• Title/Summary/Keyword: Water-hammer

Search Result 165, Processing Time 0.036 seconds

A Study of Surge Pressure Absorption by Water Hammer Arrester in Water Supply Piping System (워터 햄머 흡수기의 압력흡수 효과에 관한 연구)

  • 이용화;유지오
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.12 no.12
    • /
    • pp.1066-1072
    • /
    • 2000
  • This study is to investigate the pressure wave characteristics and the absorption of maximum and minimum pressure generated by instantaneous valve closure at the end of the straightening copper piping system with and without a water hammer arrester. Experiments were conducted under the following conditions : initial pressure 1~5 bar, flow velocity 0.6~3.0 m/s, water temperature $20^{\circ}C$ and air volume of water hammer arrester $80~180^cm^3$. Experimental results show that the optimum air volume of water hammer arrester is 110㎤.

  • PDF

Application & Examination of the Plan for Optimum Stability through Water-hammer in Pipe Line and Booster Pump Station (관로계통 및 가압펌프장 수격에 따른 최적 안정성 확보방안)

  • Ra, Beyong-Pil;Park, Jong-Ho
    • The KSFM Journal of Fluid Machinery
    • /
    • v.12 no.5
    • /
    • pp.19-24
    • /
    • 2009
  • This paper is performed to find out the stability of water-hammer in pipe line and pump station that is happened when additional water needs demanded. At first, the water supply construction project is planned to supply $6,000\;m^3/day$ through 17.9 km pipe line. But additional demand ($1,200\;m^3/day$) happened from Cheong-ra water reservoir. In this situation, air-chamber($4\;m^3$) and vacuum breaker valve(${\varphi}100\;mm$) are needed to prevent water-hammer. When the additional water is supplied, the existing facilities (air-chamber, vacuum breaker valve) are sufficient to alleviate shock not changing capacity alteration, judging from the airspace change and rise. Therefore, there is no problem for water-hammer by installing air-chamber($4\;m^3$) and vacuum breaker valve(${\varphi}100\;mm$) at the top of Yeo-ju hill.

An Experimental Study on Vibration Control of Water Hammering in Water Pipe System (급수배관시스템의 수충격 진동제어를 위한 실험적 연구)

  • Lee, Jang-Hyun;Lee, Hyo-Haeng;Kwon, Byoung-Ha;Oh, Jin-Woo
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.453-458
    • /
    • 2008
  • Pump of high lift use to development of a technological level according as a building grow big. Water-Hammer to increase by valve of fast to closing agreeably to pipe laying to accept electronic valve, because by a damage of piping-system and the devil knows injury of vibration. Water-Hammer take a low effect to various method for solve. A New type manufacture develop and testing of pipe line to same to axis use to accumulator for water-Hammer to low effect and liner control of pressure. Impact-pressure of absorption ability and confirmation to decrease of vibration level through to preexistence manufactures and comparative test. Water-hammer and pipe vibration make low of piping system.

  • PDF

EIGENVALUE APPROACH FOR UNSTEADY FRICTION WATER HAMMER MODEL

  • Jung Bong Seog;Karney Bryan W.
    • Water Engineering Research
    • /
    • v.5 no.4
    • /
    • pp.177-183
    • /
    • 2004
  • This paper introduces an eigenvalue method of transforming the hyperbolic partial differential equations of a particular unsteady friction water hammer model into characteristic form. This method is based on the solution of the corresponding one-dimensional Riemann problem that transforms hyperbolic quasi-linear equations into ordinary differential equations along the characteristic directions, which in this case arises as the eigenvalues of the system. A mathematical justification and generalization of the eigenvalues method is provided and this approach is compared to the traditional characteristic method.

  • PDF

Dynamic Characteristics of Water Hammer Arresters for Building Service Applications

  • Cha, Dong-Jin
    • International Journal of Air-Conditioning and Refrigeration
    • /
    • v.11 no.1
    • /
    • pp.40-49
    • /
    • 2003
  • Dynamic characteristics of water hammer arresters installed in a building water supply system have been investigated numerically by utilizing a commercial code that employs the method of characteristics. Some preliminary results with those arrester models produced in this study agree well with the previously reported. Then, the arrester models have been incorporated into a water supply pipe system of a 59 $m^2$apartment unit constructed by a leading construction company, and their dynamic characteristics have been investigated, especially on the reduction in the water hammer pressure. It is found that the setting of the arresters in the pipe system, which is recommended by the company, may not be proper for reducing the pressure down below 1,082.0 kPa (10.0 kg$g_f$/$cm^2$) when quick-closure valves in the pipe system are closed within 30 ms at the static pressure of 542.6 kPa (4.5 kg$g_f$/$cm^2$). More arresters in the system may be required to meet pressure criteria stated on the related standards and codes.

