• Title/Summary/Keyword: Leakage current monitoring

Search Result 77, Processing Time 0.029 seconds

Development of Leakage Current Sensor for Mobile Robot Chassis (이동 로봇 섀시 누전 모니터링 센서 개발)

  • Kim, Cheong Worl;Kwon, Ik Hyun;Kim, Sung Deuk;Lee, Young Tae
    • Journal of the Semiconductor & Display Technology
    • /
    • v.17 no.3
    • /
    • pp.104-107
    • /
    • 2018
  • In this paper, we developed a sensor for monitoring the leakage current through the chassis of the robot. The leakage current sensor needs to be developed because it is a necessary part to prevent electric shock accidents that may occur through the chassis of a robot or an electric vehicle. This leakage monitoring sensor was developed to be mounted directly on the chassis of the robot. This sensor protects the control system from noise by discharging static and high-frequency noise that may occur in the chassis of the robot and monitors the leakage current by measuring the amount of current discharged through the ground. In this paper, a leakage monitoring sensor was developed with a simple structure using resistors, capacitors and OP-AMP, and the performance was evaluated.

The Effectiveness Analysis of the Resistive Leakage Current Monitoring by Analyzing the Phase of the Body Current (인체 통전전류 위상 분석을 통한 저항성 누설전류 감시의 유효성 분석)

  • Kim, Jae-Hyun;Lim, Young-Bea;Lee, Sang-Ick;Kim, Dong-Woo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.9
    • /
    • pp.90-99
    • /
    • 2013
  • To analyze the effectiveness of the resistive leakage current monitoring as a technology preventing electrical accidents, in this paper, we have estimated the phase of the body impedance by using the body impedance model and the body impedance data from IEC. We also have analyzed the phase of the electric body current in the case of 60Hz/220V. From these results, we concluded that deliberate researches about the phase of the electrical body current and related regulations must be carried out before the resistive leakage current monitoring unit is used to protect electric shock. And we concluded that the resistive leakage current monitoring unit can be utilized to prevent electrical fires caused by electric leakage current without unwanted circuit break due to capacitive leakage current flowing from line filter capacitors to the earth.

Development of the Remote Monitoring System for Leakage Current Using Wireless Communication (무선통신을 이용한 누설전류 원격 감시시스템의 개발)

  • Park, Sung-Won;Park, Ji-Ho;Kim, Dong-Wan
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.57 no.4
    • /
    • pp.349-355
    • /
    • 2008
  • In this paper, a wireless remote monitoring system for leakage current of distribution board is developed. In the developed system, signals of the leakage current of distribution board are transmitted to a monitoring system using wireless communication. The developed system is consisted of a comparative module, control module, a wireless communication module, and hand held terminal. The developed system has any facilities which can check a leakage current with real time, send to the user this fact using a wireless remote interface method. And also developed system can take precaution for an accident by leakage current.

The Properties of Leakage Current of Silicone Rubber wish the Recovery of Hydrophobicity (발수성 회복에 따른 실리콘 고무의 누설전류 특성)

  • 서광석;김정호;문중섭;박용관;양계준;유영식
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.11a
    • /
    • pp.501-504
    • /
    • 1999
  • The polymer insulators which are installed on outdoor have a great advantage than porcelain and 71ass, due to suppression of leakage current, light weight, low cost, etc. It needs variable evaluation methods for application of these insulators on service. The analysis of measuring leakage current is useful for ageing diagnosis because of monitoring in real-time. In this paper, we look over the recovery of hydrophobicity of silicone rubber in mini salt-fog chamber with leakage current monitoring. also, we understand the relation of between hydrophobicity and leakage current and discuss on method of leakage current monitoring.

  • PDF

A New Approach to On-Line Monitoring Device for ZnO Surge Arresters

  • Lee Bok-Hee;Gil Hyoung-Jun;Kang Sung-Man
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.5C no.3
    • /
    • pp.131-137
    • /
    • 2005
  • This paper describes a new approach to the algorithm and fundamental characteristics of the device for monitoring the leakage currents flowing through zinc oxide (ZnO) surge arresters. In order to obtain a technique for a new on-line monitoring device that can be used in the deterioration diagnosis of ZnO surge arresters, the new algorithm and on-line leakage current detection device for extracting the resistive and capacitive currents using the phase shift addition method were proposed. The computer-based on-line monitoring device can sense accurately the power frequency leakage currents flowing through ZnO surge arresters. The on-line leakage current monitoring device of ZnO surge arresters proposed in this work has the high sensitivity compared to the third harmonic leakage current detection devices. As a consequence, it was found that the proposed leakage current monitoring device would be useful for forecasting the defects and degradation of ZnO surge arresters.

