• 제목/요약/키워드: Insulation Cover

검색결과 56건 처리시간 0.028초

변압기용 절연커버 재질의 전기 안전성 평가에 관한 연구 (A Study on the Electrical Safety Evaluations of Transformer Insulation Cover)

  • 김향곤;한운기;길형준;최충석
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2004년도 하계학술대회 논문집 Vol.5 No.1
    • /
    • pp.433-436
    • /
    • 2004
  • In this paper, we studied on the electrical safety evaluations of transformer insulation cover. In order to take preventive measures against an electric shock disaster in 22.9kV transformer installation, we put the insulation cover on a transformer charging parts. It needs to be designed so that the insulation covers have superior properties such as, arc-resistance, weather-resistance and heat-resistance, because they are used until the damage and destruction occur. To establish the protection cover to reduce the electrical shock, we analyzed damage mechanism and risk factors which happened by structural fault of an insulation cover in this paper. Also, based on the experimental results, we are planing to suggest new improved insulation cover models.

  • PDF

건설현장의 수전설비에서 사용되는 계기용변성기 절연커버의 성능개선에 관한 연구 (A Study on the Improvement of Insulation cover for Instrument Transformer Used In Power Receiving System of Construction Sites)

  • 길형준;최충석;김향곤;한운기;이복희
    • 조명전기설비학회논문지
    • /
    • 제19권2호
    • /
    • pp.55-62
    • /
    • 2005
  • 건설현장의 임시전력설비는 최소한의 보호장치, 산만한 작업환경, 전기설비의 노후화 등의 불안요인에 의해 타설비에 비해 많은 감전위해요인을 나타내고 있다. 이중 22.9[kV] 수전설비에 사용되는 계기용변성기 절연커버는 절연커버와 전선 인입 및 인출부 사이의 이격거리가 짧아 전기안전 측면에서 좋은 성능을 나타내지 못하고 있다. 절연커버와 부싱 사이의 크기 차이로 바람, 비등의 외부 환경에 의해 절연커버의 유동이 쉽게 발생하며, 트래킹에 의한 절연파괴로 이어질 수 있다. 따라서 본 논문에서는 전기재해를 효과적으로 방지할 수 있는 계기용변성기 절연커버를 제안하였으며 이미 실용신안으로 등록되었다. 특정 부위의 전계 집중을 감소시키기 위해 절연커버의 형상을 곡면으로 설계하였고 절연커버와 충전부 사이의 이격거리를 기존의 방식보다 더 길어지도록 조정하였다. 제안된 절연커버는 전계해석 프로그램에 의해 평가되었다.

배전용 절연카바류의 경년특성 분석 (The Analysis of Ageing Characteristics of Insulation Cover Using in Distribution Line)

  • 김동명;송일근;한재홍;이병성;한용회;이태선
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.76-78
    • /
    • 2001
  • In this paper insulation cover that being used in distribution line have been evaluated for aging characteristics. For evaluating its aging properties, we dismounted a variety of samples, like insulation covers for termination of deadend clamp, bushing, LA, COS and sleeve, in the fields. we performed mechanical properties test, electrical test, weathering test, etc. of these samples. And these samples are compared with virgin sample. Test results shows the bad mechanical strength in some part of samples. Especially, Insulation covers for the bushing terminations have cracks in the surface of samples.

  • PDF

조선해양 파이프 단열재 커버 적용을 위한 내화/난연 성능을 갖는 친환경 바잘트섬유 강화 퓨란계 복합재료 개발 연구 (Development of Eco-friendly Basalt Fiber-reinforced Furan-based Composite Material with Improved Fire and Flame Retardants for Shipbuilding and Offshore Pipe Insulation Cover)

  • 권동준;서형석
    • Composites Research
    • /
    • 제34권1호
    • /
    • pp.57-62
    • /
    • 2021
  • 조선해양산업에서 친환경 선박 및 경량화 기자재에 관한 관심이 높아짐에 따라 파이프 등의 기자재에 복합재료를 적용하고 있다. 본 연구에서는 친환경 및 내열/난연 성능을 요구하는 파이프 단열재 커버에 적용하기 위해 친환경 소재인 바잘트 섬유강화 퓨란복합재료(BFC, basalt fiber reinforced furan composite)를 제조하였다. BFC 소재의 낮은 물성을 강화시키기 위해 후경화 조건의 최적화 연구를 수행하였고, BFC 소재의 기계적강도, 내열/난연 특성 강화, 친화경 특성에 대한 실험과 평가를 진행하였다. 최종적으로 연구 결과 조선해양기자재인 파이프 단열재 커버에 BFC 소재의 적용이 가능함을 확인하였다.

