• Title/Summary/Keyword: Fault insertion

Search Result 40, Processing Time 0.035 seconds

A Study on Correction of the Protective Relay Equipped in the Dedicated Line Used for Connecting Distributed Generators to Power Network (분산전원 계통 연계 전용선로에 설치된 보호 계전기의 정정에 관한 연구)

  • Jeong, Jong-Chan;Jang, Sung-Il;Choi, Don-Man;Kim, Kwang-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2002.11b
    • /
    • pp.141-144
    • /
    • 2002
  • This paper describes the correction of the protective relay equipped in the dedicated line used for connecting distributed generators (DG) to power grid. The fault current measured in a relaying point might be changed according to the fault conditions. Generally, the fault current of the line to line fault or the line to ground fault at the dedicated line is much higher than the protective set value due to the large fault level. However. when the high impedance fault is occurred in the dedicated line, we may not detect it because its fault level can be lower than the generating capacity of DG. And, the protective relay with conventional set value may generate a trip signal for insertion of DG due to the large transient characteristics of generators. Through the various simulations such as the fault in the dedicated line and the insertion of DG, we show that it would be necessary to modify the protective relay set value for detecting the high impedance fault occurred in the dedicated line and for preventing the mis-operation of protective relay caused by the insertion of DG.

  • PDF

A Decision Method for the Optimal Insertion Resistance of a Superconducting Fault Current Limiter with Reduction of an Asymmetric Fault Current (비대칭 고장전류 저감 기능을 갖는 초전도 한류기의 최적 저항 결정 방안)

  • Kim, Chang-Hwan;Kim, Kyu-Ho;Rhee, Sang-Bong
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.64 no.1
    • /
    • pp.57-63
    • /
    • 2015
  • Fault currents characteristics contain decaying DC offset. First cycle peak value of fault currents is higher than steady-state fault current value. These characteristics can affect the operation of protective device. To reduce the asymmetric fault current, the method using a series connection of two hybrid-type Superconducting Fault Current Limiter(SFCL) components, an auxiliary SFCL and a main SFCL, has been proposed. The auxiliary SFCL limits the first half cycle fault current, while main SFCL limits the steady state fault currents. This paper proposed a decision method of the optimal insertion resistance of auxiliary and main SFCL components. To verify the effectiveness of proposed scheme, the various simulations are performed by using Electromagnetic Transient Program(EMTP).

Operation sequence verification of the power converter by fault insertion (Fault Insertion을 통한 전력변환장치의 동작 시퀀스 검증)

  • Kim, Tae-Hoon;Song, Hyun-Sik;Shin, Dong-Hyun;Lee, Back-Haeng;Lee, Chan-Song;Choi, Won-Kyu
    • Proceedings of the KIPE Conference
    • /
    • 2013.11a
    • /
    • pp.196-197
    • /
    • 2013
  • 친환경 차량의 필수장치로 사용되는 OBC(On Board Charger) 및 LDC(Low DC-DC Converter)는 시스템 성능은 물론 하드웨어적인 신뢰성과 더불어 차량에서 발생할 수 있는 다양한 Fault로부터 차량과 운전자를 보호할 수 있는 안정성과 신뢰성을 확보하는 것이 요구된다. OBC/LDC 개발에 있어 시제품을 제작하여 성능 검증과 하드웨어 신뢰성을 확보하는 것은 현재의 개발 프로세서로 충분하지만 차량에서 발생하는 다양한 Fault 상황에 대한 강건성 확보는 실차에 탑재하여 검증하지 않고서는 뚜렷한 검증 방법이 없는 실정이다. 이에 따라 본 논문에서는 차량에서 발생될 수 있는 다양한 Fault 상황을 시뮬레이터로 모사하여, 이러한 Fault를 전력변환장치에 인위적으로 주입시킨 뒤 전력변환장치가 정상적으로 동작하는지 분석한다. 이를 통해 실차에 탑재하지 않고 전력변환시스템의 신뢰성을 검증하기 위한 방안을 제시한다.

  • PDF

A Study on the Improved Protective Relaying Algorithm Applied in the Linked System Interconnecting Wind Farm with the Utilities (풍력발전단지 연계 전용선로 보호계전방식의 향상에 대한 연구)

  • 장성일;김광호;권혁완;김대영;권혁진
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.12
    • /
    • pp.675-683
    • /
    • 2003
  • This paper describes the correction strategy of an overcurrent relay applied in the linked line for interconnecting wind farm with utility power networks in order to improve the capability of a fault detection. The fault current measured in a relaying point might vary according to the fault conditions. Generally, the current of the line to line fault or the line to ground fault in the linked line is much higher than the set value of protective relay due to the large fault level. However, when the high impedance fault occurs in the linked line, we can't detect it by conventional set value because its fault level may be lower than the generating capacity of wind farm. And, the protective relay with conventional set value may generate a trip signal for the insertion of wind turbine generators due to the large transient characteristics. In order to solve above problems and improve protective relaying algorithms applied in the linked line, we propose a new correction strategy of the protective relay in the linked line. The presented method can detect the high impedance fault which can't be detected by conventional relay set value and may prevent the mis-operation of protective relay caused by the insertion of wind farm.