Consideration of Pressure-Rise and Water Hammer for Pipe System in Relation to Start-Up and Sudden Stop of the Pump (펌프 기동 및 정지에 따른 배관 압력상승과 수격작용 영향 고찰)

  • Heo, Min Woong;Min, Ji Ho
    • Transactions of the Korean Society of Pressure Vessels and Piping
    • /
    • v.13 no.1
    • /
    • pp.69-74
    • /
    • 2017
  • In the fire protection system or fire fighting water supply system, the jockey pump is generally installed for the prevention of the pressure decrease of pipes, the frequent driving of the fire pump and protection the pipes from the water hammer. In this paper, the pressure-rise in fire fighting water distribution pipes in condition of pipe pressurization by the surge tank at the start-up and the sudden-stop of the fire pump without additional installation of jockey pump is considered by using simple formula calculations and the evaluation of water hammer occurrence in condition of pipe pressurization by the surge tank is included. As a result, the pressure-rise of pipes is less than the pipe design pressure at the condition of pump's start-up and sudden stop, and the possibility of water hammer occurrence is remarkably low due to pressurization of the pipes by the surge tank.

An analysis of water hammer in pipeline systems with pump (펌프관로계의 수격현상 해석)

  • 이명호
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.22 no.1
    • /
    • pp.92-99
    • /
    • 1998
  • Unsteady flow problems created by hydraulic transients in pipeline systems with pump are of significant importance because they can cause excessive pressure, cavitation, vibration and noise. In this paper, an analysis of transient flow for the pump pipelines is developed by means of the characteristic method. The calculated results of the program to simulate water hammer due to sudden valve closure in a simple pipeline are compared with those of the analytical method. Expecially the water hammer due to power failure in pump pipeline system with surge tank was simulated. As the results, both the upsurge and the downsurge along the pipeline are reduced.

  • PDF

Water Hammer in the Pump Pipeline System with an Air Chamber (에어챔버가 설치된 가압펌프 계통에서의 수격현상)

  • Kim, Sang-Gyun;Lee, Kye-Bock
    • Journal of Energy Engineering
    • /
    • v.16 no.4
    • /
    • pp.187-193
    • /
    • 2007
  • Water hammer following the tripping of pumps can lead to overpressures and negative pressures. Reduction in overpressure and negative pressure may be necessary to avoid failure, to improve the efficiency of operation and to avoid fatigue of system components. The field tests on the water hammer have been conducted on the pump rising pipeline system with an air chamber. The hydraulic transient is modeled using the method of characteristics. Minimizing the least squares problem representing the difference between the measured and predicted transient response in the system performs the calibration of the simulation program. Among the input variables used in the water hammer analysis, the effects of the polytropic exponent, the discharge coefficient and the wave speed on the result of the numerical analysis were examined. The computer program developed in this study will be useful in designing the optimum parameters of an air chamber for the real pump pipeline system. The correct selection of air chamber size and the effects of related parameters to minimize water hammer have been investigated by both field measurements and numerical modeling.

A Study on Valve-Induced Water Hammer Characteristics for Large Pump System (밸브에 의한 대형펌프시스템의 수격특성에 관한 연구)

  • Lee, C.J.;Lim, K.S.;Cho, D.H.
    • Proceedings of KOSOMES biannual meeting
    • /
    • 2009.06a
    • /
    • pp.177-178
    • /
    • 2009
  • Hydraulic Transients would be occurred since pressure is increased or decreased when water speed inside of pipeline is rapidly changed A study on water hammer has become more important because the pumping stations were big and the systems conveying the fluid through the large and long transmission pipelines were complex. In this study, the method of characteristic line was adopted to evaluate the valve-induced water hammer phenomena in a pumps feedwater system.

  • PDF