• Title/Summary/Keyword: Grounding Electrode

Search Result 154, Processing Time 0.033 seconds

Effects of Length of Down Conductor on Transient Ground Impedance (인하도선 길이에 따른 과도접지임피던스 특성)

  • Lee, B.H.;Jeong, D.C.;Lee, S.B.;Lee, T.H.;Jung, H.U.;Lee, K.S.;Lee, S.C.
    • Proceedings of the KIEE Conference
    • /
    • 2005.07c
    • /
    • pp.2235-2237
    • /
    • 2005
  • This paper presents the transient impedance behaviors of grounding systems to lightning impulse current. The potential rise and effective impulse ground impedance of the test grounding electrodes were measured as a function of the rise time of impulse currents and lengths of down conductor. The transient ground impedances strongly depend on the configuration and size of grounding electrodes, the impulse current shapes and lengths of down conductor, and the inductance of reduce of grounding electrode inductance is an important factor to improve the transient ground impedance.

  • PDF

Measurement method of ground impedance for the grounding grid (접지그리드의 접지임피던스 측정 기법)

  • Lee, Bok-Hee;Choi, Jong-Hyuk;Choi, Young-Chul;Yoo, Jae-Duk;Beak, Young-Hwan;Kim, Dong-Seong;Shin, Hee-Kyung;Yoo, Yang-Woo
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1487_1488
    • /
    • 2009
  • In these days, the common grounding systems are adapted in most large structures. In order to evaluate the performance of grounding system, it is needed to measure ground impedance. Measuring methods of ground impedance for a large scale grounding systems have not been yet presented in detail. In this paper, we analyze earth mutual resistance and mutual coupling of $15{\times}15m$ grounding grid in different arrangements of auxiliary electrode. As a results, the auxiliary electrodes are installed where the error rate due to earth mutual resistance is less than 5%. Also, the potential lead is installed at obtuse angle from the current lead and the overlapped length between potential lead and grounding grid are minimized.

  • PDF

Soil Ionization Phenomena around a Hemispherical Electrode Stressed by Impulse Voltages (임펄스전압에 의한 반구형 전극계에서 토양의 이온화 현상)

  • Heo, Dae-min;Kim, Hoe-gu;Lee, Bok-hee
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.2 no.4
    • /
    • pp.601-608
    • /
    • 2016
  • The electrical characteristics of the soil where a ground electrode is buried vary with regions, seasons and environmental factors. Electrical discharge in the vicinity of the ground electrode will occur differently and significantly affect the performance of the grounding system. It is necessary to analyze discharge and ionization characteristics of soils when the grounding system is designed. The aims of this investigation are to understand correlation between the soil ionization and the transient ground impedance. This paper presents the experimental results on the soil ionization parameters and the transient ground resistance due to the soil ionization around a hemispherical ground electrode stressed by lightning impulse voltages.

Make-up of Equivalent Circuit of Grounding System using Water Resistivity in Hemispherical Electrode System (반구형 전극계에서 물의 저항률을 이용한 접지시스템의 등가회로 구성)

  • Lee, Bok-Hee;Choi, Jong-Hyuk;Bae, Sung-Bae
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.8
    • /
    • pp.109-115
    • /
    • 2008
  • A design criterion of grounding systems is commonly based on the ground resistance measured with low frequency in Korea. When lightning surges which have high frequency components are injected into the grounding system, the grounding impedance is great]y different from the static grounding resistance. In order to investigate the effect of water resistivity on the high frequency performance of grounding systems, this paper presents the frequency-dependent admittance using water tank simulating the grounding system in different water resistivities. As a result, because of capacitive effect admittances and conductance are increased with increasing frequency in higher water resistivity of greater than 500[${\Omega}{\cdot}m$]. On the other hand, admittances and conductances are decreased with increasing frequency due to inductive effect in lower water resistivity of less than 500[${\Omega}{\cdot}m$]. The phase difference between the current and voltage increases in the range of 200[kHz] to 5[MHz]. Consequently, frequency-dependent performance of grounding systems is closely related to the soil resistivity, it is necessary to consider the effect of grounding system performance on the frequency and soil resistivity.

Measurement and Analysis of Structural Grounding Effect of Concrete Pole (콘크리트 전주 구조체의 접지효과 측정 및 분식)

  • Choi, Jong-Kee;Kim, Dong-Myoung;Lee, Hyung-Soo;Shim, Keun-Bo;Kim, Kyung-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.1
    • /
    • pp.36-40
    • /
    • 2009
  • Concrete poles(CP) are popular supports for distribution lines. Various types of grounding electrode, such as copper-clad rods, have been used to maintain CP's ground resistance under the required value. The buried part of CP can also have structural grounding effect because of its iron reinforcing rods inside CPs. In this paper, we measured the total ground current injected into CP ground while measuring the ground current splitting to the metal electrode as well as the total injecting current. By this, it was able to measure the ground current splitting to CP structure. Based on the measured results, interrelationship between ground resistance of metal electrodes and current split factor to CP structure was analyzed.