Chosen Message Attack on the RSA-CRT Countermeasure Based on Fault Propagation Method (오류 확산 기법에 기반한 RSA-CRT 대응책에 대한선택 메시지 공격)

  • Baek, Yi-Roo;Ha, Jae-Cheol
    • Journal of the Korea Institute of Information Security & Cryptology
    • /
    • v.20 no.3
    • /
    • pp.135-140
    • /
    • 2010
  • The computation using Chinese Remainder Theorem in RSA cryptosystem is well suited in the digital signature or decryption processing due to its low computational load compared to the case of general RSA without CRT. Since the RSA-CRT algorithm is vulnerable to many fault insertion attacks, some countermeasures against them were proposed. Among several countermeasures, Yen et al. proposed two schemes based on fault propagation method. Unfortunately, a new vulnerability was founded in FDTC 2006 conference. To improve the original schemes, Kim et al. recently proposed a new countermeasure in which they adopt the AND operation for fault propagation. In this paper, we show that the proposed scheme using AND operation without checking procedure is also vulnerable to fault insertion attack with chosen messages.

Experimental Analysis of Optical Fault Injection Attack for CRT-RSA Cryptosystem (CRT-RSA 암호시스템에 대한 광학적 오류 주입 공격의 실험적 연구)

  • Park, Jea-Hoon;Moon, Sang-Jae;Ha, Jae-Cheol
    • Journal of the Korea Institute of Information Security & Cryptology
    • /
    • v.19 no.3
    • /
    • pp.51-59
    • /
    • 2009
  • The CRT-RSA cryptosystem is very vulnerable to fault insertion attacks in which an attacker can extract the secret prime factors p, q of modulus N by inserting an error during the computational operation on the cryptographic chip. In this paper, after implementing the CRT-RSA cryptosystem, we try to extract the secret key embedded in commercial microcontroller using optical injection tools such as laser beam or camera flash. As a result, we make sure that the commercial microcontroller is very vulnerable to fault insertion attacks using laser beam and camera flash, and can apply the prime factorization attack on CRT-RSA Cryptosystem.

A Study on the Phonological Fault in the News Subtitle (뉴스 자막의 발음 오표기 연구)

  • Lee Dong-Seok
    • Proceedings of the KSPS conference
    • /
    • 2006.05a
    • /
    • pp.85-88
    • /
    • 2006
  • Generally the news subtitle is considered as be free of fault. But actually it has committed a fault in many respects. Among these I made a special study of phonological faults; alternation of graphemes, insertion of graphemes, deletion of graphemes and the orthography of loanwords. It is very surprising that the news subtitle has many faults against Korean orthography, We must try to get rid of the faults in the news subtitle.

  • PDF

A Decision Scheme for Optimal Insertion Resistance in Superconducting Fault Current Limiter for Reduction of the Transformer Inrush Current (여자돌입전류 제한용 초전도한류기의 최적투입저항 결점)

  • Seo, H.C.;Rhee, S.B.
    • Proceedings of the KIEE Conference
    • /
    • 2008.11a
    • /
    • pp.37-39
    • /
    • 2008
  • This paper suggests a decision scheme for optimal insertion resistance in an Superconducting Fault Current Limiter (SFCL) application to reduce the transformer inrush current. This scheme and the SFCL model are implemented using Electromagnetic Transient Program (EMTP). We determine the optimal SFCL resistance by EMTP simulation, and this value is applied to model the SFCL by EMTP. The simulation results show the validity and effectiveness of the suggested scheme and the ability of a SFCL to reduce the inrush current.

  • PDF

Advanced Protective Coordination Schemes of Utility Interconnected Cogeneration Systems (배전계통에 연계된 열병합발전 시스템의 개선된 보호협조 방안에 관한 연구)

  • Choe, Jun-Ho;Jeong, Seong-Gyo;Chu, Dong-Uk;Kim, Nak-Gyeong;Son, Hak-Sik;Kim, Jae-Cheol
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.49 no.6
    • /
    • pp.280-288
    • /
    • 2000
  • Recently, there has been growing interest in utilizing cogeneration(COGN) systems with a high-energy efficiency due to the increasing energy consumption and the lacking of energy resource. But an insertion of COGN system to existing power distribution system can cause several problems such as voltage variations, harmonics, protective coordination, increasing fault current etc, because of reverse power of COGN, especially in protective coordination. A study on a proper coordination with existing one is being required. The existing power distribution system is operated with radial type by one source and protection system is composed based on unidirectional power source. But an Insertion of COGN system to power distribution system change existing unidirectional power source system to bidirectional power source. Therefore, investigation to cover whole field of power distribution system must be accomplished such as changing of protection devices rating by increasing fault current, reevaluation of protective coordination. In this paper, simulation using PSCAD/EMTDC was accomplished to analyze effect of COGIN on distribution fault current. Also, the existing protection system of 22.9[kV] power distribution system and customers protection system to protect of COGIN was analyzed and the study on protective coordination between of two protection system accomplished.

  • PDF

Fault location identification and protective coordination schemes presentation of distribution system interconnected Distributed Generation (분산전원이 연계된 배전계통의 사고지점 확인 및 보호협조 방안 제시)

  • Choi, Dong-Man;Choi, Joon-Ho;Ro, Kyoung-Soo;Moon, Seung-Il;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2005.11b
    • /
    • pp.313-315
    • /
    • 2005
  • Recently There has been growing interest in new renewable energy systems with high-energy efficiency due to the increasing energy consumption and environmental pollution problems. But an insertion of new distributed generation to existng power distribution systems can cause several problems such as voltage variations, harmonics, protective coordination, increasing fault current etc, because of reverse power. This paper was applied to fault location defecting a method as each Relay sensing fault current value and carried out short-circuit analysis by MATLAB and PSCAD/EMTDC programs and identity the faulted section o f22.9[kV] distribution system interconnected a large number of distributed generation. The existing protection system of 22.9[kV] power distribution system analyzed and the study on protective coordination recloser and Sectionalzer accomplished

  • PDF