22.9 kV용 변압기 부싱 절연 커버의 실태 조사 및 열화 특성 (The Deterioration Properties and Actual Conditions of Insulation Cover used at 22.9 kV Transformer Bushing)

  • 최충석;김향곤;한운기;이기연
    • 한국화재소방학회논문지
    • /
    • 제20권3호
    • /
    • pp.35-41
    • /
    • 2006
  • 본 논문에서는 22.9 kV용 변압기 부싱 절연 커버의 실태조사를 실시하였다. 절연 커버에 열적 스트레스를 인가하여 열화 패턴, 열 중량 변화, 적외선 특성 등을 해석하여 전기사고 원인 분석을 위한 근거를 제시하고자 한다. 노출된 변압기 단자를 보호하기 위해 설치한 절연 커버의 크기 및 길이가 부적절한 것이 확인되었다. 절연 커버에 $150^{\circ}C$의 열적 스트레스를 인가한 경우 플라스틱 절연 커버(A, B, D, E)는 심한 변형이 일어났으나, 고무 절연 커버 C는 정상이었다. 열 중량 분석 결과 절연 커버 A는 $307.8{\sim}405.9^{\circ}C$에서 33.3%의 감소가 있었으며, 절연 커버 C는 $258.8{\sim}332.9^{\circ}C$에서 53.7%의 감소가 발생하였다. FT-IR 분석에서 플라스틱 절연 커버는 $CH_2,\;CH_3$, C=O, C=C 결합 구조를 갖는 것으로 나타났으며, 고무 절연 커버는 OH, $CH_2,\;CH_3$, C=O, C=N, C=C 등의 결합인 것을 알 수 있었다.

22.9kV 수변전설비의 실태 및 계기용변성기 절연커버의 출화특성에 관한 연구 (A Study on the Fire Properties of MOF Insulation Cover and Field Condition of 22.9kV Class Power Receiving System)

  • 최충석;김동우;한운기;이기연
    • 한국안전학회지
    • /
    • 제20권2호
    • /
    • pp.56-60
    • /
    • 2005
  • We studied fire properties of MOF(Metering Out Fit) insulation cover and field condition of 22.9kV power receiving system. $49.5\%$ of formal equipments were installed indoors, whereas $40.8\%$ of informal equipments were installed as H-type. Insulation treatment was not done at a $22.4\%$ ratio of main line($27.7\%$ of transformer, $70.2\%$ of COS, $10.4\%$ of MOF). Fire pattern analysis showed that the fire started at the secondary part of OC wire. In the result of DTA(Differential Thermal Analysis), normal cover showed exothermic reactions at $310^{\circ}C,\;399^{\circ}C\;and\;510^{\circ}C$ (endothermic reactions at $382^{\circ}C$). Whereas damaged cover showed exothermic reactions at $412^{\circ}C$(endothermic reactions at $389^{\circ}C$). In the result of TGA(Thermo Gravimetric Analysis), the thermal weight change of normal cover was similar compared to damaged cover. In the result of FT-IR analysis, normal cover showed absorption peaks at $3,024cm^{-l},\;2,921cm^{-l},\;1,600cm^{-1},\;1,492cm^{-1},\;1,451cm^{-1},\;1,154cm^{-l},\;1,027cm^{-1},\;906cm^{-1}$. Whereas, in case of tracked cover, the absorption peaks that were shown in normal cover disappeared and different absorption peak was shown at $966cm^{-1}$.

컨버터 내장형 LED 가로등 및 보안등의 전기적 특성 분석 (Electrical Characteristics Analysis of LED Lamps using Internal Converter for Road and Street Lighting)

  • 김향곤;길형준;최효상
    • 전기학회논문지P
    • /
    • 제59권2호
    • /
    • pp.238-244
    • /
    • 2010
  • In this paper, we studied electrical characteristics of internal converter type of LED lamps for road and street lighting. We surveyed electro-technical regulations and KS(Korean industrial standards) about LED luminairs. Waveforms of voltage and current, thermal distributions, insulation resistances between live parts and exposed conductive parts, and flame test of cover of LED lamps were experimented and analyzed. In regulations, insulation resistance between live conductors and exposed conductive parts should be greater than $0.2M{\Omega}$ in case nominal voltage of wiring is 220V. In KS codes, the value of insulation resistance should be greater than $2M{\Omega}$ while applying DC 500V or DC 100V. In the result of this study, waveforms of primary voltage and current were distorted. There was difference in waveforms of secondary voltage and current according to composition of converter. Mostly, insulation resistances were measured high more than regulation and code value but some measured points were measured badly($0.0M{\Omega}$). Cover of LED lamps was ignited easily. We expect that the results of this study would be helpful for revision of regulations and national codes for the electrical safety of LED road and street lighting.

