Electric Field Analysis Simulation and Improvement of Breakdown Characteristics on the GIS Spacer

GIS 스페이서의 전계해석 시뮬레이션 및 파괴전압 특성 개선

  • Published : 2000.11.25

Abstract

This paper describes the particle-initiated breakdown characteristics of various spacers, which have a ribbed surface, in the presence of a metallic particle. The particle was attached on the surface of each spacer. The breakdown voltages were measured by changing the length and thickness of the rib. Also the electrical field analyses were performed. As a result, the breakdown voltage of the spacer with two ribs was highest, and it was varied by the length and the thickness of the rib. Especially, in case of the rib with round edge, the breakdown voltage was higher than that with rectangular edge, which complied with the result through the field analysis.

Keywords