Browse > Article
http://dx.doi.org/10.5207/JIEIE.2005.19.2.055

A Study on the Improvement of Insulation cover for Instrument Transformer Used In Power Receiving System of Construction Sites  

Gil, Hyoung-Jun (전기안전연구원 전기재해연구그룹)
Choi, Chung-Seog (전기안전연구원 전기재해연구그룹)
Kim, Hyang-Kon (전기안전연구원 전기재해연구그룹)
Han, Woon-Ki (전기안전연구원 전기재해연구그룹)
Lee, Bok-Hee (전기안전연구원 전기재해연구그룹)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.19, no.2, 2005 , pp. 55-62 More about this Journal
Abstract
There are many risk factors of electrical shock caused by a minimum of protective devices, loose working environments, deterioration of installations at temporary power installations of construction sites. An insulation cover for instrument transformer(MOF) used in 22.9[kV] class power receiving system hasn't shown good performance in terms of electrical safety because of short clearance between insulation cover and each input and output wire junction part. The insulation cover is easily moved by outside environment as wind or rain because of different size between insulation cover and busing, also can be leaded to breakdown by tracking. Therefore, we have proposed the insulation cover which effectively can prevent from electrical disaster in this paper, and a utility model patent had been registered already. To decrease the electric field concentrated on specific part, we had roundly designed the shape of insulation cover and the clearance between cover and live part was adjusted to be longer than the existing thing. The proposed insulation cover was evaluated by using the electric field solution program.
Keywords
Citations & Related Records
연도 인용수 순위
  • Reference
1 한운기, 한기붕, 길형준, 최충석, '임시전력설비 감전재해 발행현황 분석에 관한 연구', 한국산업안전학회 추계학술발표회 논문집, pp.118-123, 2003
2 Chung-Seog Choi, Hyoung-Jun Gil, Ki-Boong Han, Woon-Ki Han, 'The statistical analysis and investigation of field condition about electrical shock accidents and risk factors in temporary power installations', International Journal of Safety, Vol. 2, No. 2, pp.22-28, 2003
3 Chung-Seog Choi, Woon-Ki Han, Hyoung-Jun Gil, Ki-Boong Han, 'The fire characteristics of MOF insulation cover used in 22.9kV class temporary power installations', Asia-Oceania Symposium on Fire Science and Technology, pp.711-716, 2004
4 이복희, '접지의 핵심기초기술', 의제, pp.4-20, 2002
5 Virr, L. E., 'Increased electric shock risk underwater due to electrode configuration and insulating boundaries', IEE Proc., Computers in Cardiology, pp. 261-268, 1990
6 Bridges, J. E., 'New developments in electrical shock safety', IEEE., International Symposium on Electro-magnetic Compatibility, pp.22-25, 1994
7 길형준, 한운기, 김향곤, 최충석, '건설현장의 수전설비 및 배.분전반의 현장실태 분석', 한국조명.전기설비 학회 춘계학술대회 논문집, pp.335-340, 2004
8 이복희, 이승칠, 엄주홍, 김효진, '보조접지전극의 시설 에 의한 대지표면전위경도의 저감', 한국조명.전기설비학회 논문지, Vol. 16, No. 2, pp.121-129, 2002
9 Ronald P. O'Riley, 'Electrical Grounding', Thomson Learning, pp.24-29, 2002
10 Chung-Seog Choi, Hyang-Kon Kim, Hyoung-Jun Gil, Woon-Ki Han, 'A study on the dielectric breakdown process of insulation cover for instrument transformer by salt water', 30th International Symposium on Combustion, pp.224, 2004
11 Mohla, D., McClung, L. B., Rafferty, N. R., 'Electrical safety by design', IEEE., Petroleum and Chemical Industry Conference, pp. 363-369, 1999