Measurement Device of Resistive Leakage Current for Arrester Deterioration Diagnosis (피뢰기 열화진단을 위한 저항분 누설전류의 측정장치)

  • 길경석;한주섭;김정배
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.10
    • /
    • pp.469-475
    • /
    • 2003
  • Resistive leakage current flowing ZnO blocks increases with its ages, which is an important indicator of arrester deterioration. However, a complicated circuitry is essential to measure the resistive leakage current included in the total leakage current, and the difficult handling of the measurement makes few applications to the fields. In this paper, we propose a resistive leakage current measurement device which is composed of a current detection circuit and an analysis program operated on a microprocessor. The device samples the input leakage current waveform digitally, and discriminate the zero-cross and the peak point of the waveform to analyze the current amplitude vs. phase. The capacitive leakage current is then eliminated from the total leakage current by using an algorithm to extract the resistive leakage current only. Also, the device can be operated automatically and manually to analyze the resistive leakage current even when the leakage current waveform is distorted due to various types of arrester deterioration. To estimate the performance of the device, we carried out a test on ZnO blocks and lightning arresters. From the results, it is confirmed that the device could analyze most parameters needed for the arrester diagnostics such as total leakage current. resistive leakage current, and the $3^rd$ harmonic leakage current.

New Measurement Technique of the Resistive Leakage Current for Arrester Diagnosis (피뢰기 진단을 위한 저항분 누설전류의 새로운 측정기법)

  • Kil, G.S.;Han, J.S.;Song, J.Y.;Park, D.W.;Seo, H.D.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.05b
    • /
    • pp.73-75
    • /
    • 2004
  • Resistive leakage current following arresters is an important indicator of ageing, but total leakage current and its harmonic analysis are widely used in diagnosing arrester soundness because of difficulties in measuring resistive leakage current. In this paper, we proposed a new method for measuring resistive leakage current, which is quite different from the conventional methods such as a self-cancel method and a synchronous rectification method. The proposed method is based on that the magnitudes of resistive leakage currents are equal at the same voltage level. To confirm the possibility of the proposed method. we fabricated a leakage current measurement device and designed an analysis program that can analyze resistive leakage current. Comparing with other methods. this technique does not need a complex circuitry and is very simple to complete.

  • PDF

Leakage Current Measurement and Management of Arresters Installed in Feeder Lines (급전선로에 설치되어 있는 피뢰기의 누설전류 측정과 관리방안)

  • Han Ju-Seop;Seo Hwang-Dong;Kil Gyung-Suk;Han Moon-Seob;Jang Dong-Uk
    • Proceedings of the KSR Conference
    • /
    • 2005.05a
    • /
    • pp.819-824
    • /
    • 2005
  • This paper describes the measurement result of leakage current flowing arresters connected in feeder lines to propose an optimal management method. Twenty seven arresters set in seven areas were analyzed on a regular basis for 4 months. The results showed that the RMS and the peak value of the total leakage currents for soundness arresters were a range of $200uA{\sim}00uA$. respectively. During the period of measurement, the magnitude of the leakage current didn't show conspicious changes and there were impossible places to analyze arrester's status due to including high THD rate in a feeder line, From the study, leakage current measurement has to be performed at a condition without running an electric train in the line, and the allowable RMS value of soundness arrester is bellow 600uA.

  • PDF

Measurement Method of the Resistive Leakage Current for Lightning Arrester Diagnosis

  • Kil, Gyung-Suk;Han, Ju-Seop;Song, Jae-Yong;Seo, Hwang-Dong
    • Transactions on Electrical and Electronic Materials
    • /
    • v.6 no.2
    • /
    • pp.63-66
    • /
    • 2005
  • Several ways for monitoring the soundness of ZnO lightning arresters have been suggested, and all of which are based on the measurement of leakage current since it is well known that the resistive leakage current is a main indicator of arrester deterioration. In this paper, we proposed an algorithm to measure the resistive leakage current, which is quite different from the conventional method that eliminates capacitive current from the total leakage current. The proposed algorithm is based on that the magnitudes of the resistive leakage current are equal at the same applied voltage levels. To confirm the reliability of the algorithm, we fabricated a leakage current detector and designed an analysis program. Experimental results showed that the method does not need a complex circuitry and is useful to analyze the resistive leakage current.

Influence of System Voltage Harmonics on Arrester Deterioration Diagnostic Techniques by Leakage Current Measurement (누설전류측정에 의한 피뢰기 열화진단기술에 있어 전원고조파의 영향)

  • Kil, Gyung-Suk;Han, Joo-Sup
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.08a
    • /
    • pp.142-145
    • /
    • 2002
  • This paper describes an influence of system voltage harmonics on arrester deterioration diagnostic techniques based on leakage current measurement because the resistive current is composed of two components caused by nonlinear characteristics of arrester and by system voltage harmonics. Resistive leakage currents of arresters, which can be evaluated by the third harmonic component of total leakage currents, increase with its deterioration progress. In this paper, we developed a PSpice model for ZnO arrester to simulate the harmonics' effect described above. In simulation, pure sinusoidal voltage and the $3^{rd}$ harmonic voltage are applied to the model, and the leakage current changes are compared. The simulation results showed that the magnitudes of resistive leakage current depend not only on the phase of system voltage harmonics but also on the magnitude of it.

