• Title/Summary/Keyword: Insulation gas

Search Result 534, Processing Time 0.038 seconds

Detection of Hydrogen Gas Dissolved in Insulation Oil Based on Palladium-coated Fiber Bragg Grating (팔라듐이 코팅된 광섬유 격자를 이용한 절연유속의 용존 수소가스 검출)

  • Kim, Kwang Taek;Choi, Nu ri;Baik, Se-Jong
    • Journal of Sensor Science and Technology
    • /
    • v.27 no.6
    • /
    • pp.403-406
    • /
    • 2018
  • We have investigated a fiber-optic sensor for detecting the hydrogen gas dissolved in insulation oil based on a palladium (Pd)-coated fiber Bragg grating (FBG). As the palladium absorbs the hydrogen gas dissolved in the insulation oil, its volume expands and the Bragg wavelength shifts to a longer wavelength. The experimental results showed that the Bragg wavelength of FBG increased to 70 nm when the concentration of hydrogen dissolved in the insulation oil was 409 ppm.

A study of the Insulation Characteristic in $SF_6-N_2$ Mixture Gases ($SF_6-N_2$ 혼합기체의 절연특성에 관한 연구)

  • Ha, Sung-Chul;Song, Byoung-Doo
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11b
    • /
    • pp.613-616
    • /
    • 2001
  • This SF6 gas is widely used in industrial of insulation field. In this paper, N2 is mixed to improve pure SF6 gas characteristics. Electron transport coefficients in SF6-N2 mixture gases are simulated in range of E/N values from 70 to 400 [Td] at 300K and 1 Torr by using Boltzmann equation method. The results of this method, which are like electron drift velocity, ionization coefficient, attachment coefficient, effective ionization coefficient, and critical EIN, can be important data to present characteristic of gas for insulation. Specially critical E/N is a data to evaluate insulation strength of a gas and is presented in this paper for various mixture ratios of SF6-N2 mixture gases.?⨀␍?܀㘱〮㜳㬓M敤楣楮攠慮搠桥污瑨

  • PDF

A study of the Insulation Characteristic in $SF_{6}$-$N_2$ Mixture Gases ($SF_{6}$-$N_2$ 혼합기체의 절연특성에 관한 연구)

  • 하성철;송병두
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.11a
    • /
    • pp.613-616
    • /
    • 2001
  • This $SF_{6}$ gas is widely used in industrial of insulation field. In this paper, $N_2$ is mixed to improve pure $SF_{6}$ gas characteristics. Electron transport coefficients in $SF_{6}$-$N_2$ mixture gases are simulated in range of E/N values from 70 to 400 [Td] at 300K and 1 Torr by using Boltzmann equation method. The results of this method, which are like electron drift velocity, ionization coefficient, attachment coefficient, effective ionization coefficient, and critical E/N, can be important data to present characteristic of gas for insulation. Specially critical E/N is a data to evaluate insulation strength of a gas and is presented in this paper for various mixture ratios of $SF_{6}$-$N_2$ mixture gases.

  • PDF

Electrical AC Insulation Breakdown Characteristics of Various Epoxy / Heterogeneous Inorganic Mixed Composite (여러 종류의 에폭시/이종무기물 혼합 콤포지트의 전기적 교류 절연파괴 특성)

  • Park, Jae-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.11
    • /
    • pp.1463-1470
    • /
    • 2018
  • In this study, 20 types of samples were prepared by mixing different kinds of inorganic materials to develop insulation materials for epoxy - based GIS substation equipment used under high voltage environmentally friendly insulation gas. One of the electrical characteristics, AC insulation breakdown experiment was performed. As mixing ratio of mixed heterogeneous inorganic materials, the dielectric breakdown strength was increased with increasing filler ratio of micro silica, micro silica : micro Alumina, 1:9, 3:7, 5:5, 7:3, 9:1, and decreased as the filling amount of micro alumina increased. The AC insulation breakdown characteristics were the best when the composition ratio was 9:1. The higher the content of silica, the better the interfacial properties, and the larger the alumina content ratio, the worse the interfacial properties.

