Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1996.07b
- /
- Pages.734-736
- /
- 1996
On Calculating Eigenvalues In Large Power Systems Using Modified Arnoldi Method
- Lee, Byong-Jun (Mitsubishi Electric Corporation) ;
- Iba, Kenjl (Mitsubishi Electric Corporation) ;
- Hirose, Michio (Kansai Electric Power Co., Inc)
- 이병준 ;
- ;
- Published : 1996.07.22
Abstract
This paper presents a method of calculating a selective number of eigenvalues in power systems, which are rightmost, or are largest modulus. The modified Arnoldi method in conjunction with implicit shift OR-algorithm is used to calculate the rightmost eigenvalues. Algorithm requires neither a prior knowledge of the specified shifts nor the calculation of inverse matrix. The key advantage of the algorithm is its ability to converge to the wanted eigenvalues at once. The method is compared with the modified Arnoldi method combined with S-matrix transformation, where the eigenvalues having the largest modulus are to be determined. The two methods are applied to the reduced Kansai system. Convergence characteristics and performances are compared. Results show that both methods are robust and has good convergence properties. However, the implicit shift OR method is seen to be faster than the S-matrix method under the same condition.
Keywords
- small-signal stability;
- selective eigenvalue calculation;
- preconditioning;
- implicit shift OR;
- S-matrix;
- modified Arnoldi