계의 결함별 부분방전 패턴분석)

  • Park, Chan-Yong;Kim, Hwang-Kuk;Kim, Sung-Wook;Ji, Hong-Keun;Kil, Gyung-Suk
    • Proceedings of the KSR Conference
    • /
    • 2009.05a
    • /
    • pp.912-918
    • /
    • 2009
  • In this paper, we carried out a comparative analysis of partial discharge(PD) patterns caused by deterioration of cast-resin and oil insulation systems. Various electrode systems were fabricated such as needle-needle, needle-plane and plane-plane to simulate defects that may exist in the insulation system of transformers. A low-noise amplifier which has a gain of 40 dB and a frequency bandwidth of 500 kHz $\sim$ 30 MHz (-3 dB) was designed to detect small PD signals. From the analysis of acquired PD signals, we could find that a unique PD pattern is formed according to types of defect. These data will be applied usefully to diagnose insulation condition of transformers.

  • PDF

A study on insulation characteristics with AC Breakdown Test for Stator Winding of 3.3kV class Induction Motor (절연파괴시험을 통한 3.3kV 유도전동기의 절연특성 연구)

  • Lee, Dong-Geun;Lee, Kwang-Ho;Choi, Kyo-Nam;Kim, Hyun-Il;Kwak, Hee-Jin;Oh, Bong-Keun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2118-2122
    • /
    • 2005
  • This test was performed to assess the corelation of insulation deterioration condition with breakdown voltage of the stator winding of 3.3kV class induction motors which have been in service for 10 years after being installed in 1993. The insulation diagnostic tests include resistance, polarization index(P.I), dissipation factor$({\Delta}tan{\delta})$, maximum partial discharges (Qmax) and AC breakdown test. we evaluated the corelation of insulation diagnostic test with AC breakdown test for stator wilding of high voltage induction motor.

  • PDF

Deterioration Analysis of Electric Systems in Diesel Electric Locomotives (디젤전기기관차 전기장치 노후도 평가)

  • Kim, Jeong-Guk;Baek, Seung-Koo;Lee, Chang-Young;Kwon, Sung-Tae;Kwon, Seok-Jin
    • Proceedings of the KSR Conference
    • /
    • 2008.11b
    • /
    • pp.1213-1219
    • /
    • 2008
  • The deterioration analysis of electric systems in diesel electric locomotives, which were used for over 30 years, was performed to understand current wear and safety information. The electric systems include electric generation, traction motors, control units, high-voltage cables, and wires. In this investigation, various types of performance testing, such as insulation resistance measurement and degradation tests, were conducted to assess the degree of current deterioration. Moreover, an infrared camera was employed to verify abnormal heating in cables and wires. In this paper, the new techniques for evaluation of deterioration in electric systems have been introduced.

  • PDF

Site Evaluation and Application of the On-line and Off-line Test for the 13[kV] Class Hydropower Generator Stator Windings (13[kV]급 수력발전기 고정자 권선의 운전 및 정지 중 진단시험 현장적용 평가 및 분석)

  • Chang, Jeong-Ho;Lee, Dong-Keun;Lee, Heung-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.11
    • /
    • pp.73-82
    • /
    • 2011
  • The solid insulation system of stator windings in high voltage rotational machines is usually aging in accordance with long time operation. The partial discharge test have been known to check whether insulation deterioration exist or not, and the PD test can effectively diagnose a solid insulation condition regardless of during operation(on-line) or not(off-line). The on-line PD measurement have proven to be a successful technique in monitoring stator insulation condition nowadays. This paper describes the characteristics of comparing the on-line PD measurement data using PDMS-HG(Partial Discharge Monitoring System for Hydro-electric Generator) installed in field with the off-line diagnosis measurement data(insulation resistance, winding resistance, PI, ${\Delta}tan{\delta}$ and PD) on hydro generator(13[kV]) stator windings. These results make good use of managing rotational machines through evaluating the solid insulation condition of stator windings.

Judgement Criterion of Insulation Deterioration in 4.16kV and 6.6kV Motor Stator Windings (4.16kV 및 6.6kV 전동기 고정자 권선의 절연열화 판정기준)

  • Kim, Hee-Dong
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.4
    • /
    • pp.788-794
    • /
    • 2009
  • To assess the condition of stator insulation, nondestructive tests were performed on twenty five coil groups and twenty six motors. The stator windings has nominal ratings of 6.6kV and are classified into five coil groups ;one group with healthy insulation and four groups with four different types of artificial defects. After completing nondestructive tests, the AC voltage applied to the stator windings was gradually increasing until insulation failure in order to obtain the breakdown voltage. No.1, No.2 and No.6 of 6.6kV motors failed near rated voltage of 14kV, 8.7kV and 14kV, respectively. The breakdown voltage of three motors was lower that expected for good quality coils(14.2kV) in 6.6kV motors. No.3 and No.6 of 4.16kV motors failed near rated voltage of 5.6kV and 4.2kV, respectively. Almost all of failures were located in a line-end coil at the exit from the core slot. The breakdown voltages and the types of defects showed strong relation to the stator insulation tests such as in the case of AC current, dissipation factor(tan${\delta}$) and partial discharge magnitude.

Analysis of Heat Loss Due to Time Dependent Aging of Insulation Applied to Office Building (업무용 건축물에 적용된 단열재의 경년열화에 따른 열손실량 분석)

  • Lee, Do-Hyung;Nah, Hwan-Seon
    • Journal of the Korean Solar Energy Society
    • /
    • v.37 no.5
    • /
    • pp.65-75
    • /
    • 2017
  • In this study, the change of heat loss due to the degree of deterioration of the XPS insulation in KEPCO's office buildings is analyzed. The acceleration aging test of the XPS insulation was carried out according to the test method A of KS M ISO 11561: 2009. The performance of the insulation was analyzed by applying it to the three - dimensional steady state heat transfer analysis program. The acceleration aging test of the XPS insulation, show that the thermal resistance performance decreased by 1.44% at the A regional headquarters, 0.85% at the B regional headquarters, 6.41% at the C branch office, 7.76% at the D regional headquarters, 8.51% at the E branch office, and by 8.54% at the F branch office respectively. Using simulation, we determined that the thermal resistance value of E branch office decreased by 8.04%, while its heat loss increased by 8.52%. At A regional headquarters, the thermal resistance decreased by 1.38%, and the heat loss increased by 1.51%. At D regional headquarters, these value are 6.82% and 7.17%, respectively.