• Title/Summary/Keyword: Lightning performance

Search Result 154, Processing Time 0.027 seconds

Frequency-Dependent Resistivity and Relative Dielectric Constant of Soil on Water Content (수분함유량에 따른 토양의 저항률 및 비유전율의 주파수의존성)

  • Choi, Jong-Hyuk;Cha, Eung-Suk;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.1
    • /
    • pp.98-104
    • /
    • 2010
  • In order to evaluate the performance of a grounding system against lightning or fault currents including high frequency components, the grounding impedance should be considered rather than the steady state ground resistance. To evaluate the ground impedance, the frequency dependence of resistivity and relative dielectric constant of the soil have to be analyzed. This paper deals with the frequency dependence of the resistivity and relative dielectric constant of three types of soil on water content. As a result, the resistivity of soil is getting lower with increasing of water content. It is nearly independent of the frequency in the range less than 1[MHz], and is decreased over the frequency range above 1[MHz]. On the other hand, the relative dielectric constant is rapidly decreased with the frequency in the range less than 1[MHz], but it is nearly independent on the frequency over the range of 1[MHz]. It was found from the experiments that the frequency-dependant resistivity and relative dielectric constant of soil should be considered when designing the grounding systems for protection from lightning or switching surges.

Protection Effects According to the Conditions of Installations of SPDs for Information-Oriented Equipments (정보화 기기용 SPD의 설치조건에 따른 보호효과)

  • Lee, Bok-Hee;Lee, Dong-Moon;Cheong, Dong-Chul;Lee, Su-Bong;Lee, Seung-Chil
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.1
    • /
    • pp.35-41
    • /
    • 2007
  • Recently, there are increasing social needs for stable supply of electric power and securing high quality of information and communication services. In this work, to propose the effective protection countermeasures of information-oriented equipments against lightning surges, the protection effects of surge protective devices(SPDs) were experimentally investigated using actual-sized test circuits in various installation conditions. As a result, it was found that the protection effect of SPDs is quite different depending on the factors, such as the grounding system of power source, numbers of branch circuits, wiring method of grounding leads, and etc. In case of installing SPDs for information-oriented equipments, including all electric power lines and communication lines, the common grounding should be the most effective. Wiring method containing grounding leads with power lines in metal conduit is suitable to improve the surge cutoff performance of SPDs.

Influence of SF6/N2 Gas Mixture Ratios on the Lightning Streamer Propagation Characteristics of 22 kV MV Circuit Breaker

  • Gandhi, R.;Chandrasekar, S.;Nagarajan, C.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1663-1672
    • /
    • 2018
  • In recent times, gas insulated medium voltage (MV) circuit breakers (CB) form a vital component in power system network, considering its advantages such as reduced size and safety margins. Gas insulation characteristics of circuit breakers are generally measured by lightning impulse (LI) test according to IEC standard 60060-1 as a factory routine test. Considering the environmental issues of $SF_6$ gas, many research works are being carried out towards the mixture of $SF_6$ gases for high voltage insulation applications. However, few reports are only available regarding the LI withstand and streamer propagation characteristics (at both positive and negative polarity of waveform) of $SF_6/N_2$ gas mixture insulated medium voltage circuit breakers. In this paper, positive and negative polarity LI tests are carried out on 22 kV medium voltage circuit breaker filled with $SF_6/N_2$ gas mixture at different gas pressures (1-5 bar) and at different gas mixture ratios. Important LI parameters such as breakdown voltage, streamer velocity, time to breakdown and acceleration voltage are evaluated with IEC standard LI ($1.2/50{\mu}s$) waveform. Weibull distribution analysis of LI breakdown voltage data is carried out and 50% probability breakdown voltage, scale parameter and shape parameter are evaluated. Results illustrate that the $25%SF_6+75%N_2$ gas filled insulation considerably enhances the LI withstand and breakdown strength of MV circuit breakers. LI breakdown voltage of circuit breaker under negative polarity shows higher value when compared with positive polarity. Results show that maintaining the gas pressure at 0.3 MPa (3 bar) with 10% $SF_6$ gas mixed with 90% $N_2$ will give optimum lighting impulse withstand performance of 22 kV MV circuit breaker.

