• 제목/요약/키워드: Switchgear

검색결과 358건 처리시간 0.032초

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

  • Shin, Jong-Yeol;Lee, Young-Sang;Hong, Jin-Woong
    • Transactions on Electrical and Electronic Materials
    • /
    • 제14권4호
    • /
    • pp.211-215
    • /
    • 2013
  • Partial discharge diagnosis techniques using ultra high frequencies do not affect load movement, because there is no interruption of power. Consequently, these techniques are popular among the prevention diagnosis methods. For the first time, this measurement technique has been applied to the GIS, and has been tested by applying an extra high voltage switchboard. This particular technique makes it easy to measure in the live state, and is not affected by the noise generated by analyzing the causes of faults ? thereby making risk analysis possible. It is reported that the analysis data and the evaluation of the risk level are improved, especially for poor location, and that the measurement of Ultra high frequency (UHF) partial discharge of the real live wire in industrial switchgear is spectacular. Partial discharge diagnosis techniques by using the Ultra High Frequency sensor have been recently highlighted, and it is verified by applying them to the GIS. This has become one of the new and various power equipment techniques. Diagnosis using a UHF sensor is easy to measure, and waveform analysis is already standardized, due to numerous past case experiments. This technique is currently active in research and development, and commercialization is becoming a reality. Another aspect of this technique is that it can determine the occurrences and types of partial discharge, by the application diagnosis for live wire of ultra high voltage switchgear. Measured data by using the UHF partial discharge techniques for ultra high voltage switchgear was obtained from 200 places in Gumi, Yeosu, Taiwan and China's semiconductor plants, and also the partial discharge signals at 15 other places were found. It was confirmed that the partial discharge signal was destroyed by improving the work of junction bolt tightening check, and the cable head reinforcement insulation at 8 places with a possibility for preventing the interruption of service. Also, it was confirmed that the UHF partial discharge measurement techniques are also a prevention diagnosis method in actual industrial sites. The measured field data and the usage of the research for risk assessment techniques of the live wire status of power equipment make a valuable database for future improvements.

저압배전반 관련 IEC 국제규격 동향 (Study for IEC standard of the low-voltage switchgear and controlgear assemblies)

  • 정흥수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.896-897
    • /
    • 2011
  • 저압배전반(Low-voltage switchgear and controlgear assemblies)에 관한 대표적인 국제규격으로는 IEC 60439 시리 가 있어(국내규격으로는 KEMC(한국전기공업협동조합 단체규격) 2102), 저압배전반의 형식시험(Type test)시 이 규격을 적용하여 시험하고 있으나, 최근 IEC 60439 시리즈의 규격 개정작업이 진행되고 있다. 본 고찰에서는 새로 제정된 61439 시리즈의 주요 내용을 개략적으로 소개하여, 신 규격에 의한 배전반 형식시험에 도움을 주고자 한다.

  • PDF

가스절연개폐장치의 감시 및 진단을 위한 시스템 설계 및 구현 (System design and realization of Gas Insulator Switchgear for monitoring and diagnostic)

  • 이혁진;김윤서;양오
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 합동 추계학술대회 논문집 정보 및 제어부문
    • /
    • pp.391-394
    • /
    • 2002
  • In this paper, we describe the implementation of a monitoring and diagnostic system for Gas Insulator Switchgear(GIS). This system monitors operation status of GIS and transmits data from GIS to host. With this system, a operator can monitor a operating condition and judge the aging of each device, and prevent the failure or breakdown in advance.

  • PDF

차단장치 기술 전문 위원회 활동소개 (INTRODUCTION TO TECHNICAL COMMITEE IN SWITCHGEAR)

  • 변승봉;강영식
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1987년도 정기총회 및 창립40주년기념 학술대회 학회본부
    • /
    • pp.290-292
    • /
    • 1987
  • During the past 40 years of KIEE, thor hays exerted their best efforts in scientific and technical fields with a lot of beneficial results. To promote sharing their mutual activities and informations between the industrial and scholastic bodies, KIEE has organized a Technical Commitee in Switchgear to have the first meeting on this July 22 in accordance with the Regulations which has newly came in action by this June 5. This paper briefly describes their activities thereafter.

