• 제목/요약/키워드: Saving energy rate

검색결과 328건 처리시간 0.033초

소규모 사무공간의 조명에너지 절감율 평가에 관한 연구 (Evaluation of Lighting Energy Saving Rate in a Small Office Space)

  • 김한용;윤경;김강수
    • 한국태양에너지학회 논문집
    • /
    • 제32권3호
    • /
    • pp.50-58
    • /
    • 2012
  • The objective of this study is to evaluate the lighting dimming rates with various parameters of the building skin in a small office. We compared to simulated workplane illuminance and measured workplane illuminance for the base model. After that, the five veriables(the presence of vertical wall in double skin facade, the presence of windowsill, window to wall ratio(WWR), window visible transmittance, the width of double skin facade) were applied to base model, and we analyzed the simulated lighting energy saving rates. The results are listed as below. The simulated workplane illuminance results are similar to the measurement. Simulated illuminance was smaller than measured illuminance by 16.5%(60 lx). In accordance with applicable building skin parameters, lighting energy saving rate results are summarized as follows. Lighting energy saving rate of case1(windowsill height 0.7m) is higher than that of base case(windowsill and vertical wall) by 7.3% and the lighting energy saving rate of case2(no vertical wall) is higher than that of base case by 7.6% and the lighting energy saving rate of case3(no windowsill and vertical wall) is higher than that of base case by 12.4%. The lighting energy saving rate is increased by 2.3%, when window visible transmittance is increased from 70% to 86%. The lighting energy saving rate is increased by 4.6%, when we changed the WWR 70% to 90%. lighting energy savings rate is increased by 6.5%, when the width of double skin facade is reduced from 1m to 0.3m.

사무소 건물의 에너지 소비 요소별 절감률 분석 (Analysis of Saving Rates according to Energy Consumption Factors in Office Building)

  • 박병일;양인호
    • 설비공학논문집
    • /
    • 제28권3호
    • /
    • pp.115-122
    • /
    • 2016
  • In this study, 21 energy reduction factors were selected as architecture, system & operation, and lighting and equipment parts to analyze reduction method of the load occurring in office buildings. Energy consumption simulation was performed. In the architecture part, saving rate (1.53%) of "occupant density" factor was the most efficient. In the system and operation part, saving rate (1.28%) of "interior VAV and exterior FPU type" factor was the most efficient. In case of lighting and equipment part, saving rate (12.42%) of "schedule" factor was the most efficient. In the three parts, saving rate of the lighting and equipment part was 27.32%. This was caused by the "schedule" factor. Saving rates of the architecture part and the system and operation part were 3.39% and 1.20%, respectively.

인버터 구동 원심펌프의 급수 사용율에 따른 에너지 절감 평가 (Evaluation of Energy Savings for Inverter Driving Centrifugal Pump with Duty Cycles)

  • 김경욱;서상호;라키부자만
    • 한국유체기계학회 논문집
    • /
    • 제18권6호
    • /
    • pp.81-85
    • /
    • 2015
  • The purpose of this study is to evaluate energy savings for inverter driving multi-stage centrifugal pump. Variable speed driving pump system has high efficiency compared with constant speed driving pump system. Because of difficulty to estimate operating efficiency of variable speed driving pump system, energy saving rates are used to replace operating efficiency. energy saving rates are calculated from pump input power and pump duty cycle. But another researches have used pump duty cycles of each season for energy saving rate. In this study, for estimating energy saving rate more high accuracy, pump duty cycles are measured for 1 year. pump duty cycles, depending on the season and be classified according to the weekday/weekend or during the week day. By this pump duty cycles, Energy saving rate is calculated appropriately.