Three-dimensional Analysis for Three-phase Spacers in Gas Insulated System (3차원 전계해석 기법을 이용한 GIS 삼상 일괄형 스페이서 고찰)

  • Kang, J.S.;Lee, B.W.;Kang, S.M.;Oh, I.S.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1620-1622
    • /
    • 2003
  • Recently, as the technology for the development of high voltage power apparatus using SF6 gas has made remarkable progress, it became possible to develop more compact power apparatus adopting single body substation system. In these gas insulated power apparatus, it is impossible to achieve perfect and safe insulation using only SF6 gas, because some solid insulation parts should be installed to support current-carrying conductor parts for electrical and mechanical safety. When spacers were installed in SF6 gas insulation system, they were exposed to severe electrical intensification which could reduce system insulation performance and restrict the rated operating voltage So, it is necessary to clarify the dielectric characteristics of spacers by analytically and experimentally, in order to design and develop more compact and optimum gas insulated systems. In this paper, the field distribution of three-phase spacers were investigated using three dimensional electrostatic field analysis tool adopting BEM method. And the obtained results were compared to the conventional two dimensional computations. According to these three dimensional calculations, it was possible to find out weak points in the spacer more clearly and these results could be applied to design more compact and optimum three phase spacer developments.

  • PDF

Impulse Breakdown Behaviors of Dry Air as an Alternative Insulation Gas for SF6

  • Li, Feng;Yoo, Yang-Woo;Kim, Dong-Kyu;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.3
    • /
    • pp.24-32
    • /
    • 2011
  • [ $SF_6$ ]gas, which has an excellent dielectric strength and interruption performance, is used in various applications such as gas insulated switchgear (GIS) in substations. However, since $SF_6$ has a high global warming potential (GWP), it is necessary to find an eco-friendly alternative insulation gas. In order to examine the possibility of using alternative insulation gases for $SF_6$ in power distribution system equipment, the dielectric strength and physical phenomena of dry air in a quasi-uniform electric field are investigated experimentally in this paper. As a result, the breakdown voltages for positive polarity are higher than those for negative polarity under impulse voltage applications. The negative 50[%] flashover voltage, $V_{50}$ of dry air under conditions above 0.4[MPa] gas pressure, is higher than 150[kV], that is the basic impulse insulation level of distribution equipment. The $V_{50}$ increases linearly with increasing the gas pressure, regardless of the waveform and polarity of the applied impulse voltages. The voltage-time curves are dependent on the rise time of the impulse voltage and gas pressure. Furthermore, streamer discharge was observed through light emission images by an ICCD camera under impulse voltage applications.

Influence of SF6/N2 Gas Mixture Ratios on the Lightning Streamer Propagation Characteristics of 22 kV MV Circuit Breaker

  • Gandhi, R.;Chandrasekar, S.;Nagarajan, C.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1663-1672
    • /
    • 2018
  • In recent times, gas insulated medium voltage (MV) circuit breakers (CB) form a vital component in power system network, considering its advantages such as reduced size and safety margins. Gas insulation characteristics of circuit breakers are generally measured by lightning impulse (LI) test according to IEC standard 60060-1 as a factory routine test. Considering the environmental issues of $SF_6$ gas, many research works are being carried out towards the mixture of $SF_6$ gases for high voltage insulation applications. However, few reports are only available regarding the LI withstand and streamer propagation characteristics (at both positive and negative polarity of waveform) of $SF_6/N_2$ gas mixture insulated medium voltage circuit breakers. In this paper, positive and negative polarity LI tests are carried out on 22 kV medium voltage circuit breaker filled with $SF_6/N_2$ gas mixture at different gas pressures (1-5 bar) and at different gas mixture ratios. Important LI parameters such as breakdown voltage, streamer velocity, time to breakdown and acceleration voltage are evaluated with IEC standard LI ($1.2/50{\mu}s$) waveform. Weibull distribution analysis of LI breakdown voltage data is carried out and 50% probability breakdown voltage, scale parameter and shape parameter are evaluated. Results illustrate that the $25%SF_6+75%N_2$ gas filled insulation considerably enhances the LI withstand and breakdown strength of MV circuit breakers. LI breakdown voltage of circuit breaker under negative polarity shows higher value when compared with positive polarity. Results show that maintaining the gas pressure at 0.3 MPa (3 bar) with 10% $SF_6$ gas mixed with 90% $N_2$ will give optimum lighting impulse withstand performance of 22 kV MV circuit breaker.

