• 제목/요약/키워드: High frequency partial discharge (HFPD)

검색결과 18건 처리시간 0.024초

차량탑재형 HFPD의 개발 (The Development of HFPD System for Mibile-loading Vehicles)

  • 김덕근;임장섭;여인선
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
    • /
    • pp.33-37
    • /
    • 2001
  • Recently, the HFPD measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Also HFPD testing is able to offer the judgement standard of degradation level of HV machine and can detect discharge signals in live-line. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

신경회로망을 이용한 HFPD 패턴인식 (HFPD Pattern Recognition Using Neural Network)

  • 김덕근;정영일;임장섭;여인선
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1698-1700
    • /
    • 2002
  • Recently, the HFPD measurement methods that detect high frequency bandwidth of frequency components of partial discharge pulses are proposed and many studies are carried out. The HFPD measurement method is able to detect partial discharge signal in active line, therefore this method has a merit that can does condition monitoring of power equipments and measure growth state of partial discharge erosion with on-line and real time. In this study, the radiated HFPD signals are detected by antenna and aging diagnosis is executed with a neural network algorithm. As a result of this study, the aging diagnosis of insulation material using neural networks is possible.

  • PDF

인가 스트레스에 따른 HFPD의 통계적 패턴해석 (Statistic Pattern Analysis of HFPD According to Applied Stress)

  • 김덕근;이은석;정영일;임장섭;김태성
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마
    • /
    • pp.18-22
    • /
    • 2000
  • The partial discharge testing is widely used in insulation property measurement because it gives low stress to high voltage equipment which is undertaken tests. Therefore it is very useful method compare to previous destructive methods and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

PD 측정과 HFPD의 감도특성에 관한 연구 (A Study on the Sensitivities Characteristics in a PD and a HFPD)

  • 임장섭;김덕근
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마
    • /
    • pp.29-32
    • /
    • 2000
  • The partial discharge testing is widely used in insulation property measurement because it gives low stress to high voltage equipment which is undertaken tests. Therefore it is very useful method compare to previous destructive methods and effective diagnosis method in power transformer that requires on-line & on-site diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and PD/HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

HFPD 및 신경회로망을 이용한 고압 유도전동기 모델코일 열화진단 (Aging Diagnosis of Model Coil of HV Induction Motor Using HFPD and Neural Networks)

  • 김덕근;임장섭;여인선
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제51권8호
    • /
    • pp.361-367
    • /
    • 2002
  • Many failures in high voltage equipment are preceded by partial discharge activity. In this paper deals with the application of the high frequency partial discharge measurement technique in motorette. HFPD measurement is very effective method to detect the PD occurred in motorette which is the called name of test specimen for accelerating test of stator winding[1] In this study, CT type HFPD sensor is used to detect the partial discharges and a measured HFPD pattern is analyzed by fractal mathematics. The neural network algorithm is used to pattern recognition and ageing diagnosis. As a result of this study, the fractal dimensions are increased along to applied voltage and HFPD pattern recognition using neural network shown excellent recognition rate. Also, the ageing diagnosis of motorette has been Possible.

3d-PD 패턴과 VHF/UHF PD 신호의 고찰 (The Analysis of VHF/UHF PD and 3d-PD Pattern)

  • 임장섭;박용석;최병하;한석균
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2001년도 춘계학술대회 논문집 반도체재료
    • /
    • pp.75-78
    • /
    • 2001
  • Recently, the HFPD measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Also HFPD testing is able to offer the judgement standard of degradation level of HV machine and can detect discharge signals in live-line. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

모의 변압기의 VHF/UHF PD 스펙트럼 분석 (Spectrum Analysis of VHF/UHF PD in Simulated Transformer)

  • 김덕근;김종서;임용배;임장섭;문채주
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 춘계학술대회 논문집 유기절연재료 방전 플라즈마
    • /
    • pp.50-54
    • /
    • 2000
  • Recently, the HFPD measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Also HFPD testing is able to offer the judgement standard of degradation level of HV machine and can detect discharge signals in live-line. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires live-line diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In recent, the study of partial discharge is carrying out discover of initial defect of power equipment through condition diagnosis and system development of degradation diagnosis using HFPD(High Frequency Partial Discharge) detection. In this study, simulated transformer is manufactured and HFPD occurred from transformer is measured with broad band antenna in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages.