염수에 의해 열화된 절연커버 및 옥외용 가교폴리에틸렌 절연전선의 표면구조변화 (A Change of Surface Structure with Insulation Cover and Outdoor Cross-linked Polyethylene Insulated Wire Degraded by Salt Water)

  • 최충석;길형준;김향곤;한운기
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2004년도 하계학술대회 논문집 C
    • /
    • pp.1897-1899
    • /
    • 2004
  • In this paper, in order to analyze the characteristics of degradation by salt water with insulation cover and OC wire(outdoor cross-linked polyethylene insulated wire) used in power receiving system, an experimental apparatus has been designed and fabricated. An insulation cover and OC wire were installed in an experimental apparatus, and degraded in each case of 2%, 5%, 10% salinity during 12 weeks. An optical microscope was used to observe a changing process of sample surface, and an electrical safety was analyzed by measuring dielectric breakdown voltages of samples. As salinity increased, so ununiformity of sample surface increased. The breakdown wasn't produced to 50kV about samples regardless of salinity, testing period.

  • PDF

소듐냉각 고속로의 커버가스 영역에서 열유동 해석 (ANALYSIS OF HEAT TRANSFER AND FLUID FLOW IN THE COVER GAS REGION OF SODIUM-COOLED FAST REACTOR)

  • 이태호;김성오;한도희
    • 한국전산유체공학회지
    • /
    • 제13권3호
    • /
    • pp.21-27
    • /
    • 2008
  • The reactor head of a sodium-cooled fast reactor KALIMER-600 should be cooled during the reactor operation in order to maintain the integrity of sealing material and to prevent a creep fatigue. Analyzing turbulent natural convection flow in the cover gas region of reactor vessel with the commercial CFD code CFX10.0, the cooling requirement for the reactor head and the performance of the insulation plate were assessed. The results showed that the high temperature region around reactor vessel was caused by the convective heat transfer of Helium gas flow ascending the gap between the insulation plate and the reactor vessel inner wall. The insulation plate was shown to sufficiently block the radiative heat transfer from pool surface to reactor head to a satisfactory degree. More than $32.5m^3$/sec of cooling air flow rate was predicted to maintain the required temperature of reactor head.

BIM의 패밀리 라이브러리를 이용한 복잡한 상세를 갖는 고단열 벽체 판넬의 물량 산출 방법 (Quantity Estimation Method for High-Performance Insulated Wall Panels with Complex Details Using BIM Family Libraries)

  • 문주현
    • 한국건축시공학회지
    • /
    • 제24권4호
    • /
    • pp.447-458
    • /
    • 2024
  • 이 연구의 목적은 복잡한 상세를 갖는 부재의 생산공정에서 발생하는 물량산출 오차를 최소화할 수 있는 BIM의 패밀리 라이브러리를 이용한 고단열 벽체 판넬의 물량산출 방법을 제시하는데에 있다. 주요변수는 공장의 생산공정에서 주로 발생할 수 있는 오차인 콘크리트 피복두께와 철근 구부림의 최소 내면 반지름으로 설정하였다. Revit BIM 프로그램으로 모델링된 단면 보다 생산현장에서 제작된 고단열 벽체 판넬의 콘크리트 피복두께는 약 12% 작았으며 철근 구부림의 최소 내면 반지름은 약 1.27배 컸다. 이러한 변화를 Revit BIM 프로그램을 이용한 고단열 벽체 판넬의 모델링에 반영하고 Navisworks를 이용하여 구성된 재료들의 간섭 체크 및 보정하였다. 특히, 각 재료들의 체적 등가 개념을 이용하여 1m 단위의 벽체로 환산하였으며, 이때 수직 및 수평접합에 설치되는 단열재와 스플라이스 슬리브도 포함하였다. 환산된 1m 단위의 벽체는 각 재료들의 물량 측면에서 유사한 패밀리 라이브러리의 "단열재가 삽입된 이중 RC 벽체"로 결정될 수 있었다. 제시된 레빗 프로그램에 내장된 패밀리 라이브러리의 "단열재가 삽입된 이중 RC 벽체"는 공장의 생산공정에서 발생하는 제조오차를 고려하면서 복잡한 단면을 가지고 있는 고단열 벽체 판넬 상세에서 각 재료들의 물량을 산출하는데에 활용될 수 있을 것으로 기대된다.