ANALYSIS OF HEAT TRANSFER AND FLUID FLOW IN THE COVER GAS REGION OF SODIUM-COOLED FAST REACTOR

소듐냉각 고속로의 커버가스 영역에서 열유동 해석

  • 이태호 (한국원자력연구원, 고속로기술개발부) ;
  • 김성오 (한국원자력연구원, 고속로기술개발부) ;
  • 한도희 (한국원자력연구원, 고속로기술개발부)
  • Published : 2008.09.30

Abstract

The reactor head of a sodium-cooled fast reactor KALIMER-600 should be cooled during the reactor operation in order to maintain the integrity of sealing material and to prevent a creep fatigue. Analyzing turbulent natural convection flow in the cover gas region of reactor vessel with the commercial CFD code CFX10.0, the cooling requirement for the reactor head and the performance of the insulation plate were assessed. The results showed that the high temperature region around reactor vessel was caused by the convective heat transfer of Helium gas flow ascending the gap between the insulation plate and the reactor vessel inner wall. The insulation plate was shown to sufficiently block the radiative heat transfer from pool surface to reactor head to a satisfactory degree. More than $32.5m^3$/sec of cooling air flow rate was predicted to maintain the required temperature of reactor head.

Keywords

References

  1. 2007, 한도희 외, "KALIMER-600 개념설계 보고서," KAERI/TR-3381/2007, 한국원자력연구원
  2. 2005, ANSYS CFX-Solver, Release 10.0, ANSYS Inc.
  3. 2001, Velusamy, K., Sundararajan, T. and Seetharamu, K.N., "Interaction Effects Between Surface Radiation and Turbulent Natural Convection in Square and Rectangular Enclosures," J. Heat Transfer, Vol.123, pp.1062-1070 https://doi.org/10.1115/1.1409259
  4. 2006, Eoh, J.H. et al., "Design and Performance Analysis of the Passive Cavity Cooling System of KALIMER-600," Proceedings of the Korean Nuclear Society Autumn Meeting, Gyeongju, Korea
  5. 1989, Todreas, N.E. and Kazimi, M.S., Nuclear System I-Thermal Hydraulic Fundamentals, Hemisphere Publishing Corporation