  • PDF

인가전압에 따른 모의변압기의 HFPD 특성분석 (HFPD Characteristic Analysis of Simulated Transformer According To Applied Voltage)

  • 김덕근;임영삼;임장섭;문채주;이진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2000년도 하계학술대회 논문집 C
    • /
    • pp.1957-1959
    • /
    • 2000
  • The PD measurement method is very useful to detect insulation degradation. Recently, the HFPD(High Frequency Partial Discharge) measurement testing is widely used in partial discharge measurement of HV machines because HFPD measurement testing receives less influence of external noise and has a merit of good sensitivity. Therefore it is very useful method compare to previous conventional PD testing method and effective diagnosis method in power transformer that requires in-service diagnosis. But partial discharges have very complex characteristics of discharge pattern so it is required continuous research to development of precise analysis method. In this study, simulated transformer is manufactured and HFPD occurred from simulated transformer is measured with broad band antenna and active-line RF measurement system in real time, the degradation grade of transformer is analyzed through produced patterns in simulated transformer according to applied voltages. Also the PD pattern which was measured with EMC analyzer and RF measurement system is compared.

  • PDF

고주파 부분방전 측정에 의한 초고압 접속함 신뢰성 평가 기술 (A Evaluation Technique for Reliability of Extra-High Voltage Cable Accessories using High Frequency Partial Discharge Measurement)

  • 신두성;이창영;김충식;전승익;김동욱;박완기
    • 대한전기학회논문지:전기물성ㆍ응용부문C
    • /
    • 제49권3호
    • /
    • pp.186-195
    • /
    • 2000
  • In this paper, partial discharge (PD) measurement was performed to evaluate the quality of the cable joint and termination constructions. The resistive coupling technique for PD detection using resistivity of semiconducting layer of the cable in the accessories, such as joints and terminations. With high frequency PD (HEPD) measurement, an excellent sensitivity below 20pC could be achieved under unshielded condition. The localization of the defects in the accessories could be identified. During heating cycle, PDs were monitored and analyzed. At that time, the PDs were dependent on the temperature of the heating cycle and showed cyclic behaviors, which were attributed to local delamination of the interfaces, between epoxy unit and stress relief cone(SRC) and between SRC and cable, due to the difference of thermal expansion. As a conclusion, HFPD measurement technique was proven to be an effective diagnostic method for qualification of extra high voltage (EHV) cable accessories. With this technique, the optimal design of the components of the accessories could be verified not only in an early stage but also under operating condition. This technique would result in the improvement of the reliability of the EHV cable accessories.

  • PDF

HFPD 패턴분석을 이용한 절연열화 진단 (Insulation Ageing Diagnosis Using HFPD Pattern Analysis)

  • 김덕근;여인선;임장섭;이진
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 C
    • /
    • pp.1726-1728
    • /
    • 2003
  • The aging diagnosis method using partial discharge measurement detects discharge signals that critical cause of failure in insulation material operated a long time and can diagnose aging state of insulation materials with an aging analysis algorithm. The HFPD measurement method is a technique to analyze aging state of high voltage insulation materials and detect higher frequency signals than conventional PD measurement method therefore it takes less noise effect and could execute active line measurement. It is possible to analyze main discharge phenomena and obtain access to aging progress occurred in insulation materials through accumulation of HFPD signals during determined interval and expression of fractal dimension using statistical process of accumulated signals. The HFPD signals that occurred in each applied voltages are measured during 180 cycles and accumulated to the same phase of one cycle. These patterns that made by previous method are normalized with logarithm function and than inputted to neural networks. The aging diagnosis of insulation material was possible and the recognition ratio of neural network appeared very high.