• Title/Summary/Keyword: Insulated pipe

Search Result 42, Processing Time 0.043 seconds

A Study on Alternative Backfill Material for Pre-insulated Pipe through the Laboratory Tests (실내시험을 통한 이중보온관 되메움 대체재료에 관한 연구)

  • Choi, Bong-Hyuck;Kim, Jin-Man;Yoo, Han-Kyu
    • Journal of the Korean Geotechnical Society
    • /
    • v.27 no.9
    • /
    • pp.5-11
    • /
    • 2011
  • This paper recommends the alternative back-fill material for the pre-insulated pipe based on the results of tests performed using different kinds of backfill material. In this study, laboratory tests were preformed to determine the behavior of the pre-insulated pipe caused by variation on grain size distribution, friction characteristics and earth pressure characteristics of different types of backfill material. Two types of natural sand (fine-grained and coarse-grained sand) and crushed sand, and two types of gravel (10mm, 20mm) were used as backfill material in the laboratory tests. The laboratory test results were analyzed and compared with the pre-insulated pipe backfilled with the standard medium-grained sand. Based on the evaluation and comparison of laboratory test results, it was determined that crushed sand is the most suitable back-fill material that can be used as an alternative for medium grained sand for pre-insulated pipes.

A Study on Alternative Backfill Material for Pre-insulated Pipe through the Field Tests (현장시험을 통한 이중보온관 되메움 대체재료에 관한 연구)

  • Choi, Bong-Hyuck;Kim, Jin-Man;Yoo, Han-Kyu
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.32 no.1C
    • /
    • pp.1-6
    • /
    • 2012
  • In this study, field tests were performed to evaluate the stability of pre-insulated pipe during the compaction operation and to recommend an alternative backfill material. Three types of natural sand (fine-grained and medium-grained, coarse-grained sand), crushed sand and two types of gravel (10 mm, 20 mm) were used as backfill material in the field tests. Field tests were performed to determine the behavior (earth-pressure and deformation, installation damage) of the pre-insulated pipe due to variation of different types of backfill material. Based on the evaluation and comparison of field test results, it was determined that crushed sand is the most suitable back-fill material that can be used as an alternative for medium grained sand for pre-insulated pipes with respect to the engineering behavior and material supply.

The Stability Assessment of Backfill Materials and External Loads in Pre-Insulated District Heating Pipes (지역난방 열배관의 외부작용력 및 되메움재의 안정성 확보에 관한 연구)

  • Kim, Jin-Man;Choi, Bong-Hyuck;Ko, Hyun-Il
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.656-661
    • /
    • 2009
  • In this study, theoretical analysis and evaluation tests were performed to assess the pipe stability against compaction equipments and vehicle loads when conventional construction criteria for pre-insulation heating pipes are applied and the alternative material, crushed sand, are used for backfills. The research outcomes shows that (1) the conventional code criteria for pre-insulated heating pipes is well established to support compaction equipments and vehicle loads, (2) the crushed sands as an alternative is usable as backfill materials for pre-insulated heating pipes based on the suitability evaluations of various types of pipes, and (3) the crushed sand agree well with the design consideration of pre-insulated heating pipes construction in the points of economical efficiency and construction criteria.

  • PDF

A Study on Blasting Vibration Control Criteria for Pre-insulated Pipe through the Numerical Analysis (수치해석을 이용한 이중보온관 발파진동 관리기준에 관한 연구)

  • Choi, Bong-Hyuck;Cho, Jin-Woo;Kim, Jin-Man;Yoo, Han-Kyu
    • KSCE Journal of Civil and Environmental Engineering Research
    • /
    • v.33 no.4
    • /
    • pp.1471-1478
    • /
    • 2013
  • In this paper, numerical analysis with varying distance and burial depth was performed to recommend the blasting vibration control standard for pre-insulated pipes. The blasting load model applied in the numerical analysis was verified to the comparison with the results of the field tests. It was determined from the results of the numerical analysis that the effective stress either exceeds or approaches the allowable stress of the inner steel pipe for vibration velocity greater than 4.0cm/sec while stability is obtained for vibration velocity below 4.0cm/sec. Therefore, it was determined that the blasting vibration control criteria for pre-insulated pipes must not exceed 4.0cm/sec.

A study on Stress Corrosion Cracking of Sensor Wire in Thermally Insulated Underground Pipeline (이중보온관 부식감지선의 응력부식파괴에 관한 연구)

  • Choe, Yun-Je;Kim, Jeong-Gu
    • Korean Journal of Materials Research
    • /
    • v.12 no.2
    • /
    • pp.103-111
    • /
    • 2002
  • The thermally insulated underground pipelines have been used for district heating system. The sensor wire embedded in the insulation was used for monitoring the insulating resistance between the sensor wire and the pipe. The resistance measurement system detects corrosion of steel pipe under insulation. The corrosion and stress corrosion cracking(SCC) characteristics of sensor wire in synthetic ground water were investigated using the electrochemical methods and constant load SCC tests. The polarization tests were used to study the electrochemical behavior of sensor wire. The sensor wire was passivated at temperatures ranging from 25 to $95^{\circ}C$. However, the applied sensing current larger than passive current resulted in breakdown of passive film. The constant load SCC tests were performed to investigate the effects of applied current and load on the fracture behavior. Stress-corrosion cracks initiated at pits that were produced by sensing current. The growth of the pit involves a tunnelling mechanism, which leads to ductile fracture.

Bayonet type vacuum insulated pipes with Teflon seal (Teflon seal을 이용한 bayonet형 진공단열배관)

  • 이현철;강형석
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 1999.02a
    • /
    • pp.173-176
    • /
    • 1999
  • Vacuum insulated pipes (VIP) are one of the important equipments for cryogenic fluids' transfer. Flange type of VIP, which can easily be installed at the site, uses a set of male and female bayonet with very small gap between them. In order to prevent leakage of liquid from inner pipe to bayonet. Teflon or Kel-F is located outside both the inner pipe of male and the guide of female. Even though liquid may leak at room temperature, it cannot leak at cryogenic temperature since Teflon shrinks much more than pipes and adheres closely to the inner pipe and guide. Teflon seal method has the advantage of easy fabrication, low cost and effective sealing compared to the conventional method.

  • PDF

Integrated Expansion Analysis of Pipe-In-Pipe Systems

  • Choi, Han-Suk;Do Chang-Ho
    • Journal of Ocean Engineering and Technology
    • /
    • v.20 no.5 s.72
    • /
    • pp.9-14
    • /
    • 2006
  • This paper presents an analytical method, application of expansion, mechanical design, and integrated expansion design of subsea insulated pipe-in-pipe (PIP) systems. PIP system consists of a flowline and a casing pipe for the transport of high temperature and high pressure product from the subsea wells. To prevent heat lass from the fiowline, insulation material is applied between the pipes. The fiawline pipe and the casing pipe have mechanical connections through steel ring plate (water stops) and bulkheads. Pipeline expansion is defined by temperature, internal pressure, soil resistance, and interaction force between the flowline and the casing pipe. The results of the expansion analysis, the mechanical design of connection system of the two pipes and tie-in spool design are integrated for the whole PIP system.