차폐계수와 창면적비에 따른 공동주택의 건물에너지효율등급 평가 (The Building Energy Efficiency Rating Evaluation of Apartment depending on SC and Window area ratio)

  • 장철용;한혜심;이진숙
    • 한국태양에너지학회 논문집
    • /
    • 제30권5호
    • /
    • pp.38-43
    • /
    • 2010
  • Enhancement of exterior's insulation performance like wall or window etc. is general way for building's energy efficient and thermal performance. But exterior's opening plan is important for minimizing the energy consumption and heat loss. In this paper, energy saving rate will be analyzed and compared considering the window area's rate and window's SC(Shading Coefficient) in a apartment with Building Energy Efficiency Rating System's evaluation tool. In the process of evaluation, energy saving rate is measured at each stage of the window area's rate from 20% to 60% every 10% term and the shading coefficient value from 1.0 to 0.6. As a result of this research, energy saving evaluation could not be measured exactly with existing evaluation tool. Accord this research, Building Energy Rating System's evaluation range is needed to be broaden for exact evaluation of energy saving rate.

Energyplus를 이용한 고효율 멀티에어컨디셔너의 에너지절감 효과 분석 (A Study on analyze of energy saving rate by retrofitting multi air-conditioner from conventional type to high efficient type using Energyplus)

  • 서정식;김욱중;우정태;최연성;전종욱
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2010년도 추계학술대회 초록집
    • /
    • pp.165.2-165.2
    • /
    • 2010
  • The objective of this study is to analyze the energy saving rate by retrofitting multi air conditioner from conventional type to high efficient type using Energyplus 4.0 which was developed for simulating a building energy by D.O.E. Generally, Multi air conditioner system was installed for both the cooling and the heating in a building. However, it was difficult to estimate the energy saving rate in the case of retrofitting multi air conditioner from conventional type to high efficient type. In the present study, annual energy consumptions of them were evaluated for same building and climate condition.

  • PDF

창호 구성 요소에 따른 난방에너지 절감율 예측에 관한 연구-공동주택을 중심으로 (Prediction of Heating Energy Saving Rate on the Window Type-Focus on the Apartment House)

  • 김경아;문현준;유기형
    • 한국태양에너지학회 논문집
    • /
    • 제33권6호
    • /
    • pp.54-61
    • /
    • 2013
  • This is study on the glazing performance of the apartment house to predict energy saving rate when the early design stage by calculating heating load. there are various factors of the window type in apartment building to save energy such as window's U-value, SC or SHGC, window wall ration, frame factor, sunshade coefficient and so on. In this study, we analyzed the heating load focused on the U-value, SC and window wall ration using variable heating degree days method for a small and middle size units $59m^2$, $84m^2$, respectively. Each cases were calculated heating load of the real models compared to standard model to predict energy saving rate. From those cases it was drew the conclusion that were window's U-value, SC and window wall ration for the small and middle size units to expect 10% energy saving rate at least.

에너지 성능지표 기계부문 항목에 따른 업무용 건물의 에너지 절감율 분석 (Analysis of Energy Saving Rate of Office Buildings According to the Items of an EPI Machine Part)

  • 이호진;김서훈;정재욱;장철용;송규동
    • KIEAE Journal
    • /
    • 제13권4호
    • /
    • pp.49-54
    • /
    • 2013
  • released by IEA, 2010, indicated that Korea's GDP, of 8 countries surveyed-Korea, Frans, Germany, Italy, Japan, the UK, the USA, and Australia-was the lowest, but the electric consumption per head was third, following America and Australia. Thus, our government has been striving to reduce energy usage and especially to lessen the energy used in buildings, proposing a variety of road maps such as 'building energy efficiency rating' and 'energy saving design standards of buildings'. Accordingly, this study investigated the effect of the items of machine part among EPI items on the energy saving rate. I measured energy usage by ECO2 program, for simulation program, that is used for the building energy efficiency rating. Result showed that items concerning control of pumps and fans had much more saving rate than the ones concerning efficiency of heater and cooler that had bigger scores assigned among EPI items. Result showed that items concerning control of pumps and fans had much more saving rate than the ones concerning efficiency of heater and cooler that had bigger scores assigned among EPI items. Therefore, I think that grades assigned to items in energy performance index need to be corrected.

