• 제목/요약/키워드: HVDC system

검색결과 377건 처리시간 0.022초

Hardware-in-the-Loop Simulation을 이용한 3-레벨 NPC 전압형 HVDC 시스템 구현 및 테스트 (Implementation and Test of 3-level NPC VSC-HVDC System using Hardware-in-the-Loop Simulation)

  • 유형준;김남대;김학만
    • 전기학회논문지
    • /
    • 제63권3호
    • /
    • pp.343-348
    • /
    • 2014
  • Recently, applications of VSC-HVDC systems to power systems are growing because of their control ability of reactive power. Meanwhile, the hardware-in-the-loop simulation (HILS) based on the real-time digital simulator has been applying to develop and test imbedded controllers and systems in the power industry to decrease costs and to save time. In this paper, a 3-level neutral point clamped (NPC) VSC-HVDC system is modeled and the embedded controllers of the NPC VSC-HVDC system are designed. The designed controllers are implemented by TMS320F28335. The TMS320F28335-based controllers of the NPC VSC-HVDC system are tested using the HILS.

제주 ±80kV 60MW HVDC 협조 제어 방안 연구 (A cooperative control study of Jeju ±80kV 60MW HVDC for voltage stability enhancement)

  • 윤종수;서보혁
    • 전기학회논문지
    • /
    • 제61권9호
    • /
    • pp.1221-1225
    • /
    • 2012
  • This paper describes CSC(Current Sourced Converters)-based HVDC operational strategy for voltage stability enhancement in the power system. In case of CSC-based HVDC system, rectifier and inverter consume reactive power up to about 60% of converter rating. Therefore, CSC-based HVDC is basically not useful system for voltage stability even if AC filters and shunt capacitors are attached. But, If the particular power system condition is fulfilled, CSC-based HVDC also can be the rapid reactive power source for voltage stability enhancement using a cooperative control with converter and AC filters/Shunt Capacitors. In this paper, the cooperative control algorithm is presented and simulated to ${\pm}80kV$ 60MW HVDC system in Jeju island.

HVDC시스템의 직류측 보호 모델 개발 (The Assessment and Development of Protection Models in HVDC DC side)

  • 이성두;김찬기
    • 전기학회논문지
    • /
    • 제59권10호
    • /
    • pp.1754-1760
    • /
    • 2010
  • The HVDC system consists of ac side and dc side through thyristor valve. ac side protection is similar to conventional ac system protection schemes but dc side protection is different from ac side of HVDC system. AC system don't have controller but HVDC system has controller that controls and protects system from faults and disturbance. This paper show protectional function of HVDC dc side such as asymmetry protection, ac/dc differential protection, dc overvoltage, dc overcurrent protection. Protection models is developed using RTDS software and assessment of protection models is also performed by RTDS system.

PSS/E를 이용한 제주계통의 DFIG 풍력발전단지 및 HVDC 동적모델 개발 (Development of Dynamic Models for DFIG Wind Farms and HVDC in Jeju Power System Using PSS/E)

  • 남순열;강상희;남해곤;최준호
    • 전기학회논문지
    • /
    • 제60권12호
    • /
    • pp.2183-2189
    • /
    • 2011
  • Since main portion of the required electric power in Jeju Island is provided from the mainland through two HVDC lines, Jeju HVDC has a most significant impact on Jeju power system. Average wind speed of Jeju Island is the highest among several candidates in South Korea. So, Jeju Island has been a suitable site for the construction of wind farms where several wind farms are now operating and several others to be sited. Since the large-scale wind generation could have adverse impacts on the stable operation of Jeju power system, wind power is also important for the stability of Jeju power system. Therefore, accurate modeling of Jeju HVDC and wind farms is required for stability analysis of Jeju power system. In this paper, PSS/E-based dynamic modeling of Jeju HVDC and DFIG wind farms is proposed. Model-writing technique of PSS/E is used to develop USRAUX model and USRMDL model for controlling the frequency of HVDC and imposing an operation limit of wind power, respectively. Dynamic characteristics of Jeju HVDC and DFIG wind farms are analyzed through the dynamic simulations. The simulation results show the effectiveness of the developed models for Jeju power system.

HVDC Overhaul 기간 중 제주계통에 연계된 풍력발전의 전력품질 분석 (Power Quality Analysis of Wind Farms interconnected in Jeju System during HVDC Overhaul)

  • 채우규;윤기갑;조성수;정원욱
    • 전기학회논문지
    • /
    • 제57권11호
    • /
    • pp.1946-1953
    • /
    • 2008
  • Power system of Jeju is interconnected to the mainland using HVDC and that is also interconnected to three wind farms. It will be difficult to control of Jeju power system if HVDC is disconnected or HVDC is overhauled under large scale wind farms interconnected. We measured and analysed the power quality of two substation and two wind farms to assess that wind farms have an effect on Jeju system during the HVDC overhaul last May. We concentrated on the power quality like frequency, voltage variation, voltage harmonics, current harmonics, flicker. We can found that the frequency of Jeju system is very unstable during overhaul, so the frequency of Jeju system can be variated easily by wind farm's rapid output power variation. There are some benefits and weak points in power quality between two wind farms because each wind farm is consist of different wind turbines.

