Abstract
Recently, there are increasing social needs for stable supply of electric power and securing high quality of information and communication services. In this work, to propose the effective protection countermeasures of information-oriented equipments against lightning surges, the protection effects of surge protective devices(SPDs) were experimentally investigated using actual-sized test circuits in various installation conditions. As a result, it was found that the protection effect of SPDs is quite different depending on the factors, such as the grounding system of power source, numbers of branch circuits, wiring method of grounding leads, and etc. In case of installing SPDs for information-oriented equipments, including all electric power lines and communication lines, the common grounding should be the most effective. Wiring method containing grounding leads with power lines in metal conduit is suitable to improve the surge cutoff performance of SPDs.
최근 고품질의 정보통신서비스와 안정한 전력공급에 대한 사회적 요구가 증가하고 있다. 본 연구에서는 뇌서지로부터 정보통신설비를 효과적으로 보호하는 대책을 제안하기 위해서 실규모 실험회로를 적용하여 여러 가지 설치조건에 따른 서지보호기의 보호효과를 실험적으로 조사하였다. 그 결과 전원계통의 접지방식, 분기회로의 수, 접지선의 배선방법 등에 따라 서지보호기의 보호효과는 크게 다른 것으로 밝혀졌다. 정보화 기기용 서지보호기를 설치하는 경우, 전원선과 통신선을 포함하는 공통접지방식과 접지선을 전원선과 일괄하여 금속관 내에 배선하는 것이 서지보호기의 서지차단성능의 향상에 가장 효과적이었다.