Abstract

This paper describes an influence of system voltage harmonics on arrester deterioration diagnostic techniques based on leakage current measurement because the resistive current is composed of two components caused by nonlinear characteristics of arrester and by system voltage harmonics. Resistive leakage currents of arresters, which can be evaluated by the third harmonic component of total leakage currents, increase with its deterioration progress. In this paper, we developed a PSpice model for ZnO arrester to simulate the harmonics' effect described above. In simulation, pure sinusoidal voltage and the $3^{rd}$ harmonic voltage are applied to the model, and the leakage current changes are compared. The simulation results showed that the magnitudes of resistive leakage current depend not only on the phase of system voltage harmonics but also on the magnitude of it.

Keywords