HVDC 시스템의 수냉식 냉각 시스템 (Water-Cooling System of HVDC System)

  • 김찬기
    • 전력전자학회논문지
    • /
    • 제4권3호
    • /
    • pp.257-267
    • /
    • 1999
  • 본 논문은 대용량 컨버터의 수냉식 방열 시스템에 관한 내용을 담고 있다. 본 논문은 수냉식 방열 시스템의 이론적 근거와 모델링을 제시하고 전력용 반도체(싸이리스터)의 열량 계산을 수학적인 모델링에 근거하여 제시하였으며 실제로 우리나라에 설치되어 있는 제주-해남 HVDC 시스템에 적용하여 타당성을 검증하였다.

  • PDF

Advanced Real Time Simulation Platform for Control and Protection Studies of LSIS 80kV 60MW Jeju HVDC System

  • Iwa, Kartiwa;Lee, Kyung-Bin
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2013년도 추계학술대회 논문집
    • /
    • pp.85-86
    • /
    • 2013
  • This paper describes the physical configuration and features of the advanced control and protection devices, and operation control and monitoring system that are connected to a real time simulator for LS Industrial System 80kV 60 MW Jeju HVDC Pilot Project. Highlight of simulation result are provided to demonstrate the control and protection functionality.

  • PDF

Transient performance analysis of Cheju-Haenam HVDC system using PSCAD/EMTDC

  • Kim Chan-Ki;Kho Bong-Un;Yang Byeong-Mo;Choi Jong-Kee;Lee Jong-Min
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2001년도 Proceedings ICPE 01 2001 International Conference on Power Electronics
    • /
    • pp.600-605
    • /
    • 2001
  • This paper deals with dynamic performance of the Cheju - Haenam HVDC system. The purpose of the study is to verify the control characteristics of the HVDC system and to analyze the dynamic performances by simulation study. Because the HVDC system consists of analogue and digital controller, the simulation is achieved with specification model incorporating nonlinear function. The dynamic performance simulations are performed by PSCAD/EMTDC

  • PDF

60MW급 HVDC 시스템 제어 알고리즘 개발 (Development of 60MW HVDC System Control Algorithm)

  • 이경빈;정용호;황호윤
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2012년도 추계학술대회 논문집
    • /
    • pp.183-184
    • /
    • 2012
  • 2010년부터 민간기업인 LS산전과 한국전력공사의 공동 개발을 통하여 60MW급 ${\pm}80kV$ HVDC (High Voltage DC transmission System)전류형 HVDC시스템 알고리즘 국산화 개발을 진행하여 2012년 3월 개발을 완료하였다. 개발된 알고리즘의 성능, 안정성 및 신뢰성을 확보하기 위하여 LS산전에서 개발한 Hardware 플랫폼에 제어 알고리즘을 탑재하고 RTDS(Real Time Digital Simulator)를 통한 연계시험을 진행하여 이를 검증하였다. 본 논문에서는 개발된 HVDC 제어 알고리즘의 기능과 RTDS연계 시험결과를 소개하고자 한다.

  • PDF

MEAC를 적용한 HVDC Run-up SPS의 안정도향상 효과분석 (MEAC Method for Analysis of Power System Stability Improving Effect Considering Run-up SPS Function of HVDC)

  • 이재걸;송지영;장길수
    • 전기학회논문지
    • /
    • 제66권10호
    • /
    • pp.1454-1459
    • /
    • 2017
  • In spite of continuous increase of electric power demand and new generation plants, it is very difficult to install new transmission line. Therefore, it comes to be difficult to operate the power system stable, so it is required to find another way to get new transmission capacity. Because HVDC transmission system installation is the one of the best option for us, we have undertake the HVDC project in mainland. Buckdangjin-Goduck HVDC project(500kV, 3GW) is currently under construction and Eastern Power HVDC project(500kV, 8GW) is under the study for technical specification. Both of them have the Run-up SPS function for taking action of 765kV Transmission line fault. The Run-up SPS function increases the active power output of the HVDC rapidly when the transmission line between the power plant and network is tripped, thereby preventing the generator from overspeed and improving the power system stability. In this paper, we propose MEAC(Modified Equal Area Criteria) method based on traditional EAC method to quantitatively evaluate the effect of the HVDC run-up SPS function on the power system stability improvement.