Residual Voltage Reduction of Coaxial Surge Arrestor Using Ceramic Filler (세라믹 필터를 이용한 동축 서지어레스터의 잔류전압 저감)

  • Eom, Ju-Hong;Cho, Sung-Chul;Lee, Tae-Hyung;Lee, Young-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.2
    • /
    • pp.46-53
    • /
    • 2007
  • Extension of the mobile communication and the rapidly developing services connected with wireless multimedia(W-CDMA, DMB, Wibro, and so on) need great many base station transceiver systems, antennas, and many signal transmission line to embody these services. The min communication appliances system is exposed always in danger of transient overvoltage by direct stroke or induced lightning surge flowing in through antenna because the antenna of base station transceiver system or relay equipment is combined with expensive communication network equipments through signal transmission line. Now, gas discharge tube(GDT) or narrow band stub arrestor which is used by the surge protector for communication use is exposing limitations as for lightning surge protective means of the communication facility with high speed and wide frequency band. Therefore, for improving performance of surge arrestor, we applied ceramic filter which can reduce lightning surge invading from antenna effectively, and proved that ceramic filter is effective in residual voltage reduction through the experimental research.

Effective Impulse Impedances of Deeply Driven Grounding Electrodes

  • Lee, Bok-Hee;Jeong, Dong-Cheol;Lee, Su-Bong;Chang, Keun-Chul
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.4C no.5
    • /
    • pp.207-214
    • /
    • 2004
  • This paper presents the characteristics of transient and effective impulse impedances for deeply driven grounding electrodes used in soil with high resistivity or in downtown areas. The laboratory test associated with the time domain performance of grounding piles subjected to a lightning stroke current has been carried out using an actual-sized model grounding system. The ground impedances of the deeply driven ground rods and grounding pile under impulse currents showed inductive characteristics, and the effective impulse ground impedance owing to the inductive component is higher than the power frequency ground impedance. Both power frequency ground impedance and effective impulse ground impedance decrease upon increasing the length of the model grounding electrodes. Furthermore, the effective impulse ground impedances of the deeply driven grounding electrodes are significantly amplified in impulse currents with a rapid rise time. The reduction of the power frequency ground impedance is decisive to improve the impulse impedance characteristics of grounding systems.

A Study on the DC Leakage Current Test for Power Cable of Private Electrical Facilities considering Lightning Arrester (피뢰기를 고려한 자가용 전기설비 인입선로의 직류누설전류시험에 관한 연구)

  • Jeong, Ki-Seok;Gil, Hyoung-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.1
    • /
    • pp.142-147
    • /
    • 2018
  • Private electrical facilities are judged whether it is suitable for the insulation aging condition of their incoming underground cables using DC leakage current test method. In the case where the service point of utility is the secondary side of cut out switch installed in the electric pole, there is a problem that it is difficult to separate the lightning arresters(LA) because of their high position of the pole. Therefore, the field test voltage is applied at value lower than DC 30 kV, which are stated in the inspection guideline. However, this test could reduced the insulation performance of the LA by accelerating the electrical stress of the metal oxide varistor element in the pre-breakdown region. In this study, we analyzed the relationship between the DC test voltage and the leakage current using the non-destructive DC high voltage equipment with leakage current measurement function. The results show that the leakage current increases sharply above the specified test voltage. As a consequence, it could be contributed to improve insulation aging inspection method by selecting the possible test area on the VI characteristic curve of the pre-breakdown area of the LA.