Analysis of the Ground Impedance of Ground Grids Combined with the Carbon Ground Electrodes (탄소접지극이 병설된 접지그리드의 접지임피던스의 해석)

  • Lee, Bok-Hee;Um, Sang-Hyun;Kim, You-Ha;Lee, Kang-Soo;Jeon, Byung-Wook;Choi, Jong-Hyuk
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.36-42
    • /
    • 2013
  • This paper deals with the frequency-dependent ground impedance of ground grids combined with the carbon ground electrodes. Ground grids are generally valid for multipurpose grounding systems as well as lightning protection systems. The carbon ground electrodes may be supplementarily used to reduce the high frequency ground impedance and to improve the transient response to surge currents. The frequency-dependent ground impedances of ground grids combined with or without the carbon ground electrodes were measured and their simulations with due regard to frequency-dependent soil resistivity were implemented by using EMTP program and Matlab modeling. As a consequence, the ground impedance of ground grids combined with the carbon ground electrodes is significantly reduced when the test current is injected at the terminal of the carbon ground electrode. The measured and simulated data for the test ground grids fairly agree with each other. It was found that the proposed method of simulating the frequency-dependent ground impedance is distinguished. The simulation techniques of predicting accurately the ground impedances without actual measurements can be used in the design of grounding systems based on ground grids and the carbon ground electrodes.

Numerical Calculation for Grounding Impedance of a Horizontal Ground Electrode Based on the Electromagnetic Field Theory (전자계 이론을 기반으로 한 수평접지전극의 접지임피던스 수치계산)

  • Lee, Bok-Hee;Cho, Sung-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.2
    • /
    • pp.76-83
    • /
    • 2014
  • This paper deals with the numerical method of calculating the frequency-dependent impedances of grounding electrodes. The proposed electromagnetic field approach is based on the solutions to Maxwell's equations obtained from the method of moment in the frequency domain. In order to evaluate the quality of the proposed simulation method, the frequency-dependent impedances of horizontally-buried ground electrodes were presented. The program for calculating the current distributions and impedances of grounding electrodes was implemented in MATLAB. The grounding impedances of two 10m and 50m long horizontal ground electrodes were measured and simulated in the frequency range from 100Hz to 10MHz for easy analysis and comparison. Also the simulated results were compared with those calculated from a sophisticated computer program CDEGS (HIFREQ module). As a result, the resultant results of frequency-dependent impedances obtained by using the numerical simulation method proposed in this work are in good agreement with experimental data. The validity of the approach techniques was confirmed.

An Analysis Method for the Transient Ground Impedance Using Variable Frequency and Lightning Impulse Current (가변주파수 및 임펄스 전류를 이용한 과도접지임피던스 분석)

  • Eom, Ju-Hong;Cho, Sung-Chul;Lee, Tae-Hyung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.6
    • /
    • pp.100-108
    • /
    • 2008
  • The transient ground impedance depending on configuration, size, and material of grounding electrodes as well as the shapes of impulse currents, has a significant affect on the performance of the grounding system. This paper presents experimental results in regard to the analysis method of transient ground impedance using the lightning impulse and variable frequency currents. Also a new estimation method to replace the effective surge impedance for transient ground impedance was proposed. The ground electrodes used in this experiment are virtual ground electrodes including both resistance and inductance components, carbon ground electrode with 1[m] length, copper electrode with 9[m] length and counterpoise with 40[m] length. Ground impedances using the proposed method were measured respectively. Comparing with the ground impedance using variable frequency current the conventional ground impedance($Z_1$) calculated from the peak values of impulse voltage and impulse current is observed more correct method for evaluating the performance of ground electrode than the effective surge impedance.

Evaluations of Dangerous Voltages around Grounding Electrode using Small-sized Model (축소모델을 이용한 접지전극 주변의 위험전압 평가)

  • Baek, Young-Hwan;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.6
    • /
    • pp.83-88
    • /
    • 2010
  • In this paper, to propose a valid method solving a problem relevant to grounding from actual field data, the experimental results relevant to touch and step voltages and surface potential profiles measured around the real-sized and small-sized grounding electrode models were described. The ground surface potential profiles and dangerous voltages around the concrete pedestals employed in street facilities such as street lamps, traffic signal lamp and controllers as a case study were measured and discussed. The hemispherical cell with a diameter of 1,160[mm] was employed to simulate uniform soil. As a result, the results measured with the small-sized model were in reasonably agreement with the data obtained from the real-sized installation. It was found that the small-sized model test could be employed as a useful means evaluating the dangerous voltages around grounding electrodes installed at the inaccessible areas such as mountains, underground, underwater, and so on.

Characteristics of Transient Ground Impedance of a Scaled Grounding Grid on the High Current Impulse (대전류 임펄스에 대한 소규모 메쉬전극의 과도접지임피던스 특성)

  • Lee, Tae-Hyung;Cho, Sung-Chul;Eom, Ju-Hong;Yoo, Yang-Woo;Lee, Bok-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1418_1419
    • /
    • 2009
  • This paper presents the transient impedance when high current impulse up to 5 kA is applied to a scaled grounding grid in test field. For a realistic analysis of transient impedance on the high current impulse in the ground systems, grounding electrode installed outdoors and impulse current generator was used. The results were discussed based on its voltage and current trace, impulse impedance and V-I curve.

  • PDF