  • PDF

ZnO Arrester Diagnosis by Measurement of Temperature (온도측정에 의한 산화아연형 피뢰기 진단)

  • Kim Gyung-Suk;Han Ju-Seop;Song Jae-Yong;Seo Hwang-Dong;Moon Seung-Bo;Park Tae-Gone
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.8
    • /
    • pp.361-364
    • /
    • 2005
  • In this paper, surface temperatures of ZnO arresters as a function of ambient temperatures and leakage currents were experimentally investigated. The variations of the leakage current was below 10 uA, which comes about $4.5\%$ of the normal leakage current. Temperature differences between the ambient and the surface of arresters were not shown until $150\%$ to the normal leakage current, and were remarkable over $200\%$. From the results, we deduced a couple of polynomials which enables the calculation of the leakage current by the measurement of surface temperature. Tests on used arresters have shown the same results as the experimental one. Also, we expect that an arrester diagnosis is possible by measuring the surface temperature of them after more studies on the effect of wind, moisture penetration, and arrester types.

A New Method for Resistive Leakage Current Measurement (새로운 저항성 누전전류 측정 방법)

  • Ham, Seung-Jin;Hahn, Song-Yop;Koh, Chang-Seop
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.56 no.8
    • /
    • pp.1397-1404
    • /
    • 2007
  • It is important to measure the resistive component separately from the total leakage current at power distribution line. It is because electric disasters such as electric shock and fire are caused mainly by the resistive component of the total leakage current. In this paper, a new theory for measuring the resistive component separately from the total leakage current is suggested, and is embodied to an actual circuit using operational amplifiers, analog switch and R-C low pass filter. Through experiments for various cases containing both the resistive and capacitive leakage currents, the suggested algorithm is confirmed to be able to measure the resistive leakage current within 4.1% of error even when the capacitive leakage current is much bigger than the resistive one. The suggested method is expected to lower the total cost because it can be realized using simple and cheap devices, and implies the measuring time can be possibly reduced because the resistive leakage current is computed exactly from the signals during only a half period of power voltage.

Electrical Safety Inspection for Empty Houses Using Leakage Current Measurement (누설전류 측정을 이용한 부재수용가의 전기안전 점검)

  • Lim, Young-Bae;Jung, Jong-Wook;Jung, Jin-Soo;Cho, Seong-Won
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.260-263
    • /
    • 2006
  • The number of empty houses during normal working hours is rising. As a result, the number of uninspected electric installations for general use is increasing. To define the potential risk of the electric installation, measurement of leakage current has been getting considered but because the measured leakage current value also contained leakage current by capacitance, the measured value can not be adapted to absolute reference to the installation. Therefore in this paper, the correlation between the condition of electric installation and leakage current were analyzed.

  • PDF

A Study on the Leakage Current Voltage of Hybrid Type Thin Films Using a Dilute OTS Solution

  • Kim Hong-Bae;Oh Teresa
    • Journal of the Semiconductor & Display Technology
    • /
    • v.5 no.1 s.14
    • /
    • pp.21-25
    • /
    • 2006
  • To improve the performance of organic thin film transistor, we investigated the properties of gate insulator's surface according to the leakage current by I-V measurement. The surface was treated by the dilute n-octadecyltrichlorosilane solution. The alkyl group of n-octadecyltrichlorosilane induced the electron tunneling and the electron tunneling current caused the breakdown at high electric field, consequently shifting the breakdown voltage. The 0.5% sample with an electron-rich group was found to have a large leakage current and a low barrier height because of the effect of an energy barrier lowered by, thermionic current, which is called the Schottky contact. The surface properties of the insulator were analyzed by I-V measurement using the effect of Poole-Frankel emission.

  • PDF

Correlation between the resistive and the $3^{rd}$ harmonic leakage current of ZnO arresters (ZnO 피뢰기의 저항분 누설전류와 제 3고조파 누설전류의 관계)

  • Kim, Il-Kwon;Song, Jae-Yong;Moon, Seung-Bo;Cha, Myung-Soo;Kil, Gyung-Suk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2006.06a
    • /
    • pp.515-516
    • /
    • 2006
  • The resistive leakage current is an important parameter for arrester diagnosis. However, the 3rd harmonic leakage current is more widely used than the resistive one because of its easy measurement. In this paper, we studied the correlation between the resistive and the $3^{rd}$ harmonic leakage current of ZnO arresters. The resistive leakage current was measured according to the IEC 60099-5 in AC applied voltage. The $3^{rd}$ harmonic leakage current was analyzed by using a designed band-pass filter having 180 [Hz]-center frequency and 10 [Hz]-bandwidth. The experimental results show that the $3^{rd}$ harmonic leakage current changes proportionally with the resistive leakage current variation under the maximum continuous operating voltage (MCOV).