The Resistance Characteristics and Reliability Evaluation of an Insulation Ring Type of Corrugated Stainless Steel Tubing(CSST) (절연링형 금속플렉시블호스(CSST)의 저항 특성 및 신뢰성 평가)

  • Lee, Jang-Woo;Kim, Jeom-Sik;Choi, Chung-Seog
    • Journal of the Korean Society of Safety
    • /
    • v.31 no.6
    • /
    • pp.25-31
    • /
    • 2016
  • This paper has analyzed the structure, applicable regulations and the resistance characteristics of insulation ring type of CSST (Corrugated Stainless Steel Tubing for Gas). With the flammability test conducted in accordance with KS C IEC 60811-1-1, the evaluation of insulation resistance, temperature characteristics, and reliability has been conducted. An insulation ring type CSST consists of protective coating, tube, nut, insulation ring, packing, socket, and ball valve. Connecting an insulation ring type CSST to gas tubings for gas appliance is not permitted, moreover, the product shall be installed inside a sleeve pipe in case of buried installation such as the ceiling. Damages on protective coating and tube were detected when fire was applied to the test sample with a portable torch for 60 seconds. The insulation resistance of a normal product was $49.59M{\Omega}$, while that of the product completed the flammability test reduced to $9.21M{\Omega}$. The mean insulation resistance within the confidence Interval of 95% using the mini tap program 17 was $49.59M{\Omega}$ and the mean insulation resistance within the confidence interval reduced to $9.21M{\Omega}$. In the normal distribution analysis of 95% confidence interval, the value-P of the normal product was stable at 0.075 and AD(Anderson-Darling) statistic value was turned out to be 0.063, which is very normal, and the standard deviation was analyzed as 0.2586. The value P of the product completed the flammability test resulted in 0.005, the AD was 1.355 and the standard deviation reduced to 0.07908.

Breakdown Characteristics of Dry Air under 362 kV GIB (362 kV GIB 내에서 건조공기의 절연파괴 특성)

  • Han, Ki-Son;Ju, Hyung-Jun;Yoon, Jin-Yul;You, Hong-Geun
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.23 no.10
    • /
    • pp.804-808
    • /
    • 2010
  • In this paper, we studied the dielectric breakdown voltage characteristics by the AC withstand voltage test on using green insulation dry air instead of $SF_6$ insulation gas used in the GIB (gas insulated bus) of 362 kV GIS (gas insulated switchgear). The AC withstand voltage test applied to the standard KEPCO's 362 kV GIB with dry air insulation, and the equivalence of dielectric breakdown voltage for dry air and $SF_6$ gas were examined, and the empirical formulas of dielectric breakdown voltage for dry air were calculated, and the criterion of AC withstand voltage test for dry air insulation was derived. Using the criterion, dry air can be used instead of $SF_6$ gas for 362 kV GIB in the factory acceptance test was confirmed.

The Characteriztics of Insulation and Discharge with a Variation of Temperature in $SF_6$ ($SF_6$ 가스의 온도변화에 따른 절연특성)

  • 박경태;윤대희;박광서;김이국;박원주;이광식;이동인
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2002.11a
    • /
    • pp.335-338
    • /
    • 2002
  • In this paper the experiments of insulation characteristics by temperature change of SF6 gas and insulation characteristics about liquid SF6 in GIS(Gas Insulated Switchgear) were described. From this result, at low temperature, the breakdown voltage was increased with a drop of temperature and an increase of the inner pressure in GIS. The ability of insulation in liquid SF6 was higher than that of the highly pressurized SF6 gas.

  • PDF