Abstract
In this paper, to propose a valid method solving a problem relevant to grounding from actual field data, the experimental results relevant to touch and step voltages and surface potential profiles measured around the real-sized and small-sized grounding electrode models were described. The ground surface potential profiles and dangerous voltages around the concrete pedestals employed in street facilities such as street lamps, traffic signal lamp and controllers as a case study were measured and discussed. The hemispherical cell with a diameter of 1,160[mm] was employed to simulate uniform soil. As a result, the results measured with the small-sized model were in reasonably agreement with the data obtained from the real-sized installation. It was found that the small-sized model test could be employed as a useful means evaluating the dangerous voltages around grounding electrodes installed at the inaccessible areas such as mountains, underground, underwater, and so on.
본 논문에서는 접지에 관련된 문제를 실제 현장데이터로부터 해결할 수 있는 유용한 방법을 제안하기 위하여 실규모와 축소모델 접지전극 주변에서 측정된 접촉전압, 보폭전압과 표면전위분포에 대한 실험결과를 기술하였다. 사례연구로서 가로등, 교통신호등과 제어기와 같은 도로시설물의 설치에 사용되는 콘크리트 기초좌대 주변의 대지표면전위분포와 위험전압을 측정하고 검토하였다. 균질의 토양을 모의하기 위하여 직경이 1,160[mm]인 반구형 용기를 사용하였다. 그 결과, 축소모델을 이용하여 측정한 결과는 실규모설비에서 얻은 결과와 잘 일치하였으며, 축소모델 실험은 산악, 지하, 수중 등과 같이 접근할 수 없는 장소에 설치된 접지전극 주변의 위험전압을 평가하는 유용한 수단으로 이용될 수 있음이 확인되었다.