• Title/Summary/Keyword: GIS Spacer

Search Result 59, Processing Time 0.026 seconds

UHF Sensor Development for Partial Discharge Exclusively for Measurement in 25.8kV GIS (25.8kV GIS 부분방전 측정전용 UHF센서 개발)

  • Choi, Mun-Gyu;Cha, Hanju
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.6
    • /
    • pp.1083-1088
    • /
    • 2016
  • 25.8kV GIS part generated by sensors to measure contact an inflow of noise depending on the extent of the measured discharge occurs often not easy. Partial discharge signal measurement sensor suitable for developing a more useful measurements at the scene to this, partial discharge waveform analysis developed a sensor, and to utilize forSensor on the development of the most important is VSWR decided to (voltage standing wave ratio) voltage standing-wave ratio less than 1.5 and decided less than at the full spectrum bands that are measured, this time Return loss, as measured value by absolute criteria 14.0 dB produced the sensor, designed to or more. UHF 1.5~0.5 GHz bandwidth spectrum to be measured in GIS. UHF bands were designed to be able to measure the best signal. Recently, 25.8kV GIS production company has been increasing variety of GIS were made open spacer in partial discharge in accordance with the not very easy to detect the signal. The sensor is designed height of four cm external spacer is attachment GIS in an influx of outside noise measurement, and be so manufactured as to facilitate the least we've done. Also, since partial discharge which occur can measure the frequency of the 170kV GIS external partial-discharge signals that occur at the scene of insulation applied to the spacer. Features, and also derived good results using global positioning. Also measured discharge point about sensors that are stable and the reliability of the development and local substation equipment failure occurring signal analysis through the discharge for the prevention of widely. There should be to believe that used.

AC Electrical and Mechanical Properties of Epoxy-Nano-Microsilica Mixed Composites for Eco-Friendly GIS Spacer (친환경 GIS Spacer용, 에폭시-나노-마이크로실리카 혼합 콤포지트의 교류 전기적, 기계적 특성)

  • Park, Jae-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.9
    • /
    • pp.1181-1188
    • /
    • 2018
  • In order to develop new insulating materials for GIS Spacer using environmentally friendly insulating gas, three kinds of dispersed liquid nano composites of solid epoxy /nano layered silicate filled material were prepared. And the epoxy/nano/micro silica composite was prepared by mixing epoxy/nano 3 phr dispersion/4 kinds of filler contents(40,50,60, 70wt%). The electrical insulation breakdown strengths of the nano and nano/micro mixed composites were evaluated by using 8 kinds of samples including the original epoxy. The mechanical tensile strength of the epoxy / nano / micro silica composite were evaluated, also. The TEM was measured to evaluate the internal structure of nano/micro composites. As a result, it was confirmed that the layered silicate nano particles was exfoliated through the process of inserting epoxy resin between silicate layers and the layers. In addition, dispersion of nano / micro silica resulted in improvement of electrical insulation breakdown strength with increase of filling amount of dense tissue with nanoparticles inserted between microparticles. In addition, the tensile strength showed a similar tendency, and as the content of microsilica filler increased, the mechanical improvement was further increased.

Study on Electrical and Mechanical Properties of High Viscosity Solid Epoxy / Silica and Alumina Composite (고점도형 고상에폭시/실리카와 알루미나 콤포지트의 전기적, 기계적 특성연구)

  • Park, Jae-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.67 no.10
    • /
    • pp.1330-1337
    • /
    • 2018
  • In this study, 40, 50, 60, and 70 wt% filler dispersed samples were prepared for the current GIS Spacer or environmentally friendly GIS. In the AC electrical breakdown, EMSC and EMAC decreased with increasing filler content, and EMSC showed better breakdown strength than EMAC. The mechanical properties such as tensile strength and flexural strength of EMSC and EMAC were also increased with increasing filler content. In addition, EMSC results in better mechanical properties than EMAC. The reason for this is considered to be one in which the influence of the interface is important.