Investigations on Partial Discharge, Dielectric and Thermal Characteristics of Nano SiO2 Modified Sunflower Oil for Power Transformer Applications

  • Nagendran, S.;Chandrasekar, S.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.3
    • /
    • pp.1337-1345
    • /
    • 2018
  • The reliability of power transmission and distribution depends up on the consistency of insulation in the high voltage power transformer. In recent times, considering the drawbacks of conventional mineral oils such as poor biodegradability and poor fire safety level, several research works are being carried out on natural ester based nanofluids. Earlier research works show that sunflower oil has similar dielectric characteristics compared with mineral oil. BIOTEMP oil which is now commercially available in the market for transformers is based on sunflower oil. Addition of nanofillers in the base oil improves the dielectric characteristics of liquid insulation. Only few results are available in the literature about the insulation characteristics of nano modified natural esters. Hence understanding the influence of addition of nanofillers in the dielectric properties of sunflower oil and collecting the database is important. Considering these facts, present work contributes to investigate the important characteristics such as partial discharge, lightning impulse, breakdown strength, tandelta, volume resistivity, viscosity and thermal characteristics of $SiO_2$ nano modified sunflower oil with different wt% concentration of nano filler material varied from 0.01wt% to 0.1wt%. From the obtained results, nano modified sunflower oil shows better performance than virgin sunflower oil and hence it may be a suitable candidate for power transformer applications.

Frequency Dependent Resistivity and Relative Dielectric Constant with the Water Contents in Sand (모래의 수분함유량에 따른 비저항 및 비유전율의 주파수 의존성)

  • Lee, Bok-Hee;Cha, Eung-Suk;Choi, Jong-Hyuk;Choi, Young-Chul;Yoo, Yang-Woo;Ann, Chang-Hwan
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.348-351
    • /
    • 2009
  • In order to evaluate the performance of a grounding system against lightning or fault currents including high frequency components, the grounding impedance should be considered rather than its ground resistance. Recently, some researches on the evaluation and modeling of the grounding impedances have been carried out but the results have not been yet sufficient. This paper deals with the frequency dependence of the resistivity and relative dielectric constant of sand associated with water contents. As a result, the resistivity of sand is getting lower with increasing water content and it is nearly independent on the frequency in the range of less than 1MHz, and is decreased over the frequency range of above 1MHz. Also, the relative dielectric constant is rapidly decreased with the frequency in the range of less than 10kHz, but it is nearly not dependent on the frequency over the frequency range of 10kHz. It was found from this work that the frequency dependance of resistivity and relative dielectric constant of soil should be considered in designing the grounding systems for protection against lightning or surges.

  • PDF

Analysis of Soil lonization Characteristics in Concentric Cylindrical Electrode System under Impulse Voltages (임펄스전압에 의한 동심원통형 전극계에서 토양 이온화특성 분석)

  • Kim, Hoe-Gu;Park, Geon-Hun;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.9
    • /
    • pp.32-39
    • /
    • 2008
  • This paper presents the soil ionization phenomena and the parameters with the transient characteristics of model grounding system under lightning impulse voltages. lonization properties of dry and wet sands were investigated by using two test cells of concentric cylindrical electrode system with different dimensions. As a result non-linear electrical behavior of sand under high impulse voltage is caused by ionization process. The transient impedance of sand depends not only on the water content but also on the magnitude of applied impulse voltages. The grounding impedance is decreased with increasing the water content and the magnitude of a lied voltages. The results resented in this paper will provide useful information on the design of high performance grounding systems against lightning surge.

A Method for Enhancing Data Transmission Performance in the Power-Line Communication Channel with Low-Voltage Surge Protective Devices (저압용 SPD가 설치된 전력선통신에서 데이터전송 성능 향상)

  • Choi, Jong-Min;Jeon, Tae-Hyun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.2
    • /
    • pp.78-85
    • /
    • 2012
  • Low-Voltage power lines should equip surge protection devices which protect electronic equipments and human lives against lightning and abnormal voltages. Data transmission capacity of the power line is determined by frequency characteristics of the surge protective devices. To analyze the effects of surge protective devices on the data transmission performance, various combinations of installation methods are tested which include ZnO varistor elements that is compatible with class I, class II and class III. The result claims that ZnO varistor for class III is found to be one of the main factors that deteriorates the transmission performance. To overcome this problem a serial connection methed between Gap type SPD and ZnO varistor is proposed. With the proposed scheme, laboratory experimental results show that the data transmission performance can be improved up to 91.9[%] with proper SPD combination.