가공송전 전선 자산데이터의 정제 자동화 알고리즘 개발 연구 (Automatic Algorithm for Cleaning Asset Data of Overhead Transmission Line)

  • Mun, Sung-Duk;Kim, Tae-Joon;Kim, Kang-Sik;Hwang, Jae-Sang
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제7권1호
    • /
    • pp.73-77
    • /
    • 2021
  • As the big data analysis technologies has been developed worldwide, the importance of asset management for electric power facilities based data analysis is increasing. It is essential to secure quality of data that will determine the performance of the RISK evaluation algorithm for asset management. To improve reliability of asset management, asset data must be preprocessed. In particular, the process of cleaning dirty data is required, and it is also urgent to develop an algorithm to reduce time and improve accuracy for data treatment. In this paper, the result of the development of an automatic cleaning algorithm specialized in overhead transmission asset data is presented. A data cleaning algorithm was developed to enable data clean by analyzing quality and overall pattern of raw data.

154 kV 복도체 가공송전선로에서 전자력에 의한 소도체간 접촉 (Kissing of Sub-conductors due to Magnetic Forces in a 154 kV Bundled Overhead Transmission Line)

  • 김상범;노희원;김영홍;고광만;박종혁;김상수
    • KEPCO Journal on Electric Power and Energy
    • /
    • 제2권3호
    • /
    • pp.383-389
    • /
    • 2016
  • 국내 154 kV 복도체 가공송전선로를 대상으로 전자력에 의한 소도체간 접촉현상을 실증적으로 재현하고 대처 방안을 제시하였다. 도체에 흐르는 전류의 크기가 클수록, 스페이서의 간격이 클수록 소도체간에 작용하는 전자력은 크게 측정되었다. 스페이서 간격이 68 m일 경우 전류 크기가 2,000 A 일 때부터 소도체는 불안정한 상태가 되어 소도체간 간격이 변화하는 횡방향 진동이 시작되었다. 스페이서 간격이 136 m일 경우 전류 크기가 증가할수록 소도체간 간격은 좁아지다가 2,250 A 일 때 두 소도체는 완전히 접촉하였다. 스페이서 간격에 따른 전자력의 크기를 도식화하고 안전한 스페이서 간격을 제시하였다. 시험선로와 실선로 간에는 접촉현상이 발생하는 조건이 상이한 것으로 나타났으며, 이는 송전선로 가선 과정에서 도체에 가해진 여러 형태의 잔류 응력, 바람 조건 등의 차이 때문으로 판단되었다.

가공송전선로의 비상용량 응용과 평가 (Application and Evaluation of Emergency Rates in Overhead Transmission Lines)

  • 김성덕
    • 전기전자학회논문지
    • /
    • 제18권4호
    • /
    • pp.442-446
    • /
    • 2014
  • 본 논문에서는 ACSR 가공송전선로의 전력공급 신뢰도를 증진시키기 위한 비상정격의 적용방안에 대하여 기술하였다. 전력산업의 재편으로 인하여 한국전력은 물론 세계의 대부분 전력회사들은 새로운 투자를 하지 않으면서 경제적인 전략들만 모색하여 왔다. 그러나 전력수요가 급격히 증가하였으나 발전량의 증가는 충분히 따라가지 못했다. 따라서 첨두부하 시나 송전선로의 고장의 경우에 기존 송전선로의 송전용량을 증가시키기 위하여, 단시간 또는 장시간정격과 같은 비상용량을 적용하는 방법을 제안한다. 만약 첨두부하시, 정적송전용량 대신에 장시간 비상용량을 적용하면 10 % 또는 그 이상의 전력증대가 가능하다. 또한 2회선 송전선로 중 1회선 고장이나 과부하 경우에 비상용량이 효과적으로 사용될 수 있음을 확인하였다.

팬터그래프와 전차선간 최소 이선아크 지속시간에 따른 이선율 변화량 분석 (Analysis of Percentage of Arcing between Pantograph and Overhead Contact Line as a Function of Duration of Arc)

  • 박영;이기원;권삼영;박철민;김재광;최원석
    • 전기학회논문지
    • /
    • 제63권6호
    • /
    • pp.855-859
    • /
    • 2014
  • Quality criteria for interaction between a pantograph and overhead contact wire is a most important requirement to assess of the performance for the current collection system. Interaction performance between pantograph and catenary system is subject to approval by the infrastructure manager when a new design and contraction of overhead contact line and pantograph are installed. Among the various performance, percentage of arcing at maximum line speed is a simple test method compared with contact force of pantograph due to direct sensing of pantagraph, calibrations, installations of train, and etc. On the other hand, percentage of arcing is need to reliable arcing detector and general requirements with accordance with EN 50317. In this paper, percentage of arcing are investigated on the function of duration of arc and proposed which is satiable of percentage of arcing. As a results, we proposed which duration of arcs are unsuitable from infrastructures point of view as performance testing for quality of current collection.

레이저를 이용한 전차선 편위 및 높이 측정 시스템 개발 (Development of Catenary Stagger and Height Measurement System using Laser)

  • 송성근;이택희;송재열;박성모
    • 한국철도학회논문집
    • /
    • 제11권6호
    • /
    • pp.569-574
    • /
    • 2008
  • 전차선과 팬터그래프는 물리적인 접촉을 통하여 전동차에 전력을 공급하는 장치로, 전동차가 안전하게 운행할 수 있도록 기술적인 규정에 따라 정밀하게 시공되어야 한다. 전차선의 편위 및 높이는 여러 가지 외부 환경요소에 의하여 상태가 변화하며, 허용치를 초과한 진차선의 편위 및 높이는 높은 아크와 순간적인 전기 단전을 유발한다. 이는 팬터그래프와 전차선에 큰 손상을 주며 고장과 사고의 원인이 된다. 따라서 주기적으로 전차선의 상태를 점검하여 유지 및 보수를 할 수 있는 측정 장치의 요구가 증대되고 있다. 본 논문에서는 전차선의 높이 및 편위 검측 시스템에 관하여 기술하였다. 검측 시스템은 Acuity사의 AR4000레이저 거리측정기와 AccuRange 라인 스캐너를 사용하여 전차선 높이 및 편위를 측정한다.