사무용 건물의 에너지 절감을 위한 요소별 성능 분석 및 디자인 전략에 관한 연구 (Study of Design Strategy to Reduce Energy Consumption in a Standard Office Building)

  • 양자강;김철호;김강수
    • KIEAE Journal
    • /
    • 제16권2호
    • /
    • pp.23-31
    • /
    • 2016
  • Purpose: Recently energy consumption is rapidly increasing due to continuous development of social evolution in various field. In this situation, there is a lot of effort to reduce this energy consumption in many ways, especially in building energy. Preceding studies already started to analyze the housing area such as zero energy house and passive house by researching annual building energy consumption, but to apply the results of housing to office building is insufficient since it has different consumption tendency. Method: In this study, eQuest program was used for simulation and the base model is selected among standard office building in ASHRAE 90.1. Variables are divided into passive and active factors for comparison. Result: In passive factors, glazing system showed the highest energy saving rate by 21.3% with triple low-e glass and enhancing wall u-value showed the lowest energy saving rate by 3.6% with 0.15 m2/K. In active factors, VAV system showed 30.9% energy saving rate when compared to CAV system, and heat exchanger showed 10.2% energy saving rate. For regeneration energy part, photovoltaic panel generated 10.4% of base annual energy usage.

벡터 제어 인버터 구동 원심펌프시스템의 에너지 절감 평가 (Evaluation of Energy Saving with Vector Control Inverter Driving Centrifugal Pump System)

  • 서상호;김경욱;김형호;윤인식;조민태
    • 한국유체기계학회 논문집
    • /
    • 제18권2호
    • /
    • pp.67-72
    • /
    • 2015
  • The purpose of this study is to achieve energy saving effect of inverter driving multistage centrifugal pump. For determining the operation points in the pump system, the system curves should be obtained experimentally. To get the system curves, three pumps combined in parallel and one pump operated with different rotational speeds. But for variable speed pump system, energy saving rates can not be evaluated from operation efficiencies. That is why operation efficiencies, system curves, duty cycles, and input powers of the pump system were measured by the constructed experimental apparatus. The duty cycle segmented into different flow rates and weighting the average value for each segment by the interval time. The system was operated with two different periods. The mean duty cycles were collected from apartment and found that the system operated at 40% and at 50% or below capacity. Measured energy saving rate was 58.16%. Estimating method of energy saving rate could be more effective operation index than that of operation efficiency.

전기적 열제어 시스템을 사용한 에너지 소비량 감소에 관한 연구 (A study on the saving of energy consumption load using electrical heat control system)

  • 한규일
    • 수산해양기술연구
    • /
    • 제49권1호
    • /
    • pp.58-66
    • /
    • 2013
  • Most of steam power plant in Korea are heating the feed water system to prevent freezing water flowing in the pipe in winter time. The heating system is operated whenever the ambient temperature around the power plant area below 5 degree Centigrade. But this kind of heat supplying system cause a lot of energy consuming. If we think about the method that the temperature of the each pipe is controled by attaching the temperature measuring sensor like RTD sensor and heat is supplied only when the outer surface temperature of the pipe is under 5 degree Centigrade, then we can save a plenty of energy. In this study, the computer program package for simulation is used to compare the energy consumption load of both systems. Energy saving rate is calculated for the location of Youngweol area using the data of weather station in winter season, especially the January' severe weather data is analyzed for comparison. Various convection heat transfer coefficients for the ambient air and the flowing water inside the pipe was used for the accurate calculation. And also the various initial flowing water temperature was used for the system. Steady state analysis is done previously to approximate the result before the simulation. The result shows that the temperature control system using RTD sensor represents the high energy saving effect which is more than 90% of energy saving rate. Even in the severe January weather condition, the energy saving rate is almost 60%.