Browse > Article
http://dx.doi.org/10.5207/JIEIE.2010.24.6.083

Evaluations of Dangerous Voltages around Grounding Electrode using Small-sized Model  

Baek, Young-Hwan ((주)효성전기안전)
Lee, Bok-Hee (인하대학교 IT공대 전기공학부)
Publication Information
Journal of the Korean Institute of Illuminating and Electrical Installation Engineers / v.24, no.6, 2010 , pp. 83-88 More about this Journal
Abstract
In this paper, to propose a valid method solving a problem relevant to grounding from actual field data, the experimental results relevant to touch and step voltages and surface potential profiles measured around the real-sized and small-sized grounding electrode models were described. The ground surface potential profiles and dangerous voltages around the concrete pedestals employed in street facilities such as street lamps, traffic signal lamp and controllers as a case study were measured and discussed. The hemispherical cell with a diameter of 1,160[mm] was employed to simulate uniform soil. As a result, the results measured with the small-sized model were in reasonably agreement with the data obtained from the real-sized installation. It was found that the small-sized model test could be employed as a useful means evaluating the dangerous voltages around grounding electrodes installed at the inaccessible areas such as mountains, underground, underwater, and so on.
Keywords
Ground rod; Touch voltage; Step voltage; Ground surface potential rise; Real-sized model; Small-sized model test;
Citations & Related Records
Times Cited By KSCI : 2  (Citation Analysis)
연도 인용수 순위
1 이복희, 최충석, 길형준 “반구형 접지모의시스템을 이용한 접지전극 형상에 따른 대지전위상승의 분석“, 전기학회 논문지, Vol.54, No.7, pp.319-325, 2005.   과학기술학회마을
2 B. Thapar and K. K. Puri, “Mesh Potentials in High-Voltage Grounding Grids”, IEEE Trans. on Power Apparatus and System, Vol. PAS-86, No.2, pp.249-254, 1967.   DOI
3 IEEE. Standard Board, “IEEE Guide for Safety in AC Substation Grounding”, IEEE Std 80, pp.23-29, 2000.
4 IEEE Standard Board, “IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System”, IEEE Std 81, pp.24-26, 1983.
5 국토해양부, “도로안전시설 설치 및 관리지침”, pp.33-69, 2003.
6 조선일보 홈페이지, http://www.chosun.com/w21data/.
7 이복희, 이승칠, “접지의 핵심 기초 기술”, 도서출판 의제, pp.69-70, pp.118-124, 1999.
8 이복희, 백영환, 정현욱, “대지구조에 따른 대지표면전위의 분석”, 전기학회 논문지, Vol.56, No.10, pp.1796-1801, 2007.   과학기술학회마을
9 대한전기협회, 내선규정, pp.110-111, 2006.
10 KS C IEC 62305-3, "피뢰시스템 - 제3부 : 구조물의 물리적 손상 및 인명위험", pp.249-268, 2007.