Design and Fabrication of an Electronic Voltage Transformer (EVT) Embedded in a Spacer of Gas Insulated Switchgears (가스절연개폐장치의 스페이서 내장형 전자식 변압기의 설계 및 제작)

  • Lim, Seung-Hyun;Kim, Nam-Hoon;Kim, Dong-Eon;Kim, Seon-Gyu;Kil, Gyung-Suk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.35 no.4
    • /
    • pp.353-358
    • /
    • 2022
  • Bulky iron-core potential transformers (PT) are installed in a tank of gas insulated switchgears (GIS) for a system voltage measurement in power substations. In this paper, we studied an electronic voltage transformer (EVT) embedded in a spacer for miniaturization, eco-friendliness, and performance improvement of GIS. The prototype EVT consists of a capacitive probe (CP) that can be embedded in a spacer and a voltage Follower with a high input and a low output impedance. The CP was fabricated in the form of a Flexible-PCB to acquire the insulation performance and to withstand vibration and shock during operation. Voltage ratio of the prototype EVT is about 42,270, and the frequency bandwidth of -3 dB ranges from 0.33 Hz to 3.9 MHz. The voltage ratio error evaluated at about 6%, 12% and 18% of the rated voltage of 170 kV was 0.32%, and the phase error was 12.9 minutes. These results were within the accuracy for the class 0.5 specified in IEC 60044-7 and satisfy even in ranges from 80% to 120% of the rated voltage. If the prototype EVT replaces the conventional iron-core potential transformer, it is expected that the height of the GIS could be reduced by 11% and the amount of SF6 will be reduced by at least 10%.

Design and Fabrication of an LPVT Embedded in a GIS Spacer (GIS 스페이서 내장형 저전력 측정용 변압기의 설계 및 제작)

  • Seung-Gwan Park;Gyeong-Yeol Lee;Nam-Hoon Kim;Cheol-Hwan Kim;Gyung-Suk Kil
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.37 no.2
    • /
    • pp.175-181
    • /
    • 2024
  • In electrical power substations, bulky iron-core potential transformers (PTs) are installed in a tank of gas-insulated switchgear (GIS) to measure system voltages. This paper proposed a low-power voltage transformer (LPVT) that can replace the conventional iron-core PTs in response to the demand for the digitalization of substations. The prototype LPVT consists of a capacitive voltage divider (CVD) which is embedded in a spacer and an impedance matching circuit using passive components. The CVD was fabricated with a flexible PCB to acquire enough insulation performance and withstand vibration and shock during operation. The performance of the LPVT was evaluated at 80%, 100%, and 120% of the rated voltage (38.1 kV) according to IEC 61869-11. An accuracy correction algorithm based on LabVIEW was applied to correct the voltage ratio and phase error. The corrected voltage ratio and phase error were +0.134% and +0.079 min., respectively, which satisfies the accuracy CL 0.2. In addition, the voltage ratio of LPVT was analyzed in ranges of -40~+40℃, and a temperature correction coefficient was applied to maintain the accuracy CL 0.2. By applying the LPVT proposed in this paper to the same rating GIS, it can be reduced the length per GIS bay by 11%, and the amount of SF6 by 5~7%.

Electric Field Analysis Simulation and Improvement of Breakdown Characteristics on the GIS Spacer (GIS 스페이서의 전계해석 시뮬레이션 및 파괴전압 특성 개선)

  • Ryu, Sung-Sic;Park, Jae-Do;Kwak, Hee-Ro
    • Proceedings of the KIEE Conference
    • /
    • 2000.11c
    • /
    • pp.540-542
    • /
    • 2000
  • This paper describes the particle-initiated breakdown characteristics of various spacers, which have a ribbed surface, in the presence of a metallic particle. The particle was attached on the surface of each spacer. The breakdown voltages were measured by changing the length and thickness of the rib. Also the electrical field analyses were performed. As a result, the breakdown voltage of the spacer with two ribs was highest, and it was varied by the length and the thickness of the rib. Especially, in case of the rib with round edge, the breakdown voltage was higher than that with rectangular edge, which complied with the result through the field analysis.

  • PDF

Electric Field Analyses and Breakdown Voltage Characteristics on the Improved Spacers for GIS (개선된 GIS 스페이서의 전계해석 및 파괴전압특성)

  • Ryu, Sung-Sic;Shin, Dong-Seok;Hwak, Hee-Ro;Kim, Kyung-Wha
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.1921-1923
    • /
    • 2000
  • This paper describes the particle-initiated breakdown characteristics of various spacers, which have a ribbed surface, in the presence of a metallic particle. The particles was attached on the surface of each spacer. The breakdown voltages were measured by changing the particle position on the spacer, the length and thickness of the rib. Also the electrical field analyses were performed. As a result, the breakdown voltage of the spacer with two ribs was highest, and it was varied by the length and the thickness of the rib. Especially, in case of the rib with round edge the breakdown voltage was higher than that with rectangular edge, which complied with the result through the field analysis.

