Examination on Effect of Horizontal Vent Position on Fire Phenomena in Enclosure (구획실 화재 현상에 대한 수평 개구부 위치의 영향 검토)

  • Park, Yu Mi;Lee, Chi Young
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2022.04a
    • /
    • pp.235-236
    • /
    • 2022
  • In the present study, the effect of horizontal vent position on fire phenomena in the enclosure with vertical and horizontal vents was examined using numerical simulation. Case 1 indicates the condition that the horizontal vent is in the center of the ceiling. Case 3 indicates the condition that the horizontal vent is far away from the vertical vent. Case 2 indicates the condition that the horizontal vent is installed between Case 1 and Case 3. The temperature distribution, smoke layer temperature, velocity distribution, and mass flow rate of horizontal vent flow were analyzed. In Case 2, the temperatures were lowest and the mass flow rate through the horizontal vent was largest. This is because the flame is inclined by the inflow through the vertical vent. Hence, to determine the proper horizontal vent location for the high smoke ventilation performance, the inflow through the vertical vent and its effect on flame behavior should be considered.

  • PDF

A Study of Smoke Movement in Tunnel Fires (터널내에서 화재 발생시 연기 거동에 대한 연구)

  • 김상훈;김성찬;김충익;유홍선
    • Fire Science and Engineering
    • /
    • v.14 no.2
    • /
    • pp.21-32
    • /
    • 2000
  • In this study, reduced-scale experiments as the alternative to a real-scale fire test were conducted to understand fire properties in tunnel, and their results were compared with those of numerical simulation. The 1/20 scale experiments were conducted under the Froude scaling since smoke movement in tunnel is governed by buoyancy farce. A numerical simulations were on performed 3D unstructured meshes with PISO algorithm and buoyant plume models. Results showed that data was in reasonable agreement with the numerical data of smoke velocity, temperature distribution, and clear height.

  • PDF

A Study on Fire Features of Double-Skin Facade Structure by Using Fire Simulation (FDS) (화재 시뮬레이션(FDS)을 이용한 이중외피 구조의 화재 특성에 관한 연구)

  • Gu, Seon-Hwan;Kim, Hyun-Ho;Song, Young-Joo
    • Fire Science and Engineering
    • /
    • v.28 no.1
    • /
    • pp.1-11
    • /
    • 2014
  • This study aims to address the fire characteristics of Double-skin facade using the Fire Dynamics Simulator (FDS). To end this, Double-skin facade was classified into the four structures, that is Box, Shaft-box, Corridor, Multistory, through PyroSim program which was based on FDS, and further each structure of fire characteristics were analyzed numerically as well as comparatively in the current study. This study also examined smoke movement, smoke density, smoke detectors, and visibility in order to closely identify the each structure of fire characteristics. The results of the study discovered that the Box structure did not significantly affect smoke which was rising in the other rooms, except for the fire room whereas the Corridor structure had positive effects on Double-skin facade horizontally. In addition, the Shaft-box structure showed the fastest vertical movement by means of the shaft, on the other hand, rising smoke influenced the other rooms as well. The Multistory structure along with rising smoke had a great impact on the other divided rooms in a vertical way.

Performance Evaluation of a Natural Smoke Ventilator in Jeju (배연창의 개방층 설정방식에 따른 배연성능 평가 연구(제주지역 중심으로))

  • Lim, Chae-Hyun
    • Fire Science and Engineering
    • /
    • v.30 no.1
    • /
    • pp.6-11
    • /
    • 2016
  • This study analyzed the performance of smoke exhaustion installed to secure the life safety from the smoke each opening modes, as performing the simulation on the Jeju regions generating to strong windy using CONTAM. We assessed the effectiveness of the system under conditions of high external winds as well as an ambient wind conditions. It also assessed the relative effectiveness of opening all vents versus opening only those vents which served rooms in which the fire was located. This study revealed external winds exerted a substantial impact on the performance of the smoke ventilation system. It was found that opening the ventilation system in the room containing the fire resulted in a greater performance than opening vents in both fire in all rooms. The reduced performance of the smoke ventilation system upon the opening of all vents is thought to be due to the intrusion of outside air, and the establishment of unfavorable air circulation, caused by the negative pressure generated in the building.

Simulation of Heat and Smoke Behavior for Wood and Subway Fires by Fire Dynamics Simulator(FDS) (FDS에 의한 목재 및 지하철 화재의 열 및 연기 거동 시뮬레이션)

  • Sonh, Yun-Suk;Dan, Seung-Kyu;Lee, Bong-Woo;Kwon, Seong-Pil;Shin, Dong-Il;Kim, Tae-Ok
    • Journal of the Korean Institute of Gas
    • /
    • v.14 no.6
    • /
    • pp.31-37
    • /
    • 2010
  • In this study, to propose the analysis method of heat and smoke behavior of fire using the CFD-based fire simulator FDS, comparison of the simulation results against the experimental results and the sensitivity of the results to the grid sizes have been investigated. For the wood fire, thermal images captured from the experiments were compared against the FDS simulations, and the maximum temperatures agreed in~4.3 % error, showing the applicability of FDS in the interpretation of the fire phenomena. In the aspect of the sensitivity to the grid size for the subway fire, FDS results of smoke temperature, CO concentration and visibility converged and showed no distinct changes for the grid size < $28(L){\times}28(W){\times}14(H)$, guaranteeing that the FDS fire model set in this research could interpret the fire phenomena successfully.

