Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 2003.07c
- /
- Pages.1620-1622
- /
- 2003
Three-dimensional Analysis for Three-phase Spacers in Gas Insulated System
3차원 전계해석 기법을 이용한 GIS 삼상 일괄형 스페이서 고찰
- Kang, J.S. (LG Industrial Systems) ;
- Lee, B.W. (LG Industrial Systems) ;
- Kang, S.M. (LG Industrial Systems) ;
- Oh, I.S. (LG Industrial Systems)
- Published : 2003.07.21
Abstract
Recently, as the technology for the development of high voltage power apparatus using SF6 gas has made remarkable progress, it became possible to develop more compact power apparatus adopting single body substation system. In these gas insulated power apparatus, it is impossible to achieve perfect and safe insulation using only SF6 gas, because some solid insulation parts should be installed to support current-carrying conductor parts for electrical and mechanical safety. When spacers were installed in SF6 gas insulation system, they were exposed to severe electrical intensification which could reduce system insulation performance and restrict the rated operating voltage So, it is necessary to clarify the dielectric characteristics of spacers by analytically and experimentally, in order to design and develop more compact and optimum gas insulated systems. In this paper, the field distribution of three-phase spacers were investigated using three dimensional electrostatic field analysis tool adopting BEM method. And the obtained results were compared to the conventional two dimensional computations. According to these three dimensional calculations, it was possible to find out weak points in the spacer more clearly and these results could be applied to design more compact and optimum three phase spacer developments.
Keywords