  • PDF

Analysis of the Causes of Accidents Related to 3 Phase 170 kV Gas Insulated Switchgears(GIS) and Preventive Measures (3상 170 kV 가스절연개폐장치(GIS)의 사고 원인 분석 및 예방 대책)

  • Choi, Chung-Seog
    • Journal of the Korean Society of Safety
    • /
    • v.26 no.4
    • /
    • pp.41-46
    • /
    • 2011
  • The purpose of this paper is to analyze the causes of accidents related to the 3 phase 170 kV gas insulated switchgear of a power system collected from accident sites to secure data for the prevention of similar accidents and provide important points of view regarding diagnosis for the prevention of accidents involving gas insulated switchgears. The analysis results of the causes of accidents involving gas insulated switchgears showed deformation of the manipulation lever installed at the S-phase, disconnection of the insulation rod connection, melting of the upper conductor, a damaged tulip, damage to the lower spacer and the spacer at the breaker, etc. It is believed from this result that the potential for accidents has expanded due to accumulated energy as a result of repeated deterioration. The carbonization depth of a GIS was formed near the screw (T2, T3) used to secure the lower pole of the S-phase tulip. It is not known what has caused the screws to be extruded and melted. However, it is thought that an unbalanced electromagnetic force, micro-discharge, surface discharge, etc., have occurred at that point. In addition, even though 16 years have passed since its installation, there was no installation defect, act of arson, accidental fire, etc. General periodical inspection and diagnosis failed to find the factors causing the accidents. As a system contained in a closed metal container, it has a high risk factor. Therefore, it is necessary to design, install and operate a GIS in accordance with the standard operational procedure (SOP). In addition, it is necessary to apply conversion technology for periodical SF6 gas analysis and precision safety diagnosis. It is expected that tracking and managing these changes in characteristics by recording the results on the history card will provide a significant accident prevention effect.

Investigation on Electric Field Optimization Algorithm of Spacer in Gas Insulated System (가스절연 원통형 관로 내의 스페이서 전계 최적화 알고리즘에 관한 연구)

  • Kim, Ung-Sik;Min, Seok-Won
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.51 no.3
    • /
    • pp.115-120
    • /
    • 2002
  • This Paper describes an algorithm for the design of axi-symmetrical spacer under specified field conditions. The electric field alas been calculated by combination method of Integral Equation Method(IEM) and Charge Simulation Method(CSM). The contour of spacer is represented with NURB(Non-Uniform Rational B-spline) curve of which effectiveness has been proved. This algorithm introduces a design process in the aspect of electrical field, when a spacer in airtight cylinder is designed. Also various field conditions for obtaining optical shapes have been proposed. Due to the algorithm, the entire process shows a stable convergence. Both tangential and total electrical field are taken into consideration as specified field criteria.

A study on the UHF PD measuring technique for GIS with a metal flange around insulating spacer (스페이서에 Metal flange가 있는 GIS에서의 UHF PD 측정 기술 연구)

  • Kang, W.J.;Lee, C.J.;Kang, Y.S.;Park, J.B.;Lee, H.C.;Park, J.W.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1638-1640
    • /
    • 2003
  • In the recent years, UHF PD measuring technique for detecting partial discharges was proved the effective method for Gas Insulated Switchgear (GIS). However, in case of GIS with a metal flange around insulating spacer, UHF PD measurement using typical external UHF PD sensor is difficult. In this paper, a novel hole-type UHF PD sensor based on Archimedean spiral antenna theory has been proposed and realized. All spacers with metal flange have small hole in order to inject epoxy. Using the novel hole-type UHF PD sensor, it makes detection possible to PD signal that are emitted through the epoxy injection hole. Additionally, the measuring characteristic of UHF PD signals from several artificial defects in GIS and the novel ${\Phi}$-f-q pattern analysis technology are discussed.

  • PDF