• Title/Summary/Keyword: Power prior

검색결과 617건 처리시간 0.025초

Development of Speed Controller and its Application to a 680[MW] Rated Steam Turbine

  • Choi, In-Kyu;Woo, Joo-Hee
    • 조명전기설비학회논문지
    • /
    • 제22권11호
    • /
    • pp.30-35
    • /
    • 2008
  • An analog type turbine control system in a nuclear power plant in Korea was replaced by a digital type control system successfully. The turbine simulator was used to verify and validate the perfection of newly developed digital control system prior to its actual installation. In this paper, the newly developed turbine speed control system, ie. governor will be introduced together with how to simulate entire control loop. After that, we will compare the comparison of simulation result in laboratory with pre startup simulation result. Eventually the performance of actual operation result was testified.

STS 316의 시효 열화 처리와 크리프 거동 특성 (Thermal Aging and Creep Rupture Behavior of STS 316)

  • 임병수
    • 한국생산제조학회지
    • /
    • 제8권4호
    • /
    • pp.123-129
    • /
    • 1999
  • Although type 316 stainless steel is widely used such as in reactors of petrochemical plants and pipes of steam power plants and s attracting attention as potential basic material for the fast breeder reactor structure alloys in nuclear power plants and is attracting attention as potential basic material for the fast breeder reactor structure alloys in nuclear power plants the effect of precipitates which form during the long term exposure at service temperature on creep properties is not known sufficiently. In this study to investigate the creep properties and the influence of prior aging on the microstructure to form precipitates specimens were first solutionized at 113$0^{\circ}C$ for 20 minutes and then aged for different times of 0 hr, 100 hrs, 1000 hrs and 2200 hrs at 75$0^{\circ}C$ After heat treatments tensile tests both at room temperature and $650^{\circ}C$ and constant load creep ruptuere tests were carried out.

  • PDF

1kW급 PEFC 가정용 연료전지 시스템 실증 연구 (Development of 1kW Class PEFC System for Residential Power Generation)

  • 이호준;이정민;황남선;최동민;이종욱;오시덕
    • 한국신재생에너지학회:학술대회논문집
    • /
    • 한국신재생에너지학회 2008년도 춘계학술대회 논문집
    • /
    • pp.17-20
    • /
    • 2008
  • HYOSUNG manufactured and tested 1kW class PEFC systems to generate electrical and thermal energy for each residential usage. In particular, HYOSUNG developed power conditioning system that performs over 91% electrical conversion ratio specified in 1kW class PEFC systems. Prior to system integration, we tested each performances of components to derive control issues from it. In addition, we have been developing the adequate simulator to describe and predict system performance. In this paper, we verified HYOSUNG's 1kW class PEFC systems are valid for residential energy sources by testing the characteristics of systems and performances of main components.

  • PDF

일사량 분석을 통한 PV모듈 발전량과 시뮬레이션을 이용한 실내 조명에너지 절감량 비교 (A Study on the Comparison of the PV Module Generation from Daylight Irradiation and Indoor Lighting Savings with Lighting Simulation)

  • 박윤민;홍성관;최안섭
    • 조명전기설비학회논문지
    • /
    • 제24권12호
    • /
    • pp.17-24
    • /
    • 2010
  • Recently, BIPV system which is good enough for maintenance and functions with the shading system is being used. However BIPV system with the shading system is different from existing PV module because of using flexible PV module. Prior to the application of the BIPV system, the clearness index was calculated by Erbs et al.(1982) and analyzed for the amount of electric power generation of sky irradiance with measured data. To predict electric lighting energy savings in daylit space, electric lighting power savings with amount of PV module electric power generation was compared by using Relux 2010 software in this study.

Performance evaluation of safety-critical systems of nuclear power plant systems

  • Kumar, Pramod;Singh, Lalit Kumar;Kumar, Chiranjeev
    • Nuclear Engineering and Technology
    • /
    • 제52권3호
    • /
    • pp.560-567
    • /
    • 2020
  • The complexity of safety critical systems of Nuclear Power Plant continues to increase rapidly due its transition from analog to digital systems. It has thus become progressively more imperative to model these systems prior to their implementation in order to meet the high performance, safety and reliability requirements. Timed Petri Nets (TPNs) have been widely used to model such systems for non-functional analysis. The paper presents a novel methodology for the analysis of the performance metrics using PN modeling. The paper uses the isomorphism property of the TPNs and the Markov chains for the performance analysis of the safety critical systems. The presented methodology has been validated on a Shutdown System of a Nuclear Power Plant.