  • PDF

가스절연개폐장치용 절연스페이서의 수명평가 (Lifetime Evaluation of Insulating Spacer used in Gas Insulated Switchgear)

  • 김민규;이정기;김익수;정주영;오창수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2006년도 추계학술대회 논문집 전기물성,응용부문
    • /
    • pp.190-191
    • /
    • 2006
  • In this paper, a method to assess the reliability of an insulating spacer used in gas insulated switchgear by electrical accelerated lifetime test is represented. And a test plan to assure the expected lifetime with 90 % confidence level is also included.

  • PDF

23kV 개폐기류의 고장분석을 통한 성능향상 방안 (The performance Improvement of switches through analyzing fault on 23kV class switchgear)

  • 김동명;최선규;윤태상;정상봉
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.550-554
    • /
    • 2004
  • This paper describes the performance improvement of switchgear. G/S(Gas Switch) is a common and very important facility in distribution system. In this paper We analyze the cause of trouble with operating switches. Using the conclusion through the investigation We propose the countermeasure of a malfunction in switching equipment.

  • PDF

저압직류용 하이브리드 차단기 (Hybrid LVDC Circuit Breakers)

  • 김효성
    • 전력전자학회논문지
    • /
    • 제27권6호
    • /
    • pp.489-497
    • /
    • 2022
  • This work investigates the commutation characteristics of the current flowing through an electrical-contact-type switch to the semiconductor switch branch during the breaking operation of hybrid DC switchgear. A simple, reliable, low-cost natural commutation method is proposed, and the current commutation characteristics are analyzed in accordance with the conduction voltage drop of the semiconductor switch branch through experiments. A prototype 400 V/10 A class natural commutation type hybrid DC switchgear is set up. Its performance is verified, and its characteristics are analyzed.

전자파 측정을 이용한 폐쇄 배전반의 사고예방진단 기법에 관한 연구 (A Study on the Diagnostic Method for Fault Prevention Of Metal Clad Switchgear Using Electromagnetic Detection Techniques)

  • 김재철;서인철;김영노;전영재
    • 조명전기설비학회논문지
    • /
    • 제16권5호
    • /
    • pp.29-37
    • /
    • 2002
  • 본 논문에서는 전자파 측정기법을 이용하여 부분방전 발생 전·후에 검출된 신호를 분석하여 폐쇄 배전반의 이상 징후를 상시 감시할 수 있는 사고 예방진단기법을 제시하였다. 폐쇄 배전반의 정상 및 이상상태 판단을 위해 배전반 내부 및 외부에 헬리컬 안테나를 설치하여 이들 안테나에서 검출된 부분방전 발생 전·후의 신호를 주파수 스펙트럼 분석을 통해 크기를 비교 분석하였다. 본 논문에서는 부분방전 발생 전·후에 폐쇄 배전반 내부 및 외부에 설치된 안테나에서 검출된 신호들을 이용하여 정상상태 및 이상상태를 판별하는 방법을 적용하여 좋은 결과를 얻었으며, 향후 폐쇄 배전반의 절연 상태 감시 및 사고예방에 효율적으로 적용할 수 있으리라 기대된다.

25.8kV 고체절연차단기(Solid Insulated Switchgear)에 대한 기계적 신뢰성(수명) 평가 (Mechanical Reliability(Life-time) Estimation for 25.8kV Solid Insulated Switchgear)

  • 이도훈;강원종;이석원;신철호;김영근;이규철;이승엽;김호근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.2007_2008
    • /
    • 2009
  • 본 논문은 $SF_6$ 가스졀연차단기를 대체할 고체절연차단기(Solid Insulated Switchgear:SIS)의 기계적 신뢰성 평가에 대한 연구 결과이다. 최근 제정된 "25.8kV 가스 및 고체절연 친환경 개폐장치" 한전 구매규격에는 "Epoxy 고체절연물에 대한 기계적 신뢰성(수명)이 25년 이상"임을 보증할 수 있는 신뢰성 데이터를 제출해야 한다는 조항이 포함되어있다. 이에 개발된 고제절연차단기의 Epoxy 고체절연물에 대한 기계적 신뢰성(수명)이 25년 이상임을 보증할 수 있는 신뢰성 시험과 분석 기법에 대한 연구가 진행되었다.

  • PDF