Correlation between the resistive and the $3^{rd}$ harmonic leakage current of ZnO arresters

ZnO 피뢰기의 저항분 누설전류와 제 3고조파 누설전류의 관계

  • Published : 2006.06.22

Abstract

The resistive leakage current is an important parameter for arrester diagnosis. However, the 3rd harmonic leakage current is more widely used than the resistive one because of its easy measurement. In this paper, we studied the correlation between the resistive and the $3^{rd}$ harmonic leakage current of ZnO arresters. The resistive leakage current was measured according to the IEC 60099-5 in AC applied voltage. The $3^{rd}$ harmonic leakage current was analyzed by using a designed band-pass filter having 180 [Hz]-center frequency and 10 [Hz]-bandwidth. The experimental results show that the $3^{rd}$ harmonic leakage current changes proportionally with the resistive leakage current variation under the maximum continuous operating voltage (MCOV).

Keywords