Abstract
The solid insulation system of stator windings in high voltage rotational machines is usually aging in accordance with long time operation. The partial discharge test have been known to check whether insulation deterioration exist or not, and the PD test can effectively diagnose a solid insulation condition regardless of during operation(on-line) or not(off-line). The on-line PD measurement have proven to be a successful technique in monitoring stator insulation condition nowadays. This paper describes the characteristics of comparing the on-line PD measurement data using PDMS-HG(Partial Discharge Monitoring System for Hydro-electric Generator) installed in field with the off-line diagnosis measurement data(insulation resistance, winding resistance, PI, ${\Delta}tan{\delta}$ and PD) on hydro generator(13[kV]) stator windings. These results make good use of managing rotational machines through evaluating the solid insulation condition of stator windings.
Keywords
Hydro Generator; Stator Winding; Partial Discharge; On-line PD; Off-line Diagnosis;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 Partial discharge measurements. IEC 60270, 2001.
2 강동식 외, "고압 회전기 On-line 부분방전 측정용 Ceramic Coupler 특성", 대한전기학회 논문지, Vol.51C, No. 5. pp. 205-212, 2002.   과학기술학회마을
3 I.M. Culbert, H. Dhirani and G.C. Stone, "Handbook to Assess the Insulation Condution of Large Rotating Machines (Volume 16)", EPRI publication EL-5036, 1989.
4 IEEE Std 1434-2000, "IEEE Trial-Use Guide to the Measurement of Partial Discharges in Rotating Machinery", Aug. 2000.
5 강동식 외, "13[kV]급 수력발전기 고정자 권선용 On-line 부분방전 측정 시스템 개발 및 현장적용 평가", 대한전기 학회 논문지, Vol.55C, No4. pp. 189-198, 2006.4.   과학기술학회마을
6 한국수자원공사, "특별고압회전기 및 케이블의 절연열화 진단연구" pp 68-69, 1990.11.
7 산업자원부, "수력발전기 고정자 권선의 운전중 부분방전 진단시스템 개발", 최종보고서, 2006.7.
8 C. Hudon and M. Belec, "Partial discharge signal Interpretation for Generator Diagnostics", IEEE Trans. on Dielectrics and Electrical Insulation, Vol.12, No. 2, pp. 297-319, 2005.   DOI