Total monitoring device of leakage current in transformer (변압기 누설전류 통합 감시장치)

  • Lee, Jung-Eun;Choi, Hong-Kyoo;Yum, Sung-Bae;Park, Hyung-Min;Yoo, Hai-Chool;Hong, Seong-Goo;Shin, Hye-Young
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.360-363
    • /
    • 2009
  • Total monitoring device of leakage current in transformer can detects the flowing leakage current on the neutral line, and that is monitored at real-time by the transfer. If the over-flowing current is detected Total monitoring device of leakage current in transformer will warn the administrator to prevent electrical accident. In this thesis, we are going to explain about Total monitoring device of leakage current in transformer and the necessity of Total monitoring device of leakage current in transformer through real-accident cases and equipment condition in Korea.

  • PDF

An Development of Leakage Current Sensing Module of the System on Chip Type Under Consideration of Electromagnetic Interface in Power Trunk Line (전력간선에서의 전자파 장애를 고려한 원칩형 누설전류 원격 검출단말기의 개발)

  • Kim, Dong-Wan;Park, Ji-Ho;Park, Sung-Won
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.58 no.4
    • /
    • pp.377-384
    • /
    • 2009
  • In this paper, leakage current sensing module of SoC(System on Chip)type and real time monitoring system under consideration of electromagnetic interface in power trunk line are developed. The first, leakage current sensing module of SoC type under consideration of electromagnetic interface is developed, and the developed sensing module of SoC type is composed of leakage sensing part, power supply part, interface part, communication part, AD(Alternating current to Direct current)convert part and amplification part. And also the electromagnetic compatibility is evaluated by conduction and radiation of EMI(Electromagnetic Interference) for developed sensing module. The developed system can have confidence, stability and do energy saving under mixed electric circumstance of the low voltage communication device and high voltage equipment. The second, the real time remote monitoring system is developed using designed wire and wireless communication module with leakage current sensing module of SoC type. The developed real time remote monitoring system can monitor sensing state, occurrence state of leakage current and alarm for each step etc.. And the device configuration, PCB layout for leakage current sensing module of system on chip type and the experiment configuration in consideration of EMI are presented. Also the measurement results of conduction and radiation for EMI are presented.

A study case on application of a total monitoring device of leakage current in transformer (변압기 누설전류 통합 감시장치 적용사례)

  • Lee, Jung-Eun;Choi, Hong-Kyoo;Kim, Young-Kyu;Park, Hyung-Min;Song, Young-Joo;Yoo, Hai-Chool
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.51-54
    • /
    • 2009
  • Total monitoring device of leakage current in transformer can detects the flowing leakage current on the ground wire connected with the neutral point, and that is monitored at real-time by the transfer. If the over-flowing current is detected, Total monitoring device of leakage current in transformer will warn the administrator to prevent electrical accident. In this thesis, we are going to explain about Total monitoring device of leakage current in transformer. Also we measure leakage current and judge safety in customer.

  • PDF

The Evaluation of Degradation Characteristics of Silicone Rubber for Outdoor by Leakage Current Monitoring (누설전류 모니터링에 의한 옥외용 실리콘 고무의 열화 특성 평가)

  • Kim, Jeong-Ho;Song, Woo-Chang;Cho, Han-Goo;Park, Yong-Kwan
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.50 no.2
    • /
    • pp.60-64
    • /
    • 2001
  • The degradation process of silicone rubber was investigated by leakage current monitoring in Inclined-Plane method. DAS (Data Acquisition System) with 12-bit, 8-channel A/D converter was prepared. Average current, cumulative charge, current waveform and the number of peak pulses were measured on-line. And, FFT (Fast Fourier Transform) analysis was performed with stored current waveform. Besides, maximum erosion depth was measured in order to use as the indicator of the degradation process. So, the results of leakage current components and maximum erosion depth measurements were compared to find one or more components which have trends of changing similarly to that of erosion process. The result suggests that the ratio of peak current to r.m.s. current, harmonic contents and the number of peak pulses are well corresponding with the degradation process.

  • PDF

A Study on the Integrated Monitoring of a Leakage Current of the Grounding Wire of Neutral Point of the Low Voltage Side of Transformer (변압기 저압측 중성점 접지선의 누설전류 통합 감시에 관한 연구)

  • Hong, Soon-Seuk;Park, Joon-Yeol;Lee, Jung-Eun;Choi, Kyung-Han
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.5
    • /
    • pp.106-113
    • /
    • 2010
  • If leakage current is neglected, it can become a cause for disasters such as electric shock and fire, therefore a continuous monitoring is necessary. However in most cases, because management of substations is performed by unmanned systems, or walk-around inspections, continuous monitor is difficult. So when an accident occurs and the cause is not immediately resolved causing the emergency generator's OCGR getting activated by the leakage current that in turn cut off the ACB, the emergency generator may stop working. To prevent such a problem, a real-time integrated monitoring system for monitoring the leakage current returning to the grounding wire of neutral point of the low voltage side of transformer is proposed. Therefore in this paper, the effects of flow of leakage current, which is caused by insulation degradation phenomena or insulation destroy phenomena, were identified by simulation. And through cases studies; the excellence of integrated monitoring system was verified.