The Deterioration Properties and Actual Conditions of Insulation Cover used at 22.9 kV Transformer Bushing  

Choi, Chung-Seog (전기안전연구원(한국전기안전공사))
Kim, Hyang-Kon (전기안전연구원(한국전기안전공사))
Han, Woon-Ki (전기안전연구원(한국전기안전공사))
Lee, Ki-Yeon (전기안전연구원(한국전기안전공사))
Publication Information
Fire Science and Engineering / v.20, no.3, 2006 , pp. 35-41 More about this Journal
Abstract
In this study, we presented the problems in the insulation cover of 22.9kV transformer bushing through investigating actual conditions. After thermal stress applied to the insulation cover, deterioration patterns, thermogravimetric and infrared characteristics were analyzed, and the results were applied to the cause analysis of accidents and judgement of safety. The insulation covers are used to protect exposed terminals of transformer, but they had improper size and length. Therefore, they could not show efficient insulation function. In case that thermal stress of $150^{\circ}C$ was applied to the insulation covers, plastic insulation covers(A, B, D, E) damaged severely, whereas rubber insulation cover(C) showed normal shapes. In the result of thermogravimetric analysis, the thermal gravity of plastic covers(A) decreased about 33.3% at $307.8^{\circ}C\;to\;405.9^{\circ}C$. and he thermal gravity of rubber covers (C) decreased about 53.7% at $258.8^{\circ}C\;to\;32.9^{\circ}C$. In the result of FT-IR analysis, plastic covers showed peaks characteristic of $CH_2,\;CH_3$, C=O and C=C bonds, whereas rubber covers showed peaks characteristic of OH, $CH_2,\;CH_3$, C=O, C=N and C=C bonds.
Keywords
Transformer bushing; Insulation cover; Deterioration; TGA; FT-IR;
Citations & Related Records
Times Cited By KSCI : 1  (Citation Analysis)
연도 인용수 순위
1 최충석 외 5, '전기화재공학', 동화기술, pp.189-270, (2004)
2 C.-S. Choi et al., 'The Statistical Analysis and Investigation of Field Condition about Electrical Shock Accidents and Risk Factors in Temporary Power Installations', International Journal of Safety, Vol. 2, No. 2, pp.22-28(2003)
3 C.-S. Choi et al., 'The Fire Characteristics of MOF Insulation Cover Used in 22.9 kV Class Temporary Power Installations', Asia-Oceania Symposium on Fire Science and Technology, pp.711-716(2004)
4 최충석, 이경섭, 이덕출, '열 열화된 600 V 2종 비닐 절연전선의 특성 변화 분석', 대한전기학회논문지, Vol. 49C, No. 1, pp.8-12(2000)
5 최충석, 송길목, 김동우, '누전차단기 외함 전원측 단자사이의 트래킹에 의한 탄화특성 분석', 한국화재소방학회논문지, Vol. 17, No. 4, pp.13-19(2003)
6 송인회, 電氣災害統計分析, 韓國電氣安全公社, pp.88-89(2004)
7 한국산업규격 KS C 4307, 주상변압기용 부싱의 크기, 기술표준원(1999)
8 한국전력공사, 한국전력공사 표준 구매 시방서 PS 112-647(2001)
9 C.-S. Choi et al., 'A study on the Characteristics of Tracking Deterioration Between Electrodes on Phenolic Resin Used for Low Voltage', KIEE, The international Conference on Electrical Engineering Proceedings, pp.1135-1138(2002)
10 길형준, 한운기, 김향곤, 최충석, '건설현장의 수전설비 및 배.분전반의 현장실태 분석', 한국조명.전기설비학회 춘계학술대회 논문집, pp.335-340(2004)
11 ASTM D 2303-90, Standard Test Method for Liquid-Contaminant, Inclined-Plane Tracking and Erosion of Insulating Materials, ASTM