A Study on Measures to Improve Smoke Control Performance in Case of Fire in a Clean room as an LCD Manufacturing Process (LCD 제조공정 클린룸의 화재시 CFD를 이용한 제연성능 개선대책에 관한 연구)

  • Son, Bong-Sei;Jang, Chan-Hee
    • Fire Science and Engineering
    • /
    • v.26 no.5
    • /
    • pp.41-47
    • /
    • 2012
  • As a core process in the manufacture of state-of-the-art industrial technologies such as semiconductor and LCD, a clean room is the most important process which can affect the performance and quality of products drastically. Nevertheless, scientific research on comprehensive safety measures from a fire protection standpoint is not being carried out in Korea. This study aims to derive measures to improve smoke control systems by identifying performance and problems of smoke systems installed in clean rooms as an LCD manufacturing process and analyzing fire and evacuation simulations considering several scenarios. As a result of analysis of fires and smoke in a clean roomas an LCD manufacturing process, it is found to be necessary to stop air handling units through interlocking in case of a fire and exhaust smoke out of the room through the top of FAB in consideration of buoyancy of smoke. It is also found to be necessary to install quick response sprinkler heads and accessories to accelerate the response time, because the heat-accumulating performance of sprinkler heads decreases in this application. Despite its low density of dwelling due to the automation process, clean room is characterized by an array of complex production equipment and working environment requiring dustproof clothes, which makes it difficult to acquire evacuation safety performance. Thus, thorough control of danger factors in processes and periodic education and training are required. It is also necessary to establish a level of domestic technologies equivalent to the level of standards of advanced countries in fire protection.

Interactive VFX System for TV Virtual Studio (TV 가상 스튜디오용 인터랙티브 VFX 시스템)

  • Byun, Hae Won
    • Journal of the Korea Computer Graphics Society
    • /
    • v.21 no.5
    • /
    • pp.21-27
    • /
    • 2015
  • In this paper, we presents visual effect(water, fire, smoke) simulation and interaction system for TV virtual studio. TV virtual studio seamlessly synthesizes CG background and a live performer standing on a TV green studio. Previous virtual studios focus on the registration of CG background and a performer in real world. In contrast to the previous systems, we can afford to make new types of TV scenes more easily by simulating interactive visual effects according to a performer. This requires the extraction of the performer motion to be transformed 3D vector field and simulate fluids by applying the vector field to Navier Stokes equation. To add realism to water VFX simulation and interaction, we also simulate the dynamic behavior of splashing fluids on the water surface. To provide real-time recording of TV programs, real-time VFX simulation and interaction is presented through a GPU programming. Experimental results show this system can be used practically for realizing water, fire, smoke VFX simulation and the dynamic behavior simulation of fish flocks inside ocean.

Experimental and Computational Investigation of Aerodynamic Characteristics of Hovering Coleoptera

  • Saputra, Saputra;Byun, Do-Young;Yoo, Yong-Hoon;Park, Hoon-Choel;Byun, Yong-Hwan
    • Proceedings of the KSME Conference
    • /
    • 2007.05a
    • /
    • pp.384-388
    • /
    • 2007
  • Aerodynamic characteristics of Coleoptera species of Epilachna quadricollis and Allomyrina dichotoma are experimentally and numerically investigated. Using digital high speed camera and smoke wire technique, we visualized the continuous wing kinematics and the flight motion of free-flying coleoptera. The experimental visualization shows that the elytra flapped concurrently with the main wing both in the downstroke and upstroke motions. The wing motion of Epilachna quadricollis was captured and analyzed frame by frame to identify the kinematics of the wings and to implement it in the movement of a model wing (thin plate) in the simulation. The two-dimensional simulation of Epilachna quadricollis hovering flight was performed by assuming the wing cross section shape as a thin plate, even though most of insect's wings are made of curved corrugated membrane. The effect of Reynolds number are investigated by the simulation. Meanwhile, in order to investigate the role and effect of elytra, the flow visualization of Allomyrina dichotoma was carried on using smoke wire visualization technique. Here, we confirmed that the vortex generated by elytra due to its movement is strongly influence the vortex dynamic generated by hind wings.

  • PDF

THE EXAMINATION OF ACCURACY OF FIRE-DRIVEN FLOW SIMULATION IN TUNNEL EQUIPPED WITH VENTILATION (환기가 있는 터널에서의 화재유동 해석의 정확성에 대한 고찰)

  • Jang, Yong-Jun;Lee, Chang-Hyun;Kim, Hag-Beom;Jung, Woo-Sung
    • Journal of computational fluids engineering
    • /
    • v.14 no.3
    • /
    • pp.115-122
    • /
    • 2009
  • Numerical methods are applied to simulate the smoke behavior in a ventilated tunnel using large eddy simulation (LES) which is incorporated in FDS (Fire Dynamics Simulator) with proper combustion and radiation model. In this study, present numerical results are compared with data obtained from experiments on pool fires in a ventilated tunnel. The model tunnel is $182m(L){\times}5.4m(W){\times}2.4m(H)$. Two fire scenarios with different ventilation rates are considered with two different fire strengths. The present results are analyzed with those from LES without combustion and radiation model and from RANS ($\kappa-\epsilon$) model as well. Temperature distributions caused by fire in tunnel are compared with each other. It is found that thermal stratification and smoke back-layer can be predicted by FDS and the temperature predictions by FDS show better results than LES without combustion and radiation model. The FDS solver, however, failed to predict correct flow pattern when the high ventilation rate is considered in tunnel because of the defects in the tunnel-inlet turbulence and the near-wall turbulence.