배전계통에서 1선 지락고장 시험에 의한 지락고장전류 분류에 관한 연구 (A Study on the Ground Fault Current Distribution by Single Phase-to-Neutral Fault Tests in Power Distribution System)

  • 김경철;유창훈
    • 조명전기설비학회논문지
    • /
    • 제27권7호
    • /
    • pp.37-44
    • /
    • 2013
  • Phase to ground faults are possibly one of the maximum number of faults in power distribution system. During a ground fault the maximum fault current and neutral to ground voltage will appear at the pole nearest to the fault. Distribution lines are consisted of three phase conductors, an overhead ground wire and a multigrounded neutral line. In this paper phase to neutral faults were staged at the specified concrete pole along the distribution line and measured the ground fault current distribution in the ground fault current, three poles nearest to the fault point, overhead ground wire and neutral line. A simplified equivalent circuit model for the distribution system under case study calculated by using MATLAB gives results very close to the ground fault current distribution yielded by field tests.

송전선로 점퍼선 횡진방지용 지지애자장치 개발 (Development of Hold on Swing a Jumper Support String for Overhead Transmission Line)

  • 백승도;민병욱;위화복;박기용;금의연;정헌수
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 A
    • /
    • pp.521-523
    • /
    • 2005
  • A Jumper wire is currently used to connect each fixed power line on both sides of dead end tower for overhead transmission line, but in case of a jumper wire swing under circumstances of typhoon, etc. and the air clearance is deficient then a flashover fault may Happen. Now the angle tower has the jumper support string to prevent a swing of jumper wire and to secure the air clearance between jumper wire and tower main body, but the flashover fault by swing of jumper wire was happened yl times across all over the country, because of the typhoon 'Rusa' in year 2002 and 'Maemi' in year 2003. This paper presents the design and development of 'Counter Weight' which enables to keep the swing angle of jumper wire under 40 degree in design condition to prevent a flashover fault by swing of jumper wire by a high wind pressure load in case of typhoon and have completed a mechanical and electrical characteristic test.

  • PDF

HVDC 가공 송전선로 전기환경특성 모의시험용 코로나 케이지 계측시스템 개발 (Development of Corona Cage Measurement System for Simulation on Electrical Environmental Characteristics of HVDC Overhead Transmission Line)

  • 길경석;양광호;이성두;주문노
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제55권5호
    • /
    • pp.245-249
    • /
    • 2006
  • Corona characteristics of conductors are dependent on the electric field conditions in the immediate vicinity of the conductors. In case of DC transmission line, particularly, the space charge plays an important role in the electric field distribution. Therefore, DC corona cage simulation is necessary for long-term test in the same conditions. This paper presents the results of designing and constructing hardwares such as DC power supply, measurement system and DAS to carry out the simulation. The corona cage longitudinally is divided into five equal length sections and three inner sections of those are isolated from the ground of outer cage. The measurement items are radio noise, corona current, television noise, audible noise and meteorological conditions. In the next step, various simulations about the type and configuration of two or three candidate conductors will be conducted. And then finally an environmentally-friendly conductor for HVDC overhead transmission line will be decided.

송전 선로의 사고 거리에 따른 특성 주파수 해석 (Analysis of Characteristic Frequency along Fault Distance on a Transmission Line)

  • 남순열;홍정기;강상희;박종근
    • 대한전기학회논문지:전력기술부문A
    • /
    • 제53권8호
    • /
    • pp.432-437
    • /
    • 2004
  • Since the characteristic frequency is decreased in proportion to the fault distance, the characteristic frequency component may be insufficiently eliminated by a low-pass filter on a long transmission line. In order to set a standard for the cut-off frequency of the low-pass filter, this paper proposes a method for obtaining the characteristic frequencies due to line faults. The application results of the proposed method are presented for line to ground (LG) faults and line to line (LL) faults on a 345 kV 200 km overhead transmission line. The EMTP is used to generate fault signals under different fault locations and fault inception angles. By comparison between the characteristic frequencies obtained from the proposed method and the EMTP simulation, it is shown that the proposed method accurately obtains the characteristic frequency.

도르래식 장력조정장치 개발 (Development of a Pulley-type Tensioning Device)

  • 이기원;조용현;박영
    • 한국철도학회논문집
    • /
    • 제12권5호
    • /
    • pp.663-669
    • /
    • 2009
  • 전기철도에서 열차의 속도향상을 위하여 전차선의 장력상승은 필수적이며, 전차선로의 집전성능은 장력에 따라 크게 좌우한다. 경부고속철도에서 사용하고 있는 도르래식 장력장치는 장력변동율이 3% 이내로 규정되어 있고, 전량 수입에 의존하고 있다. 따라서 고속선에서의 장력변동을 요구소건을 만족하는 도르래식 장력조정장치를 개발하였다. 개발한 장력조정장치의 성능을 확인하기 위하여 경부고속철도 장력조정장치의 규격에 따라 성능시험, 내하중 시험 및 파단시험을 수행하였다. 장력조정장치의 신뢰성을 확보하기 위하여 공장에서의 피로시험과 충북선 본선에서 1 년 이상을 시범설치, 운영하였다. 이들 시험을 통하여 개발된 장력조정장치가 신뢰성을 가지며 본선에 적용할 수 있다는 것을 입증하였다.