INTERFIRM RELATIONSHIPS IN KOREAN ELECTRIC/ELECTRONIC PARTS INDUSTRY

  • Sejo Oh;F. Robert Dwyer;Kim, Sungil;Park, Jin-Yong
    • 한국유통학회지:유통연구
    • /
    • 제2권2호
    • /
    • pp.135-151
    • /
    • 1997
  • This study of interfirm relationships is tested on a sample of Korean electric and electronic parts industry. The hypotheses present that (1) buyer's power affects administrative structure and relational norms, (2) communications are affected prior three antecedents, and (3) buyer's power, administrative structure, relational norms, and communication affects relational performances. The results indicate that buyer's power plays important roles in administrative structure and relational norms but communications are not explained three constructs. The result also indicates performances are partially affected by antecedents.

  • PDF

발전소 보일러 제어기에 대한 내고장성 제어 시스템의 적용에 관한 연구 (A Case Study on Application of Fault Tolerant Control System to Boiler Controller in Power Plant)

  • 조영조;문봉채;김병국
    • 대한전자공학회논문지
    • /
    • 제27권1호
    • /
    • pp.10-19
    • /
    • 1990
  • A fault tolerant control system, in which a digital back-up controller system is added on the existing analog control system, is developed for enhancing reliability of boiler control system in power plant. The digital back-up controller system(DBCS) has a multi-processor structure with capabilities of fault diagnosis, back-up control, self test, and graphic monitoring. Specifically, switching mechanism composed of expandable modules is designed so that back-up controller takes over any faulty control loops and the number of back-up control loops is determined as that of simultaneous faults. A process simulator that simulates the boiler analog control system is developed for safety test and performance evaluation prior to real plant application. DBCS is installed at the Ulsan thermal power plant, and fault tolerant control performance is assured under the faults that some controller modules are pulled out.

  • PDF

국내 원자력발전소 인적오류사례의 추이 분석 (Analysis of human errors involved in Korean nuclear power plant trips)

  • 이정운;이용희;박근옥
    • 대한인간공학회지
    • /
    • 제15권1호
    • /
    • pp.27-38
    • /
    • 1996
  • A total of 77 unanticipated trip cases induced by human errors in Korean nuclear power plants were collected from the nuclear power plant trip event reports and analyzed to investigate the areas of high priority for human error reduction. Prior to this analysis, a classification system was made on the four task-related categories including plant systems, work situations, task types, and error types. The erroneous actions affecting the unanticipated plant trips were indentified by reviewing carefully the description of trip events. Then, the events with erroneous action were analyzed by using the classification system. Based on the results for the individual cases, human error occurrences were counted for each of the four categories, also for the selected pairs of categories, to find out the relationships between the two categories in aspects of human errors. As a result, the plant systems, work situations, and task types, and error types which are dominant in human error occurrences were identified.

  • PDF

On Calculating Eigenvalues In Large Power Systems Using Modified Arnoldi Method

  • 이병준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1996년도 하계학술대회 논문집 B
    • /
    • pp.734-736
    • /
    • 1996
  • This paper presents a method of calculating a selective number of eigenvalues in power systems, which are rightmost, or are largest modulus. The modified Arnoldi method in conjunction with implicit shift OR-algorithm is used to calculate the rightmost eigenvalues. Algorithm requires neither a prior knowledge of the specified shifts nor the calculation of inverse matrix. The key advantage of the algorithm is its ability to converge to the wanted eigenvalues at once. The method is compared with the modified Arnoldi method combined with S-matrix transformation, where the eigenvalues having the largest modulus are to be determined. The two methods are applied to the reduced Kansai system. Convergence characteristics and performances are compared. Results show that both methods are robust and has good convergence properties. However, the implicit shift OR method is seen to be faster than the S-matrix method under the same condition.

  • PDF

원자로 제어봉구동장치 제어시스템용 이벤트 기록 방법 (Event Logging Method for Control Rod Control System)

  • 천종민;김춘경;조창희;정순현;남정한
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 학술회의 논문집 정보 및 제어부문 B
    • /
    • pp.552-554
    • /
    • 2003
  • This paper is about the method by which Power Control Unit(PCU) of Control Rod Control System(CRCS) logs events in the system and the real-time monitoring display. This method enables the functions like the event logging of Control Rod Drive Mechanism(CRDM)/power Cabinet, the off-line show of the event data logged and the on-line show by communication between the PCU and the monitoring display. Operators in a nuclear power plant must be able to grasp any possible abnormal states correctly. Because our newly designed system has a good ability to log and display the kinds, tine, and the prior and posterior states of urgent or non-urgent events, the operators can judge, maintain and repair the abnormal event more easily.

  • PDF